6.3 Basic information about the drive system
Internal encoding of the binector/connector output parameters
The internal codes are needed, for example, to write BICO input parameters via PROFIdrive.
Figure 6-6
Example 1: interconnecting digital signals
Suppose you want to operate a drive via terminals DI 0 and DI 1 on the Control Unit using
jog 1 and jog 2.
Figure 6-7
Example 2: connection of OC/OFF3 to several drives
The OFF3 signal is to be connected to two drives via terminal DI 2 on the Control Unit.
Each drive has a binector input 1. OFF3 and 2. OFF3. The two signals are processed via an
AND gate to STW1.2 (OFF3).
272
Internal encoding of the binector/connector output parameters
Interconnection of digital signals (example)
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A