Extended functions
9.3.1
Technology controller
Description
The "technology controller" function module allows simple control functions to be
implemented, e.g.:
● Level control
● Temperature control
● Dancer roll position control
● Pressure control
● Flow control
● Simple control without higher-level control
● Tension control
The technology controller features:
● Two scalable setpoints
● Scalable output signal
● Separate fixed values
● Integrated motorized potentiometer
● The output limits can be activated and deactivated via the ramp-function generator.
● The D component can be switched to the system deviation or actual value channel.
● The motorized potentiometer of the technology controller is only active when the drive
pulses are enabled.
The technology controller is designed as a PID controller, whereby the differentiator can be
switched to the control deviation channel or the actual value channel (factory setting).
The P, I, and D components can be set separately.
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A