Increasing the output frequency

9.2.10.1
Description
In applications that require higher output frequencies, the pulse frequency of the converter
may have to be increased.
It may also be necessary to change the pulse frequency to prevent resonances from
occurring.
Since increasing the pulse frequency also increases the switching losses, a derating factor
for the output current must be taken into account when the drive is configured.
Once the pulse frequency has been increased, the new output currents are automatically
included in the calculation for power unit protection.
Note
Use of a sine-wave filter
Use of a sine-wave filter (option L15) must be selected using p0230 = 3 when
commissioning. This setting fixes the pulse frequency to 4 kHz or 2.5 kHz and it cannot be
changed.
9.2.10.2
Default pulse frequencies
The specified maximum output frequencies can be achieved with the default pulse
frequencies listed below.
Table 9- 4
The pulse frequencies set in the factory are also the minimum frequencies.
The scanning times for the inputs and outputs of the customer terminal block TM31 are set in
the factory to 4000 µs. This is also the minimum limit.
9.2.10.3
Increasing the pulse frequency
Description
The pulse frequency can be increased in a virtually continuously variable manner to between
the value preassigned in the factory and the maximum pulse frequency which can be set.
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Maximum output frequency with default pulse frequency
Converter rating

 [ kW]
1750 to 2700
Functions, monitoring, and protective functions
Default pulse frequency

 [ kHz]
Line voltage 3 AC 660 ... 690 V
1.25
9.2 Drive functions
Maximum output frequency
[Hz]
100
511