External Supply Of The Auxiliary Supply From A Secure Line - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Electrical installation

4.8 External supply of the auxiliary supply from a secure line

In the delivery condition, the tripping current is set as follows:
Table 4- 8
Article number
6SL3710-2GH41-8EA3
6SL3710-2GH42-0EA3
6SL3710-2GH42-2EA3
6SL3710-2GH42-4EA3
6SL3710-2GH42-7EA3
Note
Consequences when the circuit breaker is incorrectly set
The settings specified above should be checked. Incorrect settings can cause unwanted or
delayed tripping of the circuit breaker and result in damage to the cabinet unit.
Diagnostics
Messages output during operation and in the event of faults are described in the Operating
Instructions in the customer DVD supplied with the device.
4.8
External supply of the auxiliary supply from a secure line
Description
An external auxiliary supply is always recommended if communication and closed-loop
control are to be independent of the supply system. An external auxiliary supply is
particularly recommended for low-power lines susceptible to short-time voltage dips or power
failures.
With an external supply independent of the main supply, warnings and fault messages may
still be displayed on the operator panel and internal protection and monitoring devices if the
main supply fails.
92
Delivery condition of the overcurrent tripping unit
Output current
1729
1948
2158
2413
2752
Overcurrent trip (L)
0.9 (both switches)
1.0 (both switches)
0.9 (both switches)
1.0 (both switches)
0.9 (both switches)
Operating Instructions, 07/2016, A5E03347396A
Short-circuit trip, non-
delayed (I)
2 (both switches)
2 (both switches)
2 (both switches)
2 (both switches)
2 (both switches)
Converter cabinet units

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents