6.6 Control via the operator panel
6.6.3

Parameterization menu

You can adjust the device settings in the Parameterization menu.
The drive software is modular. The individual modules are called DOs ("drive objects").
The following DOs are available in the SINAMICS G150:
• CU:
• B_INF:
• VECTOR:
• TM31:
• TM150:
Parameters with identical functions may exist with the same parameter number in more than
one DO (e.g. p0002).
The AOP30 is used for operating devices that comprise more than one drive so that attention
is focused on one drive (i.e. the "current" drive). The switchover is made in the main menu.
The corresponding function key is labeled "Drive."
This drive determines the following:
● Operation screen
● Fault and alarm displays
● The controller (ON, OFF, ...) of a drive
Depending on your requirements, you can choose between two AOP display types:
1. All parameters
All the parameters present in the device are listed here. The DO to which the currently
selected parameter belongs is displayed in curly brackets in the top left of the screen.
2. DO selection 

In this display, you can pre-select a DO Only the parameters for this DO are then listed.
(The expert list display in STARTER only uses this DO view)
In both cases, the set access level governs which parameters are displayed. You can set the
access level in the menu for inhibit functions, which can be called up using the key button.
The parameters for access levels 1 and 2 are sufficient for simple applications.
At access level 3 ("Expert"), you can change the structure of the function by interconnecting
BICO parameters.
In the Data set selection menu, you can choose which of the data sets chosen is currently
DISPLAYED on the operator panel.
Data set parameters are indicated by a "c", "d", "m", "e", or "p" between the parameter
number and parameter designator.
When a data set parameter is changed, the data set selection dialog appears.
292
General parameters for the Control Unit
Non-regulated infeed
Drive control
TM31 Terminal Module (option G60)
TM150 temperature sensor module (option G51)
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A