Example 2: Writing Parameters (Multi-Parameter Request) - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Evaluate response
Table 6- 23
Parameter response
Response header
Parameter value
Information about the parameter response:
● Request reference mirrored:
This response belongs to the request with request reference 25.
● Response identifier:
01 hex → Read request positive, values available starting from 1st value
● Request reference mirrored:
The values correspond to the values from the request.
● Format:
06 hex → Parameter values are in the unsigned16 format.
● Number of values:
08 hex → 8 parameter values are available.
● 1st value ... 8th value:
In the fault buffer of drive 2, a fault is only entered in the 1st value.
6.7.4.4

Example 2: Writing parameters (multi-parameter request)

Preconditions
● The PROFIdrive controller has been commissioned and is fully operational.
● PROFIdrive communication between the controller and the device is operational.
● The controller can read and write data sets in conformance with PROFINET/PROFIBUS.
● Special requirements for this example:
Control mode: Vector control (with extended setpoint channel)
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Parameter response
Request reference mirrored =
25 hex
Axis mirrored = 02 hex
Format = 06 hex
1st value = 1355 dec
2nd value = 0 dec
...
8th value = 0 dec
6.7 Communication according to PROFIdrive
Response ID = 01 hex
Number of parameters =
01 hex
Number of values = 08 hex
Operation
Offset
0 + 1
2 + 3
4 + 5
6
8
...
20
333