Siemens SINAMICS G150 Operating Instructions Manual page 430

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Setpoint channel and closed-loop control
7.3 V/f control
Parameter
Meaning
value
5
Precise frequency
drives (textiles)
6
Precise frequency
drives with flux cur-
rent control (FCC)
7
Parabolic character-
istic and ECO
19
Independent voltage
setpoint
Function diagram
FP 6301
Parameter
• p1300
• p1320
• p1327
• p1330
• p1331
• p1333
• r1348
• p1350
430
Characteristic (see parameter value 0) that takes into account the specific technolog-
ical features of an application (e.g. textile applications).
The current limitation (Imax controller) only affects the output voltage and not the
output frequency.
The slip compensation and resonance damping are disabled.
Characteristic (see parameter value 1) that takes into account the specific technolog-
ical features of an application (e.g. textile applications).
The current limitation (Imax controller) only affects the output voltage and not the
output frequency.
The slip compensation and resonance damping are disabled.
Voltage losses in the stator resistance for static / dynamic loads are also compen-
sated (flux current control, FCC). This is particularly useful for small motors, since
they have a relatively high stator resistance.
Characteristic (see parameter value 1) and Eco mode at constant operating point.
At constant operating point, the efficiency is optimized by varying the voltage.
Active slip compensation is necessary here; the scaling must be set so that the
slip is fully compensated (p1335 = 100%).
The user can define the output voltage of the Power Module independently of the
frequency using BICO parameter p1330 via the interfaces (e.g., analog input AI0 of
the TM31 –> p1330 = r4055[0]).
V/f characteristic and voltage boost
Open-loop/closed-loop control operating mode
V/f control programmable characteristic frequency 1
...
V/f control programmable characteristic voltage 4
CI: V/f control independent of voltage setpoint
Voltage limitation
V/f control FCC starting frequency
V/f control Eco factor actual value
V/f control soft starting
Application / property
Operating Instructions, 07/2016, A5E03347396A