Saving settings and series commissioning
7.1 Saving settings on a memory card
7.1.5

Activate message for a memory card that is not inserted

Function
The inverter identifies that a memory card is not inserted, and signals this state. The message
is deactivated in the inverter factory setting.
Activate message
Procedure
To activate alarm A01101 for a memory card that is not inserted, proceed as follows:
1. Set p2118[x] = 1101, x = 0, 1, ... 19
2. Set p2119[x] = 2
You have activated message A01101 for a memory card that is not inserted.
To cyclically signal to a higher-level control that a memory card is not inserted, interconnect
parameter r9401 to the send data of a PROFIdrive telegram of your choice.
Deactivate message
Procedure
To deactivate alarm A01101 for a memory card that is not inserted, proceed as follows:
1. Set p2118[x] = 1101, x = 0, 1, ... 19
2. Set p2119[x] = 3
You have deactivated message A01101 for a memory card that is not inserted.
Parameter
Parameter
p2118[0 ... 19]
p2119[0 ... 19]
r9401
332
Explanation
Change message type message number (factory setting: 0)
Change message type (factory setting: 0)
1: Fault
2: Alarm
3: No message
Safely remove memory card status
.00
1 signal: Memory card inserted
.01
1 signal: Memory card activated
.02
1 signal: SIEMENS memory card
.03
1 signal: Memory card used as USB data storage medium from the PC
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF