Siemens SINAMICS G150 Operating Instructions Manual page 595

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

LED
Color
COM
---
PROFIdrive cyclic
operation
Green
Red
OPT
---
(OPTION)
Green
Red
RDY and COM
Red
RDY and OPT
Orange
Any individual behaviors of the LED OPT are described at the respective Option Board.
1)
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
State
Description
OFF
Cyclic communication is not (yet) running.
Note:
The PROFIdrive is ready for communication when the Control Unit
is ready for operation (see LED RDY).
Continuous light
Cyclic communication is taking place.
0.5 Hz flashing
Cyclic communication has still not been fully established.
light
Possible causes:
- The controller is not transmitting any setpoints.
- In isochronous mode, the controller did not send a Global Control
or it sent a defective Global Control (GC).
0.5 Hz flashing
PROFIBUS master is sending incorrect parameter assign-
light
ment/configuration
2 Hz flashing light
Cyclic bus communication has been interrupted or could not be
established.
OFF
Electronic power supply missing or outside permissible tolerance
range.
The component is not ready for operation.
The Option Board is missing or an associated drive object has not
been created.
Continuous light
Option board is ready.
0.5 Hz flashing
Depends on the option board used
light
Continuous light
Depends on the option board used
0.5 Hz flashing
Depends on the option board used
light
2 Hz flashing light
This component has at least one fault.
The option board is not ready (e.g., after switching on).
2 Hz flashing light
Bus error - communication has been interrupted.
0.5 Hz flashing
The firmware of the connected option board is being updated.
light
Diagnosis/faults and alarms
10.2 Diagnosis
.
1)
.
1)
.
1)
595

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents