Electrical installation
4.10 Other connections
Table 4- 73
Terminal block -X2 – Adaptation of analog inputs and outputs
Terminal
Designation
50/51
60/61
62/63
4.10.31

Separate 24 V DC power supply for NAMUR (option B02)

Description
If the customer cannot provide a separate 24 V DC supply (PELV), this option enables a
second power supply to be installed to provide the PELV (terminal assignment as option
B00, 24 V infeed at terminal -X1:1,2,3 no longer needed).
4.10.32
Outgoing section for external auxiliary equipment for NAMUR (option B03)
Description
If power is to be supplied to a motor fan on site, option B03 provides an uncontrolled fuse-
protected (10 A) outgoing section. As soon as the supply voltage is present at the converter
input, it is also present at these terminals. The voltage corresponds to the converter input
voltage. You must take this into account when configuring the separately driven fan.
Connecting
Table 4- 74
Max. connectable cross-section: 2.5 mm²
194
Item code of interface con-
verter
AI
T401
AO
T402
AO
T403
Terminal block -X1 – uncontrolled power outlet (10 A) for supplying a separately driven
motor fan
Terminal
1, 2, 3, PE
Outgoing section for separately driven motor fan
Settings on rotary switch S1
2: 0 ... 20 mA
4: 4 ... 20 mA (default)
1: 0 ... 20 mA
2: 4 ... 20 mA (default)
1: 0 ... 20 mA
2: 4 ... 20 mA (default)