Parameter
• r4052
• p4053
• r4055
• p4056
• p4057
• p4058
• p4059
• p4060
• p4063
Note
Delivery condition
In the factory setting and after basic commissioning, an input current of 20 mA is equal to the
main setpoint 100% reference speed (p2000), which has been set to the maximum speed
(p1082).
Example: Switching analog input 0 from current to voltage input –10 to +10 V
Note
Save changes so that they are protected against power failure
The change to the analog input must then be stored on the CompactFlash card so that it is
protected in the event of a power failure.
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Actual input voltage/current
Analog inputs smoothing time constant
Current referenced input value
Analog inputs type
Analog inputs, characteristic value x1
Analog inputs, characteristic value y1
Analog inputs, characteristic value x2
Analog inputs, characteristic value y2
Analog inputs offset
Current/voltage switchover
Set current/voltage selector to "Voltage" ("V").
Set analog input type 0 to -10 ... +10 V.
Operation
6.5 Setpoint sources
285