Several variations of the V/f characteristic exist, which are listed in the following table.
Table 7- 1
p1300 V/f characteristics
Parameter
Meaning
value
0
Linear characteristic
1
Linear characteristic
with flux current
control (FCC)
2
Parabolic character-
istic
3
Programmable char-
acteristic
4
Linear characteristic
and ECO
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Standard with variable voltage boost
Characteristic that compensates for voltage
losses in the stator resistance for static /
dynamic loads (flux current control FCC).
This is particularly useful for small motors,
since they have a relatively high stator re-
sistance.
Characteristic that takes into account the
motor torque curve (e.g. fan/pump).
Quadratic characteristic (f² characteristic)
Energy saving because the low voltage
also results in small currents and losses.
Characteristic that takes into account the
motor/machine torque characteristic.
Characteristic (see parameter value 0) and Eco mode at constant operating point.
At constant operating point, the efficiency is optimized by varying the voltage.
Active slip compensation is necessary here; the scaling must be set so that the
slip is fully compensated (p1335 = 100%).
Setpoint channel and closed-loop control
Application / property
7.3 V/f control