Parameter Description
3.15 Parameters 16-** Data Readouts
3.15.1 16-0* General Status
16-00 Control Word
Range:
Function:
0
[0 - 65535 ] View the control word sent from the frequency
*
converter via the serial communication port in
hex code.
16-01 Reference [Unit]
Range:
0 ReferenceFeed-
[-999999 -
backUnit
999999
*
ReferenceFeed-
backUnit]
16-02 Reference [%]
Range:
Function:
0 %
[-200 -
View the total reference. The total reference
*
200 %]
is the sum of digital, analog, preset, bus,
and freeze references, plus catch up and
slow down.
16-03 Status Word
Range:
Function:
0
[0 - 65535 ] View the status word sent from the frequency
*
converter via the serial communication port in
hex code.
16-05 Main Actual Value [%]
Range:
Function:
0.00 %
[-100.00 -
View the 2 byte word sent with the
*
100.00 %]
status word to the fieldbus master
reporting the main actual value. Refer to
the VLT
Programming Guide for further details.
16-09 Custom Readout
Range:
0 CustomRea-
[-999999.99 -
doutUnit
999999.99
*
CustomRea-
doutUnit]
MG20OB02
Programming Guide
Function:
View the present reference
value applied on impulse or
analog basis in the unit
resulting from the configu-
ration selected in
parameter 1-00 Configu-
ration Mode (Hz, Nm, or
RPM).
®
PROFIBUS DP MCA 101
Function:
View the user-defined readouts
as defined in
parameter 0-30 Custom Readout
Unit, parameter 0-31 Custom
Readout Min Value, and
parameter 0-32 Custom Readout
Max Value.
Danfoss A/S © 05/2018 All rights reserved.
3.15.2 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0 kW
[0 -
Shows motor power in kW. The value shown
*
10000
is calculated based on the actual motor
kW]
voltage and motor current. The value is
filtered, and therefore approximately 1.3 s
may pass from when an input value changes
to when the data readout values change. The
resolution of readout value on fieldbus is in
10 W steps.
16-11 Power [hp]
Range:
Function:
0 hp
[0 -
View the motor power in hp. The value
*
10000 hp]
shown is calculated based on the actual
motor voltage and motor current. The value
is filtered, and therefore approximately 1.3 ms
may pass from when an input value changes
to when the data readout values change.
16-12 Motor Voltage
Range:
Function:
0 V
[0 - 6000 V] View the motor voltage, a calculated value
*
used for controlling the motor.
16-13 Frequency
Range:
Function:
0 Hz
[0 - 6500 Hz] View the motor frequency without
*
resonance damping.
16-14 Motor current
Range:
Function:
0 A
[0 - 10000
View the motor current measured as an
*
A]
average value, I
thus approximately 1.3 s may pass from
when an input value changes to when the
data readout values change.
16-15 Frequency [%]
Range:
Function:
0 %
[-100 -
View a 2-byte word reporting the actual motor
*
100 %]
frequency (without resonance damping) as a
percentage (scale 0000–4000 hex) of
parameter 4-19 Max Output Frequency. Set
parameter 9-16 PCD Read Configuration index 1
to send it with the status word instead of the
MAV.