dv/dt filter compact plus Voltage Peak Limiter (Option L07)

Description
The dv/dt filter compact plus Voltage Peak Limiter comprises two components: the dv/dt
reactor and the voltage-limiting network (Voltage Peak Limiter), which cuts off the voltage
peaks and feeds back the energy into the DC link. The dv/dt filter compact plus Voltage Peak
Limiter is designed for motors for which the voltage strength of the insulation system is
unknown or insufficient.
dv/dt filters compact plus Voltage Peak Limiters limit the voltage rate of rise dv/dt to values <
1600 V/µs - and the typical voltage peaks to the following values according to limit value
curve A acc. to IEC 60034-25:2007:
● < 1400 V at 660 V < U
Restrictions
The following constraints should be noted when a dv/dt filter compact plus Voltage Peak
Limiter is deployed:
● The output frequency is limited to no more than 150 Hz.
● Maximum permissible motor cable lengths:
– Shielded cable: max. 100 m
– Unshielded cable: max. 150 m
NOTICE
Damage to the dv/dt filter compact by exceeding the maximum output frequency
The maximum permissible output frequency when a dv/dt filter compact is used is 150 Hz.
The dv/dt filter compact can be damaged if the output frequency is exceeded.
• Operate the dv/dt filter compact with a maximum output frequency of 150 Hz.
NOTICE
Damage to the dv/dt filter compact during continuous operation with low output frequencies
Uninterrupted duty at an output frequency less than 10 Hz can result in thermal overload
and destroy the dv/dt filter.
• When using a dv/dt filter compact plus voltage peak limiter do not operate the drive
• You may operate the drive for a maximum load duration of 5 minutes at an output
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
line
continuously with an output frequency less than 10 Hz.
frequency less than 10 Hz, provided that you then select an operation with an output
frequency higher than 10 Hz for a period of 5 minutes.
< 690 V.