Electrical installation
4.10 Other connections
NOTICE
Damage to the dv/dt filter compact by exceeding the maximum pulse frequency
The maximum permissible pulse frequency when using a dv/dt filter compact is 2.5 kHz.
The dv/dt filter compact can be damaged if the pulse frequency is exceeded.
• When using the dv/dt filter compact, operate the Motor Module with a maximum pulse
NOTICE
Damage to the dv/dt filter compact if it is not activated during commissioning
The dv/dt filter compact may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter compact during commissioning using parameter p0230 = 2.
NOTICE
Damage to the dv/dt filter compact if a motor is not connected
dv/dt filters compact which are operated without a motor being connected can be damaged
or destroyed.
• Never operate a dv/dt filter compact connected to the Motor Module without a connected
Note
Setting pulse frequencies
It is permissible to set pulse frequencies in the range between the rated pulse frequency and
the relevant maximum pulse frequency when a dv/dt filter compact plus Voltage Peak Limiter
is deployed. "Current derating as a function of the pulse frequency" of the converter must be
observed here (refer to the Technical data).
Commissioning
During commissioning, the dv/dt filter compact plus Voltage Peak Limiter must be logged on
using STARTER or the AOP30 operator panel (p0230 = 2).
Note
Reset when establishing the factory setting
When the factory settings are restored, parameter p0230 is reset.
The parameter must be reset if the system is commissioned again.
120
frequency of 2.5 kHz.
motor.
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A