Siemens SINAMICS G150 Operating Instructions Manual page 401

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Table 6- 54
Assigning the Modbus register to the parameters - process data
Register Description
Control data
40100
Control word (see List Manual, func-
tion diagram 2442)
40101
Main setpoint
40102
STW 3
40103
STW 4
40104
PZD 5
40105
PZD 6
40106
PZD 7
40107
PZD 8
40108
PZD 9
40109
PZD 10
Status data
40110
Status word (see List Manual, func-
tion diagram 2452)
40111
Main actual value
40112
ZSW 3
40113
ZSW 4
40114
PZD 5
40115
PZD 6
40116
PZD 7
40117
PZD 8
40118
PZD 9
40119
PZD 10
Table 6- 55
Assigning the Modbus register to the parameters - parameter data
Register Description
Drive identification
40300
Actual power unit code number
40301
Control Unit firmware
Drive data
40320
Rated power of the power unit
40321
Current limit
40322
Ramp-up time
40323
Ramp-down time
40324
Reference speed
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Access
Unit
Scaling
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
Access
Unit
Scaling
R
-
1
R
-
1
R
kW
100
R/W
%
10
R/W
s
100
R/W
s
100
R/W
RPM
1
6.12 Communication via MODBUS TCP
ON/OFF text
Data / parameter
or Value range
-
Process data 1
-
Process data 2
-
Process data 3
-
Process data 4
-
Process data 5
-
Process data 6
-
Process data 7
-
Process data 8
-
Process data 9
-
Process data 10
-
Process data 1
-
Process data 2
-
Process data 3
-
Process data 4
-
Process data 5
-
Process data 6
-
Process data 7
-
Process data 8
-
Process data 9
-
Process data 10
ON/OFF text
Data / parameter
or Value range
0 ... 65535
r0200
0 ... 65535
r0018 / 10000
0 ... 655.35
r0206
0.0 ... 6553.5
p0640
10.00 ... 655.35
p1120
10.00 ... 655.35
p1121
6 ... 65535
p2000
Operation
401

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents