Application classes

Description
There are different application classes for PROFIdrive according to the scope and type of the
application processes. PROFIdrive features a total of six application classes, the three most
important are considered here.
Selection of telegrams as a function of the application class
The telegrams listed in the table below can be used in the following application classes:
Table 6- 14
Selection of telegrams as a function of the application class
Telegram
(p0922 = x)
1
Speed setpoint, 16 bit
2
Speed setpoint, 32 bit
3
Speed setpoint, 32 bit with 1 position encoder
4
Speed setpoint, 32 bit with 2 position encoders
5
Speed setpoint, 32 bit with 1 position encoder and DSC
6
Speed setpoint, 32 bit with 2 position encoders and DSC
7
Positioning, telegram 7 (basic positioner)
9
Positioning, telegram 9 (basic positioner with direct input)
20
Speed setpoint, 16 bit VIK-NAMUR
81
Encoder telegram, 1 encoder channel
82
Extended encoder telegram, 1 encoder channel + speed actual value
16 bits
83
Extended encoder telegram, 1 encoder channel + speed actual value
32 bits
102
Speed setpoint, 32 bit with 1 position encoder and torque reduction
103
Speed setpoint, 32 bit with 2 position encoder and torque reduction
105
Speed setpoint, 32 bit with 1 position encoder, torque reduction and
DSC
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Description
6.7 Communication according to PROFIdrive
Class 1
x
x
x
Operation
Class 3
Class 4
x
x
x
x
x
x
x
x
x
x
x
x