Current derating as a function of the pulse frequency

When the pulse frequency is increased, the derating factor of the output current must be
taken into account. This derating factor must be applied to the currents specified in the
technical data for the cabinet units.
Table 12- 6
Derating factor of the output current as a function of the pulse frequency
Article no.
Type rating
6SL3710-...
[kW]
2GH41-8EA3
1750
2GH42-0EA3
1950
2GH42-2EA3
2150
2GH42-4EA3
2400
2GH42-7EA3
2700
Note
Derating factors for pulse frequencies in the range between fixed values
For pulse frequencies in the range between the specified fixed values, the relevant derating
factors can be determined by linear interpolation.
650
Output current
at 1.25 kHz
[A]
2 kHz
Supply voltage 3 AC 660 ... 690 V
1740
92%
1940
91%
2150
87%
2390
87%
2685
91%
Derating factor at the pulse frequency
2.5 kHz
4 kHz
87%
67%
86%
64%
79%
55%
79%
55%
86%
64%
Operating Instructions, 07/2016, A5E03347396A
5 kHz
7.5 kHz
55%
33%
50%
30%
40%
25%
40%
25%
50%
30%
Converter cabinet units