Slip Compensation - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Note
Automatic setting
When p1349 = 0, the changeover limit is automatically set to 95% of the rated motor
frequency, but only up to 45 Hz.
Function diagram
FP 6310
Parameters
• r0066
• r0078
• p1338
• p1339
• p1349
7.3.3

Slip compensation

Description
Slip compensation essentially keeps the speed of induction motors constant irrespective of
the load (M
When the load is increased from M
so that the resulting frequency and thus also the motor speed remain constant. For a
decrease in the load from M
accordingly.
For p1300 = 4 and 7 (V/f controllers with ECO), the slip compensation must be activated to
ensure correct operation.
For p1300 = 5 and 6 (textiles) the slip compensation is internally disabled in order to be able
to precisely set the output frequency.
If a motor holding brake is applied, a setting value can be specified at the slip compensation
output via p1351. If parameter p1351 > 0 then the slip compensation is switched on
automatically (p1335 = 100%).
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Resonance damping and slip compensation
Output frequency
torque-generating actual current value
V/f control resonance damping gain
V/f control resonance damping filter time constant
V/f control resonance damping maximum frequency
or M
).
1
2
to M
2
1
Setpoint channel and closed-loop control
to M
, the setpoint frequency is increased automatically
1
2
, the setpoint frequency is automatically decreased
7.3 V/f control
435