Siemens SINAMICS G150 Operating Instructions Manual page 369

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

I&M parameter des-
For-
ignation
mat
I&M 3:
Visible
DESCRIPTOR
string
I&M 4: SIGNATURE
Octet
string
The I&M data sets 1...4 are stored permanently in parameters p8806...p8809. Significant
properties of these four parameters:
● They can be displayed in the STARTER expert list.
● The SINAMICS "Reset parameter" (p0976 = 1, p0970 = 1) function does not have any
effect on the content of parameters.
● I&M data sets are not changed when the alternative parameter sets are stored or loaded.
The transfer of parameter sets between a memory card and non-volatile device memory
does not have any effect on the I&M data sets.
Parameters
• p8805[0...1]
• p8806[0...53] Identification and Maintenance 1
• p8807[0...15] Identification and Maintenance 2
• p8808[0...53] Identification and Maintenance 3
• r8809[0...53]
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Size/
Initialization
octets
54
Space
0x20...0x20
54
Space
0x00...0x00
Identification and Maintenance configuration
Identification and Maintenance 4
6.9 Communication via PROFINET IO
SINAMICS
Meaning
parameters
p8808[0...53] Text with any comments or notes.
p8809[0...53] The parameter can be filled automatically by
the system, in which case it contains a stand-
ard value, namely, a functional check signature
for the change tracking by Safety Integrated.
The check signature has the following format:
The first four octets (0...3) contain the con-
tent of parameter r9781 index 0: "SI change
monitoring checksum (Control Unit)".
The second four octets (4...7) contain the
content of parameter r9782 index 0: "SI
change monitoring time stamp (Control
Unit)".
The remainder (octets 8...53) contains
zeroes.
Alternatively, a user can enter a user value
from an application and so overwrite the
standard value. Parameter p8805 specifies
which value is entered in p8809:
p8805 = 0 standard value entered
p8805 = 1 user value entered
When p8805 = 0 is set, the standard setting for
p8809 is restored again.
Operation
369