Commissioning
The following sequence is recommended for commissioning:
● Configure the drive
When the drive is being commissioned using STARTER or the AOP30 operator panel,
the permanent-magnet synchronous motor must be selected. The motor data specified in
the table below must then be entered. Finally, the motor identification routine and speed
optimization (p1900) are activated. Encoder adjustment is activated automatically
together with the motor identification routine.
● Motor identification (standstill measurement, p1910)
● Speed controller optimization (rotary measurement, p1960)
Motor data for permanent-magnet synchronous motors
Table 7- 2
Motor data type plate
Parameter
Description
p0304
Rated motor voltage
p0305
Rated motor current
p0307
Rated motor power
p0310
Rated motor frequency
p0311
Rated motor speed
p0314
Motor pole pair number
p0316
Motor torque constant
If the torque constant k
can calculate this value from the rated motor data or from the stall current I
M
as follows:
0
or
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
7.4 Vector speed/torque control with/without encoder
Comment
If this value is not known, the value "0" can also be
entered. Entering the correct value, however, means
that the stator leakage inductance (p0356, p0357) can
be calculated more accurately.
If this value is not known, the value "0" can also be
entered.
If this value is not known, the value "0" can also be
entered.
is not stamped on the type plate or specified in the data sheet, you
T
Setpoint channel and closed-loop control
0
and stall torque
467