Channel-related diagnostics
Channel-related diagnostics encompasses the following data:
Bit
Octet
Name
x
Header-
Byte
x + 1
x + 2
≙ Channel-related diagnostics
1)
≙ Input/output
2)
≙ "Channel type "non specific"
3)
System response
Only one signal is generated if channel-related diagnostics identifies several faults belonging
to the same message class at the same drive object.
Data sets DS0/DS1 and diagnostics alarm
The PROFIdrive message classes are transferred using diagnostic alarm DS0/DS1. All faults
are assigned channel 0. The drive objects are assigned using the slot number.
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
7
6
1
0
1)
1)
1
1
2)
2)
0
0
3)
3)
6.7 Communication according to PROFIdrive
5
4
3
0 ... 63 (module number) including these bytes
0 (no component assignment)
Message classes:
2 Undervoltage
3 Overvoltage
16 Hardware/software error
17 Line supply/filter faulted
18 DC-link overvoltage
19 Power electronics faulted
20 Electronic component overtemp.
21 Ground/phase fault detected
22 Motor overload
23 Commun. with controller faulted
24 Safety monit. Detected an error
25 Act. Position/speed value error
26 Internal communication faulted
27 Infeed faulted
28 Braking controller faulted
29 External signal state error
30 Application/function faulted
31 Parameterization/commiss. error
2
1
9 Error