3.5.8 PLD-H and PLA-H I/O modules
PLD-H 16-08-00
Pin layout
PLD-H 08-16-00
Pin layout
178
Connector
Function
X11
PLC inputs, channel A
X12
PLC inputs, channel A
X21
PLC outputs, channel A
Diagnosis (meanings of the LEDs):
Red (X11/pin 1) status LED
• Flashes: status of I/O module OK
• Continuously on or off: error on I/O module
Yellow (per output): Status of the output
Error recognition:
Short circuit: A short circuit is reported when a current >= 20 A flows
for approximately 3 ms. Both the output-specific message and the group
message are modal.
After the short circuit has been removed, the PLC must reset the output
before it can be activated again.
Open circuit operation (line break): With load currents <= 300 mA, the
PLD 16-8 reports a line breakage.
Connector
Function
X11
PLC inputs, channel A
X21
PLC outputs, channel A
X22
PLC outputs, channel A
Diagnosis (meanings of the LEDs):
Red (X11/pin 1) status LED
• Flashes: status of I/O module OK
• Continuously on or off: error on I/O module
Yellow (per output): Status of the output
Error recognition:
Short circuit: A short circuit is reported when a current >= 20 A flows
for approximately 3 ms. Both the output-specific message and the group
message are modal.
After the short circuit has been removed, the PLC must reset the output
before it can be activated again.
Open circuit operation (line break): With load currents <= 300 mA, the
PLD 08-16 reports a line breakage.
HEIDENHAIN Technical Manual MANUALplus 620