Temperature sensor connection directly to the Control Interface Module

Temperature measurement via KTY
The device is connected to terminals X41:3 (Temp-) and X41:4 (Temp+) on the Control
Interface Module in the forward direction of the diode.
● Activate motor temperature measurement via Motor Module: p0600 = 11.
● Set the KTY temperature sensor type: p0601 = 2.
Temperature measurement via PTC
The connection is made at the terminals X41:3 (Temp-) and X41:4 (Temp+) at the Control
Interface Module. The threshold for changing over to an alarm or fault is 1650 Ω.
● Activate motor temperature measurement via Motor Module: p0600 = 11.
● Set the PTC temperature sensor type: p0601 = 1.
Temperature measurement using the bimetal normally closed contact
The connection is made at the terminals X41:3 (Temp-) and X41:4 (Temp+) at the Control
Interface Module. The threshold for changing over to an alarm or fault is 100 Ω.
● Activate motor temperature measurement via Motor Module: p0600 = 11.
● Set the temperature sensor type bimetal normally closed contact: p0601 = 4.
Temperature measurement via PT100
The connection is made at the terminals X41:3 (Temp-) and X41:4 (Temp+) at the Control
Interface Module. p0624 can be used to set the temperature offset for the PT100 measured
value.
● Activate motor temperature measurement via Motor Module: p0600 = 11.
● Set the PT100 temperature sensor type: p0601 = 5.
Temperature measurement via PT1000
The connection is made at the terminals X41:3 (Temp-) and X41:4 (Temp+) at the Control
Interface Module.
● Activate motor temperature measurement via Motor Module: p0600 = 11:
● Set the PT1000 temperature sensor type: p0601 = 6.
Sensor connection to units connected in parallel
In the case of units connected in parallel, the number of the power unit to which the
temperature sensor is connected must be specified in p0602.