Advertisement

Commissioning
5.3 Procedure for commissioning with STARTER
Note
Motor reactor
If a motor reactor (option L08) is being used, the option selection must be activated,
otherwise the closed-loop motor control will not be able to operate in an optimum fashion.
Note
Check option selection
Check your options carefully against the options specified on the type plate.
Since the wizard establishes internal interconnections on the basis of the options selected,
you cannot change the selected options by clicking < Back.
If you make an incorrect entry, delete the entire drive unit from the project navigator and
create a new one.
⇒ Check your options carefully and then click Continue >
210
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A