Suppressing the
status signals of the
HEIDENHAIN
supply unit
January 2012
Settings in the configuration editor
Axes
ParameterSets
[Key name of the parameter set]
CfgPowerStage
powStatusCheckOff
The parameter object CfgPowerStage is not required for:
Virtual axes (MP_axisMode = Virtual)
Axes that are for display only (MP_axisMode = Display)
Analog axes (MP_axisHw = Analog)
The HEIDENHAIN power supply units have several status signals which lead
to error messages on the control. MP_powStatusCheckOff is used to
suppress the error message for each status signal.
HEIDENHAIN does not recommend suppressing the error messages from the
power supply units. If you are using a UE 2xx, the signals must be suppressed
because the UE 2xx compact inverter does not provide these signals.
The handling of status signals from HEIDENHAIN power supply units, which
are already inactive during control start-up, varies depending on
MP_ampStatusCheckOff – bit 0.
MP_powStatusCheckOff
Bit 0 = 0: Missing signals do not result in an error message when the drive
is switched on.
Bit 0 = 1: Missing signals result in an error message when the drive is
switched on. Signals that are not provided by the power supply unit must be
suppressed with MP_powStatusCheckOff (bit 1 to bit 6), because non-
existent signals are always identified as errors.
Note
Signals that change their status during operation are always identified as
errors.
6.17 Monitoring Functions
MP number
401209
981