3.1.2 Degrees of protection
3.1.3 Electromagnetic compatibility
Likely sources of
interference
152
Danger
The interfaces for the PLC inputs/outputs, machine operating panel and PL
connection comply with the requirements for basic insulation in accordance
with IEC 742 EN 50 178.
Only units that comply with the requirements of IEC 742 EN 50 178 for
basic insulation may be connected, otherwise damage to persons or prop-
erty may be caused. The maximum dc voltage mean value of the PLC
inputs is 31 V.
The following components fulfill the requirements for IP54 (dust and splash-
proof protection).
Visual display unit (front, when properly installed)
Keyboard unit (front, when properly installed)
Machine operating panel (front, when properly installed)
Handwheel (built-in or connected, depending on the type)
All electric and electronic control components must be installed in an environ-
ment (e.g. electrical cabinet, housing) that fulfills the requirements of protec-
tion class IP54 (dust and splash-proof protection) in order to fulfill the require-
ments of contamination level 2.
Note
All components of the OEM operating panel must also comply with
protection class IP54, just like the HEIDENHAIN operating panel
components.
This unit fulfills the requirements for Class A according to EN 55022 and is
intended for operation in industrially zoned areas.
Protect your equipment from interference by observing the following rules and
recommendations.
Interference is mainly produced by capacitive and inductive coupling from
electrical conductors or from device inputs/outputs, such as:
Strong magnetic fields from transformers or electric motors
Relays, contactors and solenoid valves
High-frequency equipment, pulse equipment and stray magnetic fields from
switch-mode power supplies
Power lines and leads to the above equipment
HEIDENHAIN Technical Manual MANUALplus 620