Communication Via Modbus Tcp - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

6.12

Communication via MODBUS TCP

6.12.1
Overview
The Modbus protocol is a communication protocol based on a master/slave architecture.
Modbus offers three transmission modes:
● Modbus ASCII - via a serial interface
data in the ASCII code. The data throughput is lower compared to RTU.
● Modbus RTU - via a serial interface
data in the binary format. The data throughput is greater than in ASCII code.
● Modbus TCP - via Ethernet
data as TCP/IP packages. TCP port 502 is reserved for Modbus TCP.
With the Control Unit CU320-2, only transfer type "Modbus TCP" is available.
Modbus functionality
Process data and parameters are accessed via the Modbus register.
● Process data: 40100 - 40119
● Drive data: 40300 - 40522
● All parameters via DS47: 40601 - 40722
Modbus TCP always provides a basic Ethernet functionality, which corresponds to the
functionality of Ethernet interface X127:
● Commissioning access for STARTER with S7 protocol
● DCP to set the IP address etc.
● SNMP for identification
General information about communication
Communication with Modbus TCP runs via the Ethernet interfaces:
● X150:
For Modbus TCP with a CU320-2 PN.
● X1400:
For Modbus TCP with a CU320-2 PN or a CU320-2 DP via a CBE20.
Precisely one Modbus connection can be established. A simultaneous connection via
interfaces X150 and X1400 is rejected, and is acknowledged using Alarm A08555.
However, you can use one interface for Modbus TCP, and the other as PROFINET interface.
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
6.12 Communication via MODBUS TCP
Operation
397

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents