Table 4- 71
Terminal block -X2 – connection NAMUR control terminal block
Terminal
Designation
10
11
12
13
14
15
16
17
18
30
DO (COM)
31
DO (NO)
32
DO (COM)
33
DO (NO)
34
DO (NO)
35
DO (COM)
36
DO (NC)
50/51
AI 0/4-20 mA
60/61
AO 0/4-20 mA
62/63
AO 0/4-20 mA
Max. connectable cross-section: 2.5 mm²
Table 4- 72
Terminal block -X3 – connection for the motor PTC thermistor sensor
Terminal
Designation
90/91
Max. connectable cross-section: 2.5 mm²
Adapting the analog inputs and outputs
If the setting ranges of the analog inputs and outputs are to be changed, the associated
interface converters (-T401 / -T402 / -T403) must be set. The corresponding interface
converter must be removed for this purpose and the rotary switch on the side ("S1") turned
to the corresponding position.
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Default
DI
ON/OFF (dynamic)/
ON/OFF (static)
DI
OFF (dynamic)
DI
Faster
DI
Slower
DI
RESET
DI
Interlock
DI
Counterclockwise
DI
Power Disconnection
Ready for operation
Motor turning
Fault
Speed setpoint
Motor frequency
Motor current
Default
AI
Connection for a PTC ther-
mistor
Comment
Effective operation can be coded by a wire jumper on
terminal -X400:9;10 (delivery condition: jumper insert-
ed):
jumper inserted: ON/OFF (dynamic)/
jumper removed: ON/OFF (static)
Motorized potentiometer
Motorized potentiometer
Acknowledge error
OFF2
"0" signal: CW phase sequence
"1" signal: CCW phase sequence
EMERGENCY OFF circuit
"0" signal: Power disconnection
"1" signal: No power disconnection
Relay output (NO contact)
Relay output (NO contact)
Relay output (two-way contact)
Default: 4 ... 20 mA
Default: 4 ... 20 mA
(preallocated with motor frequency, can be reparame-
terized for other variables)
Default: 4 ... 20 mA
(preallocated with motor current, can be reparameter-
ized for other variables)
Comment
Shutdown if limit value is exceeded.
Electrical installation
4.10 Other connections