Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
To enable the digital inputs (DI) to function, terminal M2 must be connected.
This is achieved through one of the following measures:
1. Also route the reference ground of the digital inputs.
2. A jumper to terminal M. (Note: This removes the electrical isolation for these digital
inputs.)
Note
If the 24 V supply is briefly interrupted, then the digital outputs are deactivated during this
time.
X126: PROFIBUS connection
The PROFIBUS is connected by means of a 9-pin SUB D socket (X126). The connections
are electrically isolated.
Table 4- 12
PROFIBUS interface X126
Pin
1
-
2
M24_SERV
3
RxD/TxD–P
4
CNTR–P
5
DGND
6
VP
7
P24_SERV
8
RxD/TxD–N
9
-
A teleservice adapter can be connected to the PROFIBUS interface for remote diagnostics.
The power supply for the teleservice (terminals 2 and 7) can have a load of up to 150 mA.
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Signal name
Not assigned
Power supply for teleservice, ground
Receive/transmit data P (B)
Control signal
PROFIBUS data reference potential
Supply voltage plus
Power supply for teleservice, + (24 V)
Receive/transmit data N (A)
Not assigned
Meaning
Electrical installation
4.9 Signal connections
Range
0 V
RS485
TTL
5 V ± 10%
24 V (20.4 ... 28.8 V)
RS485