Direction Reversal - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Functions, monitoring, and protective functions
9.2 Drive functions
Note
Deactivated functions in simulation mode
The following functions are deactivated in the simulation mode:
• Motor data identification
• Motor data identification, rotating without encoder
• Pole position identification
No flying restart is carried-out for V/f control and sensorless closed-loop vector control.
Note
Activating binector output r0863.1 in the simulation mode
In the simulation mode, binector output r0863.1 is set = 1. Therefore, before activating the
simulation mode, check as to whether additional devices are switched on using the signal. If
necessary, the corresponding BICO interconnection should be temporarily removed.
Commissioning
Simulation is activated using p1272 = 1; the following pre-requisites must be fulfilled:
● The drive unit must have been commissioned for the first time (default: Standard
induction motors).
● The DC link voltage must lie below 40 V (observe the tolerance of the DC link voltage
sensing).
Alarm A07825 (simulation mode activated) must be output during simulation operation.
Parameter
• p1272
9.2.15

Direction reversal

Description
The direction of rotation of the motor can be reversed using direction reversal via p1821
without having to change the motor rotating field by interchanging two phases on the motor
and inverting the encoder signals using p0410.
Reversal via p1821 can be detected from the motor direction of rotation. The speed setpoint
and actual value, torque setpoint and actual value remain unchanged, as does the relative
position change.
518
Simulation operation
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents