Siemens SINAMICS G150 Operating Instructions Manual page 299

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

VECTOR object
Table 6- 5
List of signals for the operation screen - VECTOR object
Signal
Speed setpoint upstream of ramp-function
generator
Output frequency
Power smoothed
DC link voltage smoothed
Actual speed value smoothed
Absolute actual current, smoothed
Motor temperature
Converter temperature
Actual torque smoothed
Converter output voltage smoothed
For diagnostic purposes
Speed setpoint smoothed
Control factor smoothed
Field-producing current component
Torque-producing current component
Converter overload

Degree of thermal overload
Speed actual value motor encoder
Speed setpoint after the filter
Actual speed smoothed
Control deviation
Slip frequency
Output frequency
Output voltage
Control factor
Torque-generating actual current
Actual torque value
For further diagnostic purposes
Fixed speed setpoint effective
Active motorized potentiometer setpoint
Resulting speed setpoint
Speed controller output
I component of speed controller
PROFIBUS setpoint
If a temperature sensor has not been installed, a value of –200 °C is displayed.
1)
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Factory setting (entry no.)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
Parameter
Short name
r1114
NSETP
r0024
F_OUT
r0032
PACTV
r0026
U_DC
r0021
N_ACT
r0027
I_IST
r0035
T_MOT
1)
r0037
T_LT
r0031
M_ACT
r0025
C_OUT
r0020
NSETP
r0028
AUSST
r0029
IDACT
r0030
IQACT
r0036
LTI2T
r0061
N_ACT
r0062
NSETP
r0063
N_ACT
r0064
NDIFF
r0065
FSCHL
r0066
F_OUT
r0072
UACT
r0074
AUSST
r0078
IQACT
r0080
M_ACT
r1024
r1050
r1119
NSETP
r1508
NREGY
r1482
NREGI
r2050
PBSOL
6.6 Control via the operator panel
Unit
Scaling (100 %=...) See
table below
1/min
p2000
Hz
Reference frequency
kW
r2004
V
p2001
1/min
p2000
A
p2002
°C
p2006
°C
p2006
Nm
p2003
V
p2001
1/min
p2000
%
Reference modulation
depth
A
p2002
A
p2002
%
100 % = Shutdown
1/min
p2000
1/min
p2000
1/min
p2000
1/min
p2000
Hz
Reference frequency
Hz
Reference frequency
V
p2001
%
Reference modulation
depth
A
p2002
Nm
p2003
1/min
p2000
1/min
p2000
1/min
p2000
Nm
p2003
Nm
p2003
1/min
p2000
Operation
299

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents