Routing Cables; Routing Cables; Check Before Routing Cables - YASKAWA FSDrive-MV1000 Instructions Manual

Super energy-saving medium-voltage ac drive
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

3.4 Routing Cables

3.4

Routing Cables

The structure of the terminals conforms to JCS standards stipulated by the Japanese Electric Wire & Cable Makers'
Association. Route the cables according to the JCS standards appropriate for the input voltage used.
Examples of cable routing are shown below.
Note: Secure the cables with cable brackets. Do not secure them at an intermediate point between the cable bracket and control circuit
terminals. Prepare cable brackets suitable for the size of the cables used.

◆ Check Before Routing Cables

Main Circuit Input-side Cable
Route the input cable at the input side of the drive into the transformer panel through the inlet port of the drive input
cable at the bottom of the transformer panel.
Mount a cable bracket on the cable bracket clamp near the cable inlet port to secure the cables.
Main Circuit Output-side Cable
Route the output cable at the output side of the drive into the Power Cell panel through the inlet port of the drive output
cable at the bottom of the transformer panel.
Mount a cable bracket on the cable bracket clamp near the cable inlet port to secure the cables.
NOTICE: Keep the wiring for the main circuit separate from that for the control circuit. Select a power supply with a capacity larger
than that of the drive to be connected. When connecting multiple drives to a single power supply, select a power supply with
a capacity larger than the sum of the power required by all the drives to be connected. Even when the power supply has
sufficient capacity, the power supply voltage may drop when the power is turned on, causing malfunction of connected
devices if the power supply has a large power impedance.
Figure 3.5
Left side view
T S
R
F
A – Cooling fan
B – Power Cell
C – Control circuit terminal
D – Main circuit output terminals U, V and W
60
Transformer panel
A
H
E
G
F
Figure 3.5 Cable Routing (Drive: 2-kV Class, 700 HP)
Front view
Power Cell panel
Control panel
B
F
E – Cable bracket clamp
F – Main circuit cable
G – Cable bracket
H – Main circuit input terminals R, S, and T
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
2.4kV
Right side view
C
U
V
W
D
E
F
G

Hide quick links:

Advertisement

Table of Contents
loading