Siemens SINAMICS G150 Operating Instructions Manual page 600

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Diagnosis/faults and alarms
10.2 Diagnosis
SMC30 – encoder evaluation (-B83)
Table 10- 8
Description of the LEDs on the SMC30
LED
Color
READY
---
Green
Orange
Red
Green/red
Green / orange
or
red / orange
OUT>5 V
---
Orange
CBE20 – Communication Board Ethernet
Table 10- 9
Description of the LEDs at ports 1-4 of the X1400 interface on the CBE20
LED
Color
Link port
---
Green
Activity
---
port
Yellow
600
State
OFF
The electronic power supply is missing or lies outside the permissible
tolerance range.
Continuous light The component is ready for operation and cyclic DRIVE-CLiQ communi-
cation is taking place.
Continuous light DRIVE-CLiQ communication is being established.
Continuous light This component has at least one fault.
Remark:
The LED is activated irrespective of whether the corresponding messag-
es have been reconfigured.
0.5 Hz flashing
Firmware is being downloaded.
light
2 Hz flashing
Firmware download is complete. Waiting for POWER ON.
light
Flashing light
Detection of the components via LED is activated (p0144).
Remark:
Both options depend on the LED status when module recognition is acti-
vated via p0144 = 1.
OFF
The electronic power supply is missing or lies outside the permissible
tolerance range.
Power supply ≤ 5 V.
Continuous light Electronic power supply for measuring system present.
Supply voltage > 5 V.
Notice:
You must ensure that the connected encoder can be operated with a 24
V supply.
Operating an encoder designed for a 5 V supply with a 24 V supply can
damage the encoder electronics beyond repair.
State
OFF
The electronic power supply is missing or lies outside the permissible
tolerance range (link missing or defective).
Continuous light A different device is connected to port x and a physical connection exists.
OFF
The electronic power supply is missing or lies outside the permissible
tolerance range (no activity).
Continuous light Data is being received or sent at port x.
Description
Description
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents