Maintenance and servicing
11.4 Replacing components
Danger to life due to electric shock when using unsuitable fuses
If unsuitable fuses are used, an electric shock can cause severe injury or death.
• Use only fuses specified in the spare parts list.
11.4.11

Replacing the cabinet operator panel

1. Switch the unit into a no-voltage condition.
2. Open the cabinet.
3. Disconnect the power supply and communications line on the operator panel.
4. Release the fastenings on the operator panel.
5. Remove the operator panel.
6. Install the new operator panel.
7. Carry out any other work by reversing the sequence.
11.4.12
Replacing the Backup Battery for the Cabinet Operator Panel
Table 11- 2
Type
Manufacturer
Nominal capacity
Self-discharge at 20 °C
Service life (in backup mode)
Service life (in operation)
Replacement
1. Switch the unit into a no-voltage condition.
2. Open the cabinet.
3. Disconnect the 24 V DC power supply and communications line on the operator panel.
4. Open the cover of the battery compartment.
5. Remove the old battery.
6. Insert the new battery.
7. Close the cover of the battery compartment.
8. Reconnect the 24 V DC power supply and communications line.
9. Close the cabinet.
638
WARNING
Technical specifications of the backup battery
CR2032 3 V lithium battery
Maxell, Sony, Panasonic
220 mAh
1 %/year
> 1 year at 70 °C; >1.5 years at 20 °C
> 2 years
Operating Instructions, 07/2016, A5E03347396A