Other Connections - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Electrical installation

4.10 Other connections

X542: 2 relay outputs (two-way contact)
Table 4- 25
Max. connectable cross-section: 2.5 mm²
DO: digital output, NO: normally-open contact, NC: normally-closed contact, COM: mid-position
1)
contact
Depending on the parameterization and the supply voltage (P24) of the TM31
2)
Note
Additional protective conductor
If 230 V AC is applied to the relay outputs, the Terminal Module must also be grounded via a
6 mm² protective conductor.
4.10
Other connections
Depending on the options installed, further connections have to be established, for example,
dv/dt filter plus Voltage Peak Limiter, connection for external auxiliary equipment,
EMERGENCY OFF button, cabinet illumination with service socket, anti-condensation
heating for cabinet, contactor combination (EMERGENCY OFF / EMERGENCY STOP),
thermistor motor protection unit, braking unit, PT100 evaluation unit, insulation monitor,
communication modules, encoder evaluator, and NAMUR option.
Detailed information on connecting individual options with interfaces can be found on the
customer DVD supplied with the device.
118
Terminal block X542
Terminal
Designation
1
DO 0.NC
2
DO 0.COM
3
DO 0.NO
4
DO 1.NC
5
DO 1.COM
6
DO 1.NO
1)
Contact type: Changeover contact max. load current: 8 A
Max. switching voltage: 250 V
Max. Switching capacity at 250 V
Max. Switching capacity at 250 V
Max. Switching capacity at 30 V
Required minimum current: 100 mA
Output delay: ≤ 20 ms
Overvoltage category: Class II acc. to EN 60664-1
Operating Instructions, 07/2016, A5E03347396A
Technical data
. 30 V
AC
DC
: 2000 VA (cosϕ = 1)
AC
750 VA (cosϕ = 0.4)
AC:
: 240 W (resistive load)
DC
2)
Converter cabinet units

Hide quick links: