4. In STARTER, set the same values for IP address, subnet mask, standard gateway and
the name station as in the control system (see Chapter "Configuring communication
(Page 385)").
Furthermore, you can find a detailed description of how to create a generic I/O module on
the following Internet page:
(Creating a generic I/O module
(https://support.industry.siemens.com/cs/gr/en/view/92045369)).
Routing and shielding Ethernet cables
You can find information on how to do this on the following Internet page:
Ethernet IP (https://www.odva.org/Publication-Download).
Commissioning the drive in an EtherNet/IP network
To commission the drive, connect the drive via an interface (depending on the Control Unit
type: PROFIBUS, PROFINET, Ethernet, etc) with your computer, on which the STARTER
with version ≥ 4.5 is installed.
6.11.3

Configuring communication

Make the communication settings
Make the following settings for the CBE20 in order to communicate with a higher-level
control via EtherNet/IP:
1. With p8835 = 4, set the firmware version "Ethernet/IP".
2. Set the IP address using p8941.
You can find the currently valid address in r8951.
3. Set the subnet mask using p8943.
You can find the currently valid subnet mask in r8953.
4. Set the standard gateway using p8942.
You can find the currently valid standard gateway in r8952.
5. Set the station name using p8940.
You can find the currently valid station name in r8950.
6. Set "Save and activate configuration" as interface configuration with p8945 = 2.
7. Save the data using command "Copy RAM to ROM".
8. Perform a POWER ON.
Your settings become active after switching on.