Siemens SINAMICS G150 Operating Instructions Manual page 655

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Table 12- 8
Version A, 660 ... 690 V 3 AC, Part 2
Article number
Unit rating
- for I
at 50 Hz 690 V
1)
L
- for I
at 50 Hz 690 V
1)
H
Output current
- Rated current I
N
- Base load current I
2)
L
- Base load current I
3)
H
Input current
- Rated input current
4)
- Input current, max.
- Current requirements for 24 V DC
auxiliary supply
Supply voltages
- Line voltage
- Line frequency
- Electronic power supply
Power loss
Cooling air requirement
Sound pressure level L
pA
(1 m) at 50/60 Hz
Line connection
- Recommended: IEC
4)
- maximum: IEC
- Fixing screw
Motor connection
- Recommended: IEC
5)
- maximum: IEC
- Fixing screw
Protective conductor connection
Fixing screw
Max. motor cable length
shielded / unshielded
Dimensions (standard version)
- Width
- Height
- Depth
Basic Line Module frame size
Motor Module frame size
Weight (without options), approx.
Recommended protection
- Line protection
(with option L26)
Rated current
frame size to IEC 60269
- Line and semiconductor protection
(without option L26)
Rated current
Frame size to IEC 60269
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
6SL3710- 2GH42-4EA3
kW
2400
kW
2150
A
2413
A
2390
A
2158
A
2510
A
3860
A
4.7
V
660 V 3 AC -10 % to 690 V 3 AC +10 % (-15 % < 1 min)
ACrms
Hz
V
DC
kW
46
m
/s
3.67
3
dB(A)
75/78
Per sub-cabinet:
mm
4 x 150
2
mm
8 x 240
2
M12 (4 holes)
Per sub-cabinet:
mm
3 x 185
2
mm
6 x 240
2
M12 (3 holes)
Per sub-cabinet:
M12 (18 holes)
m
300 / 450
mm
3600
mm
2000
mm
600
GD
JX
kg
3860
Per sub-cabinet:
3NA3365-6
A
3 x 500
3
Per sub-cabinet:
3NE1334-2
A
3 x 500
2
Technical specifications
2GH42-7EA3
2700
2400
2752
2685
2463
2865
4400
6.0
47 ... 63
24 (20.4 ... 28.8)
52
5.15
75/78
Per sub-cabinet:
4 x 150
8 x 240
M12 (4 holes)
Per sub-cabinet:
3 x 185
6 x 240
M12 (3 holes)
Per sub-cabinet:
M12 (18 holes)
300 / 450
4400
2000
600
GD
JX
4580
Per sub-cabinet:
3NA3372
3 x 630
3
Per sub-cabinet:
3NE1436-3
3 x 630
3
12.3 Technical data
655

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents