Programming Guide | VLT® Aqua Drive FC 202 Contents Contents Introduction Purpose of the Programming Guide Supported Software Versions Type Approvals and Certifications Safety Safety Symbols Safety Precautions Protection Mode Electrical Wiring Electrical Wiring - Control Cables 3.1.1 Wiring Diagram Input Polarity of Control Terminals 3.1.2 3.1.3...
Page 4
Programming Guide | VLT® Aqua Drive FC 202 Status View II 4.1.8.2 Status View III 4.1.8.3 Quick Menu Key Functions 4.1.9 4.1.10 Q2 Quick Setup 4.1.11 Programming in the Quick Setup Q3 Function Set-ups 4.1.12 4.1.13 Function Set-ups Overview 4.1.13.1 Function Set-up Q3-1 General Settings 4.1.13.2 Function Set-up Q3-2 Open-loop Settings...
Page 5
Programming Guide | VLT® Aqua Drive FC 202 0-5* Copy/Save 5.2.7 5.2.8 0-6* Password 5.2.9 0-7* Clock Settings Parameter Group 1-** Load and Motor 5.3.1 1-0* General Settings Motor Setups 5.3.2 5.3.2.1 Asynchronous Motor Setup 5.3.2.2 PM Motor Setup 5.3.2.3 Programming of PM Motors 5.3.2.4 SynRM and PMaSynRM Motor Setup...
Page 6
Programming Guide | VLT® Aqua Drive FC 202 Semi-automatic Bypass Speed Setup 5.6.5 Parameter Group 5-** Digital In/Out 5-0* Digital I/O Mode 5.7.1 5.7.2 5-1* Digital Inputs 5.7.3 5-3* Digital Outputs 5-4* Relays 5.7.4 5.7.5 5-5* Pulse Input 5.7.6 5-6* Pulse Outputs 5-8* I/O Options 5.7.7 5.7.8...
Page 7
Programming Guide | VLT® Aqua Drive FC 202 10-0* Common Settings 5.12.1 5.12.2 10-1* DeviceNet 5.12.3 10-2* COS Filters 10-3* Parameter Access 5.12.4 5.13 Parameter Group 12-** Ethernet 12-0* IP Settings 5.13.1 5.13.2 12-1* Ethernet Link Parameters 5.13.3 12-2* Process Data 12-3* EtherNet/IP 5.13.4 5.13.5...
Page 8
Programming Guide | VLT® Aqua Drive FC 202 Service Log 5.16.3 5.16.4 Clearing the Service Log 5.16.5 Service Log Indication Reading the Service Log Information 5.16.6 5.16.7 Alarms that Trigger a Service Log Record 5.16.8 15-2* Historic Log 15-3* Alarm Log 5.16.9 5.16.10 15-4* Drive Identification...
Page 10
Programming Guide | VLT® Aqua Drive FC 202 Parameter Group 26-** Analog I/O Option MCB 109 5.25 5.25.1 Introduction to Parameters Related to the VLT® Analog I/O Option MCB 109 26-0* Analog I/O Mode 5.25.2 5.25.3 26-1* Analog Input X42/1 5.25.4 26-2* Analog Input X42/3 26-3* Analog Input X42/5...
Page 11
Programming Guide | VLT® Aqua Drive FC 202 30-9* Wifi LCP 5.28.4 5.29 Parameter Group 31-** Bypass Option Parameter Group 34-** MCO Data Readouts 5.30 5.30.1 34-0* PCD Write Par. 34-2* PCD Read Par. 5.30.2 5.31 Parameter Group 35-** Sensor Input Option 5.31.1 35-0* Temp.
Page 12
Programming Guide | VLT® Aqua Drive FC 202 45-4* Threshold Generation 5.35.5 5.35.6 45-5* Sensor Config. 5.35.7 45-6* Stator Res. Setting 45-9* Actual Readouts 5.35.8 5.36 Parameter Group 46-** CBM Adv. Thresholds 46-0* History 5.36.1 5.36.2 46-0* General 5.36.3 46-1* Timing 46-2* Stator 5.36.4 5.36.5...
This programming guide can be used for all FC 202 drives. The software version number can be read from parameter 15-43 Software Version. Type Approvals and Certifications The following table shows examples of possible type approvals and certifications for Danfoss drives. NOTICE Drives of enclosure size T7 (525–690 V) are not UL listed.
Page 16
Programming Guide | VLT® Aqua Drive FC 202 Introduction For more information on UL 508C thermal memory retention requirements, refer to the section Motor Thermal Protection in the product- specific design guide. For more information on compliance with the European Agreement concerning International Carriage of Dangerous Goods by Inland Waterways (AND), refer to the section AND-compliant Installation in the product-specific design guide.
Programming Guide | VLT® Aqua Drive FC 202 Safety Safety Safety Symbols The following symbols are used in Danfoss documentation. DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Page 18
Programming Guide | VLT® Aqua Drive FC 202 Safety WARNING UNINTENDED START When the drive is connected to AC mains, DC supply, or load sharing, the motor may start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage.
Programming Guide | VLT® Aqua Drive FC 202 Safety Protection Mode Once a hardware limit on motor current or DC-link voltage is exceeded, the drive enters protection mode. Protection mode means a change of the PWM modulation strategy and a low switching frequency to minimize losses. This continues for 10 s after the last fault and increases the reliability and robustness of the drive while re-establishing full control of the motor.
Programming Guide | VLT® Aqua Drive FC 202 Electrical Wiring If this occurs, it may be necessary to break the shield or insert a 100 nF capacitor between shield and enclosure. Connect the digital and analog inputs and outputs separately to the common inputs (terminals 20, 55, and 39) of the drive to avoid ground currents from both groups to affect other groups.
Programming Guide | VLT® Aqua Drive FC 202 Electrical Wiring +24V Par. 5-10 Par. 5-12 Par. 5-13 Par. 5-14 Figure 7: Speed Up/Down 3.2.4 Potentiometer Reference Voltage reference via a potentiometer Reference source 1= [1] Analog input 53 (default). Terminal 53, Low Voltage = 0 V. Terminal 53, High Voltage = 10 V.
Programming Guide | VLT® Aqua Drive FC 202 How to Program How to Program The Local Control Panel Overview of the LCP 4.1.1 Easily program the drive via the local control panel (LCP). Status 1(0) 1234rpm 10.4A 43.5Hz 43.5Hz Run OK Quick Main Alarm...
Programming Guide | VLT® Aqua Drive FC 202 How to Program NOTICE If start-up is delayed, the LCP shows the INITIALIZING message until it is ready. Adding or removing options can delay the start-up. LCD Display 4.1.2 The display has backlight and a total of 6 alpha-numeric lines. The display lines show the direction of rotation (arrow), the selected setup, and the programming setup.
Programming Guide | VLT® Aqua Drive FC 202 How to Program Flashing Red LED/Alarm: Indicates an alarm. Warn. Alarm Figure 11: Indicator Lights 4.1.3 LCP Keys Control keys The control keys are divided into functions. The keys below the display and indicator lights are used for parameter setup, including option of display indication during normal operation.
Page 30
Programming Guide | VLT® Aqua Drive FC 202 How to Program Table 2: LCP Keys and Description (continued) LCP keys Description [Back] Returns to the previous step or layer in the navigation structure. [Cancel] Last change or command is canceled as long as the display has not been changed.
Programming Guide | VLT® Aqua Drive FC 202 How to Program Table 3: Local Control Keys and Description (continued) LCP keys Description [Auto On] Enables the drive to be controlled via the control terminals and/ or serial communication. When a start signal is applied on the control terminals and/or the bus, the drive starts.
Page 32
Programming Guide | VLT® Aqua Drive FC 202 How to Program Refer to to see the measurements that can be linked to each of the operating variables. When options are mounted, more Table 4 measurements are available. Define the links: Parameter 0-20 Display Line 1.1 Small.
Page 33
Programming Guide | VLT® Aqua Drive FC 202 How to Program Table 4: Units (continued) Operating variable Unit Parameter 16-25 Torque [Nm] High Parameter 16-30 DC Link Voltage Parameter 16-32 Brake Energy /s Parameter 16-33 Brake Energy Average °C Parameter 16-34 Heatsink Temp. Parameter 16-35 Inverter Thermal Parameter 16-36 Inv.
Programming Guide | VLT® Aqua Drive FC 202 How to Program Status 1 (1) 799 RPM 7.83 A 36.4 kW 0.000 53.2 % Auto Remote Ramping Figure 12: Status View I 4.1.8.2 Status View II See the operating variables (1.1, 1.2, 1.3, and 2) shown in the following illustration. In the example, speed, motor current, motor power, and frequency are selected in the 1st and 2nd lines.
Page 36
Programming Guide | VLT® Aqua Drive FC 202 How to Program 0RPM 0.00A 1(1) Quick Menus Q1 My Personal Menu Q2 Quick Setup Q4 Smart Setup Q5 Changes Made Figure 15: Quick Menus Select Q1 My Personal Menu to show the selected personal parameters. These parameters are selected in parameter 0-25 My Personal Menu.
Programming Guide | VLT® Aqua Drive FC 202 How to Program Q2 Quick Setup 4.1.10 The parameters can easily be set up for most applications only by using the Quick Setup. After pressing [Quick Menu], the different options in the Quick Menu are listed. 40.0% 4.84 A 1(1)
Programming Guide | VLT® Aqua Drive FC 202 How to Program Table 6: Quick Setup Parameters (continued) Parameter [Unit] Parameter 5-12 Terminal 27 Digital Input Parameter 5-40 Function Relay 1) The information shown in the display depends on the selections made in parameter 0-02 Motor Speed Unit and parameter 0-03 Regional Settings. The default settings of parameter 0-02 Motor Speed Unit and parameter 0-03 Regional Settings depend on which region of the world the drive is supplied to, but can be reprogrammed as required.
Programming Guide | VLT® Aqua Drive FC 202 How to Program Among other features, the Function Set-ups also include parameters for selecting the following: Which variables to show on the LCP. Digital preset speeds. Scaling of analog references. Closed-loop single-zone and multi-zone applications. Specific functions related to water.
Programming Guide | VLT® Aqua Drive FC 202 How to Program Table 8: Q3-2 Open-loop Settings (continued) Q3-2 Open-loop settings Q3-20 Digital reference Q3-21 Analog reference Parameter 5-14 Terminal 32 Digital Input Parameter 6-14 Terminal 53 Low Ref./Feedb. Value Parameter 5-15 Terminal 33 Digital Input Parameter 6-15 Terminal 53 High Ref./Feedb.
Programming Guide | VLT® Aqua Drive FC 202 How to Program 1107 RPM 3.84 A 1(1) Main Menu 0-** Operation/Display 1-** Load/Motor 2-** Brakes 3-** References/Ramps Figure 17: Main Menu Mode Each parameter has a name and number which remain the same regardless of the programming mode. In the main menu mode, the parameters are divided into groups.
Programming Guide | VLT® Aqua Drive FC 202 How to Program 740RPM 10.64 A 1 [1] 0-0 * Basic Settings 0 -01 Language [0] English Figure 19: Changing a Text Value 4.1.19 Changing a Data Value If the selected parameter shows a numeric data value, change the selected data value with the [◄] [►] and the [▲] [▼] navigation keys. Press the [◄] [►] keys to move the cursor horizontally.
Programming Guide | VLT® Aqua Drive FC 202 How to Program Change the selected digit infinitely variably with [▲] [▼]. The cursor indicates the selected digit. Place the cursor on the digit to save and press [OK]. 957 RPM 11.58A 1 (1) Start Adjustments 1-7*...
Programming Guide | VLT® Aqua Drive FC 202 How to Program The Numerical Control Panel Overview of the Numerical LCP 4.2.1 Setup Status Quick Main Setup Menu Menu Warn. Alarm Hand Auto Reset Figure 24: NLCP Numeric display. Menu keys and indicator lights - changing parameters and switching between display functions.
Page 45
Programming Guide | VLT® Aqua Drive FC 202 How to Program Table 10: LCP Keys and Description LCP keys Description [Status] Indicates the status of the drive and/or the motor. If an alarm occurs, the NLCP automatically switches to status mode. Several alarms can be shown.
Programming Guide | VLT® Aqua Drive FC 202 How to Program Local control keys: Local control keys are at the bottom of the control panel. Table 11: Local Control Keys and Description LCP keys Description [Hand On] Enables control of the drive via the LCP. [Hand On] also starts the motor, and it is now possible to enter the motor speed data with the navigation keys.
Programming Guide | VLT® Aqua Drive FC 202 How to Program NOTICE LOSS OF DATA Restoring default settings results in a loss of programming, motor data, localization, and monitoring records. To create a backup, upload data to the LCP before initialization. Press [Main Menu] twice to access parameters.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Parameter Descriptions Selecting Parameters The parameters are grouped into various parameter groups for easy selection of the correct parameter for optimal operation of the drive. Parameter descriptions and selections are shown in the LCP. Access the parameters by pressing [Quick Menu] or [Main Menu] on the LCP. The Quick Menu is used mainly for commissioning the unit at start-up by providing parameters necessary to start operation.
Page 49
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [28] Bras. Port Part of language package 4. [36] Slovenian Part of language package 3. [39] Korean Part of language package 2. [40] Japanese Part of language package 2. [41] Turkish Part of language package 4.
Page 50
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Select to show motor speed variables and parameters using motor speed (RPM). Select to show motor speed variables and parameters using output frequency (Hz). 0-03 Regional Setting Default value: [0] International Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: 2 setups Conversion index: – Data Type: Uint8 Change during operation: False This parameter defines if the local reference unit should be shown as the motor shaft speed (in RPM/Hz) or as percent. Option Name Description...
Page 52
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Set-up 4 Multi Set-up Remote setup selections using digital inputs and the serial communication port. This setup used the settings from parameter 0-12 This Set-up Linked to. Stop the drive before making changes to open-loop and closed-loop functions.
Page 53
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Set-up 2 Set-up 3 Set-up 4 0-13 Readout: Linked Set-ups Default value: Parameter type: Range, 0 – 255, Array [5] Setup: Conversion index: All setups Data type: Uint16 Change during operation: False...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint8 Change during operation: False Read out the active emergency setup selected by either digital inputs or via fieldbus. 0-2* LCP Display 5.2.4 Define the variable shown in the LCP.
Page 55
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1013] Warning parameter View a DeviceNet-specific warning word. One separate bit is assigned to every warning. [1230] Warning parameter [1397] Alert alarm word [1398] Alert warning word [1399] Alert status word [1500]...
Page 56
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1619] Thermistor sensor temperature [1620] Motor angle [1622] Torque [%] Present motor load as a percentage of the rated motor torque. [1623] Motor shaft power [kW] [1624] Calibrated stator resistance [1626] Power filtered [kW]...
Page 57
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1658] PID output [%] [1659] Adjusted setpoint [1660] Digital input Signal states from the 6 digital terminals (18, 19, 27, 29, 32, and 33). There are 16 bits in total, but only 6 of them are used. Input 18 corresponds to the far left of the used bits.
Page 58
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1686] FC port REF 1 Status word (STW) sent to the bus master. [1687] Bus readout alarm/warning [1689] Configurable alarm/warning word [1690] Alarm word One or more alarms in a hex code. [1691] Alarm word 2 One or more alarms in a hex code.
Page 59
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1850] Sensorless readout [Unit] [1860] Digital input 2 [1870] Mains voltage [1871] Mains frequency [1872] Mains imbalance [1873] Worst inrush [1874] Inrush mode [1875] Rectifier DC volt. [1876] Mains voltage2 [1877]...
Page 60
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [2921] Derag power [HP] [2965] Totalized volume [2966] Actual volume [2969] Flow [3110] Bypass status word [3111] Bypass running hours [3401] PCD 1 write to MCO [3402] PCD 2 write to MCO [3403] PCD 3 write to MCO...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [4594] Sensor 2 [%] [4595] Sensor 2 [unit] [4596] Sensor 3 [%] [4597] Sensor 3 [unit] [4598] Sensor 4 [%] [4599] Sensor 4 [unit] 0-21 Display Line 1.2 Small The options are the same as those listed for parameter 0-20 Display Line 1.1 Small.
Page 62
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Actual speed. Custom Readout (Value) P 16-09 Custom Readout Unit P 0-30 Max value P 0-32 Min value Linear units Motor Speed only (P0-31) Motor Speed High limit P 4-13 (RPM) P 4-14 (Hz) Figure 28: Custom Readout The relation depends on the type of unit selected in parameter 0-30 Custom Readout Unit.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Parameter 0-37 Display Text 1 Default value: Parameter type: Range, 0 - 25 Setup: 1 setup Conversion index: Data type: VisStr[25] Change during operation: True Enter a text which can be viewed in the graphical display by selecting [37] Display Text 1 in Parameter 0-20 Display Line 1 Small Parameter 0-21 Display Line 1.2 Small Parameter 0-22 Display Line 1.3 Small...
Page 66
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint8 Change during operation: True Option Name Description Disabled No effect when [Hand On] is pressed. Select [0] Disabled to avoid accidental start of the drive in hand-on mode. [1]* Enabled The LCP switches to hand-on mode directly when [Hand On] is...
Page 67
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Disabled Avoids accidental stop of the drive in auto-on mode. [1]* Enabled Password Avoids unauthorized start in auto-on mode. If parameter 0-42 [Auto on] Key on LCP is included in the Quick Menu, then define the password in parameter 0-65 Personal Menu Password.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Disabled No effect when [Reset] is pressed. Avoids accidental alarm reset. [1]* Enabled Password Avoids unauthorized start in auto-on mode. If parameter 0-43 [Reset] Key on LCP is included in the Quick Menu, then define the password in parameter 0-65 Personal Menu Password.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description All from LCP Copies all parameters in all setups from the LCP memory to the drive memory. Size indep. from LCP Copy only the parameters that are independent of the motor size.
Page 70
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Full access Disables password defined in parameter 0-60 Main Menu Password. LCP: Read only Prevent unauthorized editing of Main Menu parameters. LCP: No access Prevent unauthorized viewing and editing of Main Menu parameters.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Use this parameter to unlock the drive via fieldbus or VLT® Motion Control Tool MCT 10. When a valid password is entered, the drives is unlocked for 30 minutes. 0-7* Clock Settings 5.2.9 Set the time and date of the internal clock.
Page 72
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description YYYY-MM-DD DD-MM-YYYY MM/DD/YYYY 0-72 Time Format Default value: [0] 24 h Parameter type: Option Setup: 1 setup Conversion index: – Data type: Uint8 Change during operation: True Option Name Description...
Page 73
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions This parameter stores the last 5 drive power-off timestamps. Index [0] is the latest power-off time, whereas index [4] is the oldest. 0-76 DST/Summertime Start Default value: Size related Parameter type: Range, 0 - 0 Setup: 1 setup...
Page 74
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 0-82 Additional Working Days Default value: Size related Parameter type: Range, 0 - 0, Array [5] Setup: 1 setup Conversion index: Data type: TimeOfDay Change during operation: True Array with 5 elements [0]–[4] shown below the parameter number in the display. Press [OK] and step between elements with [▲] and [▼].
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint8 Change during operation: True Option Name Description [0]* Disabled Restoring the time at power-up is disabled. Enabled Restoring the time at power-up is enabled. 0-89 Date and Time Readout Default value: Parameter type: Range, 0 - 2...
Page 76
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Open loop Motor speed is determined by applying a speed reference or by setting the speed when in hand-on mode. Open loop is also used if the drive is part of a closed-loop system based on an external PID controller providing a speed reference signal as output.
Page 77
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Constant torque For speed control of screw and scroll compressors. Provides a voltage which is optimized for a constant torque load characteristic of the motor in the entire range down to 10 Hz. Variable torque For speed control of centrifugal pumps and fans.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description High torque Allows up to 160% overtorque. [1]* Normal torque For oversized motor. Allows up to 110% overtorque. 1-06 Clockwise Direction Default value: Parameter type: [0] Normal Option Setup: All setups...
PM Motor Setup 5.3.2.2 This section describes how to set up a PM motor. Danfoss offers 2 types of PM motors: [1] Non-salient PM and [3] Salient PM. The following example covers a non-salient PM motor. Programming of PM Motors 5.3.2.3...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Rotor Detection 5.3.2.3.4 This function is the recommended selection for applications where the motor starts from standstill, for example, pumps or conveyors. On some motors, a sound is heard when the drive performs the rotor detection. This does not harm the motor. Parking 5.3.2.3.5 This function is the recommended selection for applications where the motor is rotating at slow speed, for example, windmilling in fan...
Page 81
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Programming Motor Data 5.3.2.5.2 After selecting a SynRM or PMaSynRM motor, the motor-related parameters in parameter groups 1-2* Motor Data, 1-3* Adv. Motor Data, and 1-4* Adv. Motor Data II are active. The necessary data is on the motor nameplate and on the motor datasheet. Set parameter 1-24 Motor Current.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Start the motor at nominal speed. If the application does not run well, check the VVC+ SynRM and PMaSynRM settings. See recommendations for various applications in Table Table 15: Recommendations for Various Applications Application Settings Low-inertia applications...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description SynRM Use for SynRM, synchronous reluctance motors. PMaSynRM Use for PMaSynRM, Permanent Magnet assisted synchronous reluctance motors. 5.3.4 1-1* VVC+ for Synchronous Motors The default control parameters for VVC+ synchronous motors are optimized for applications where inertia load in the range of 50>Jl/ Jm>5.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True Reduces the influence of high frequency ripple and system resonance in the calculation of supply voltage. Without this filter, the ripples in the currents can distort the calculated voltage and affect the stability of the system. 1-2* Motor Data 5.3.5 This parameter group contains input data from the nameplate on the connected motor.
Page 85
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE Setting this parameter sets the following parameters to their default settings: Parameter 1-15 Low Speed Filter Time Const. Parameter 1-16 High Speed Filter Time Const. Parameter 1-17 Voltage Filter Time Const. Parameter 1-24 motor Current Parameter 1-30 Stator Resistance (Rs) Parameter 1-31 Rotor Resistance (Rr)
Page 86
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE Setting this parameter sets the following parameters to their default settings: Parameter 1-15 Low Speed Filter Time Const. Parameter 1-16 High Speed Filter Time Const. Parameter 1-17 Voltage Filter Time Const. Parameter 1-30 Stator Resistance (Rs) Parameter 1-31 Rotor Resistance (Rr) Parameter 1-33 Stator Leakage Reactance (X1)
Page 87
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter the value from the motor nameplate data. The default value corresponds to the nominal rated output. This parameter is available when parameter 1-10 Motor Construction is set to [1] PM, non-salient SPM, [2] PM, salient IPM, [5] SynRM, and [6] PMaSynRM. 1-28 Motor Rotation Check Default value: [0] Off...
Page 88
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE Ensure that a value is set in parameter 14-43 Motor Cosphi before running AMA II. Option Name Description [0]* Enable complete AMA Performs • AMA of the stator resistance R •...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE If 1 of the settings in parameter group 1-2* Motor Data is changed, parameter 1-30 Stator Resistance (Rs) to parameter 1-39 Motor Polesreturn to their default settings. NOTICE AMA works problem-free on 1 motor size down, typically works on 2 motor sizes down, rarely works on 3 sizes down, and never works on 4 sizes down.
Page 90
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions ω Par. 1-37 Par. 1-30 d-axis equivalent circuit Par. 1-37 ω Par. 1-30 Par. 1-40 ω λ q-axis equivalent circuit Figure 30: Motor Equivalent Circuit Diagram for a PM Non-salient Motor 1-30 Stator Resistance (Rs) Default value: Size related...
Page 91
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Set the rotor resistance value R to improve shaft performance using 1 of these methods: Run an AMA on a cold motor. The drive measures the value from the motor. All compensations are reset to 100%. Enter the R value manually.
Page 92
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint32 Change during operation: False NOTICE This parameter cannot be adjusted while the motor is running. NOTICE Parameter 1-35 Main Reactance (Xh) has no effect when parameter 1-10 Motor Construction is set to [1] PM, non-salient SPM. Set the main reactance of the motor using 1 of these methods: Run an AMA on a cold motor.
Page 93
There is no general standard. The different setups of stator winding resistance and induction are shown in the illustration Stator Winding Setups. Danfoss AC drives always require the line-to-common value. The back EMF of a PM motor is defined as induced EMF developed across any of 2 phases of stator winding of a free-running motor.
Page 94
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Permanent magnet motors Line-to-line back EMF in RMS value at 1000 RPM speed (mech) Figure 32: Machine Parameter Definitions of Back EMF of PM Motors 1-38 q-axis Inductance (Lq) Default value: Size related Parameter type: Range, 0.001 - 1000 mH...
Page 95
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 1-40 Back EMF at 1000 RPM Default value: Size related Parameter type: Range, 1 - 9000 V Setup: All setups Conversion index: Data type: Uint16 Conversion index: False NOTICE This parameter is only active when parameter 1-10 Motor Construction is set to options that enable PM (permanent magnet) motors.
Page 96
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Use this parameter to optimize the torque estimate in the full speed range. The estimated torque is based on the shaft power, P shaft .
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 1-49 q-axis Inductance Sat. Point Default value: Size related Parameter type: Range, 1 - 500% Setup: All setups Conversion index: Data type: Uint16 Change during operation: False NOTICE Run an AMA to set the value of this parameter. Edit the value manually only when the application requires a value other than determined by AMA.
Page 98
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Set the required speed for normal magnetizing current. If the speed is set lower than the motor slip speed, parameter 1-50 Motor Magnetisation at Zero Speed and parameter 1-51 Min Speed Normal Magnetising [RPM] are of no significance. Use this parameter along with parameter 1-50 Motor Magnetisation at Zero Speed.
Page 99
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 1-54 Voltage Reduction in Fieldweakening Default value: Parameter type: Range, -50 - 100 V Setup: All setups Conversion index: Data type: Int8 Change during operation: True The value of this parameter reduces the maximum voltage available for the flux of the motor in field weakening, providing more voltage for torque.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: False NOTICE This parameter is only available in VVC+. NOTICE This parameter is active when parameter 1-73 Flying Start is enabled. Sets the current level for the flying start test pulses that are used to detect the motor direction.
Page 101
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Motor size [kW] Changeover [Hz] 0.25–7.5 <10 11–45 <5 55–550 <3–4 Par.1-60 Par.1-61 100% Changeover Figure 36: Low-speed Load Compensation 1-61 High Speed Load Compensation Default value: Parameter type: 100% Range, 0 - 300% Setup: All setups...
Page 102
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Int16 Change during operation: True NOTICE Parameter 1-62 Slip Compensation only has effect when parameter 1-10 Motor Construction = [0] Asynchron. Enter the % value for slip compensation to compensate for tolerances in the value of n .
Page 103
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint32 Change during operation: True NOTICE If parameter 40-50 Flux Sensorless Model Shift is set to [0] Off, this parameter is ignored. Enter the minimum motor current at low speed, see parameter 1-53 Model Shift Frequency.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE This parameter cannot be adjusted while the motor is running. The system inertia and parameter 7-08 Speed PID Feed Forward Factor is used to calculate acceleration feed forward for the speed PID controller.
Page 105
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Select the start function during start delay. This parameter is linked to parameter 1-71 Start Delay. Option Name Description DC hold/motor preheat Energize the motor with a DC hold current (parameter 2-00 DC Hold Current) during the start delay time.
Page 106
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The flying-start function used for PM motors is based on an initial speed estimation. The speed is always estimated as the 1st thing after an active start signal is given. Based on the setting of parameter 1-70 Start Mode, the following happens: Parameter 1-70 Start Mode = [0] Rotor Detection: If the speed estimate appears as greater than 0Â...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True NOTICE Parameter 1-78 Compressor Start Max Speed [Hz] has no effect when parameter 1-10 Motor Construction = [1] PM, nonsalient SPM. The parameter enables high starting torque. This is a function where the current limit and torque limit are ignored during start of the motor.
Page 108
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions [1] PM non-salient: [0] Coast ¢ Option Name Description [0]* Coast Leaves motor in free mode. The motor is disconnected from the drive. DC hold/motor preheat Energizes the motor with a DC hold current (see parameter 2-00 DC Hold Current).
Page 109
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 1-86 1-71 1-79 Figure 37: Advanced Minimum Speed Monitoring Parameter 1-79 Pump Start Max to Trip. This time includes Parameter 1-71 Start Delay 1-71 1-79 the time in T 1-71 Parameter 1-86 Trip Speed Low [RPM].
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter the low limit for the motor speed at which the drive trips. If the value is 0, the function is not active. If the speed at any time after the start (or during a stop) drops below the value in the parameter, the drive trips with alarm 49, Speed Limit.
Page 111
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [20] ATEX ETR Activates the thermal monitoring function for Ex-e motors for ATEX. Enables parameter 1-94 ATEX ETR cur.lim. speed reduction, parameter 1-98 ATEX ETR interpol. points freq., and parameter 1-99 ATEX ETR interpol points current.
Page 112
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE This parameter cannot be adjusted while the motor is running. NOTICE Set digital input to [0] PNP - Active at 24 V in parameter 5-00 Digital I/O Mode. ...
Page 113
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Pt1000 1 kΩ at 0 °C (32 °F). Ni1000 (6178 ppm/K) 1 kΩ at 0 °C (32 °F). Ni1000-LG (TC5) Examples: • Siemens LG-Ni1000 • Tasseron RTD Ni1000-TC5 1000 Ohm 1-96 Thermistor Sensor Resource Default value: Parameter type: [0] None...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 100% 5 Hz 15 Hz 25 Hz 50 Hz Figure 39: Example of ATEX ETR Thermal Limitation Curve 1-99 ATEX ETR Interpol. Points Current Default value: Parameter type: Size related Range, 0 - 100%, Array [4] Setup: 2 setups...
Page 115
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 39 42 53 54 12 13 18 33 20 <800 Ω >2.7 kΩ PTC / Thermistor Figure 41: PTC Thermistor Connection - Digital Input Using an analog input and 10 V as supply: Example: The drive trips when the motor temperature is too high. Parameter setup: Set parameter 1-90 Motor Thermal Protectionto [2] Thermistor Trip.
Page 116
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions t [s] 2000 1000 = 2 x f (parameter 1-23) = 1 x f = 0.2 x f (parameter 1-24) Figure 43: ETR Profile 5.3.11.1.3 ATEX ETR The VLT® PTC Thermistor Card MCB 112 offers ATEX-approved monitoring of motor temperature. Alternatively, an external ATEX- approved PTC protection device can be used.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE Compare the minimum switching frequency requirement stated by the motor manufacturer to the minimum switching frequency of the drive, the default value in parameter 14-01 Switching Frequency. If the drive does not meet this requirement, use a sine- wave filter.
Page 118
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter a value for holding current as a percentage of the rated motor current I set in parameter 1-24 Motor Current. 100% DC hold current corresponds to I . This parameter holds the motor function (holding torque) or preheats the motor. This parameter is active if DC hold is selected in parameter 1-72 Start Function or parameter 1-80 Function at Stop.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Set the duration of the parking current set in parameter 2-06 Parking Current, once activated. 2-1* Brake Energy Funct. 5.4.2 This parameter group contains dynamic brake parameters. The parameters in this group are only valid for drives with brake chopper. 2-10 Brake Function Default value: –...
Page 120
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Parameter 2-12 Brake Power Limit (kW) is the expected average power dissipated in the brake resistor over a period of 120 s. It is used as the monitoring limit for parameter 16-33 Brake Energy Average and thereby specifies when a warning/alarm is to be given. To calculate parameter 2-12 Brake Power Limit (kW), the following formula can be used.
Page 121
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Trip 30s Trips the drive and shows an alarm when the calculated power exceeds 100% of the monitoring limit. Warning & trip 30s Activates both of the above, including warning and alarm. Warning 60s Activates a warning on the display when the power transmitted during the duty time exceeds 100% of the monitoring limit...
Page 122
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 2: The DC-link ripple amplitude is measured for 300 ms with the brake turned on. If the DC-link ripple amplitude while braking is lower than the DC-link ripple amplitude before braking +1%: Brake check has ¢...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The unit selected in parameter 3-00 Reference Range. If [9] Positioning is selected in parameter 1-00 Configuration Mode , this parameter defines the default speed for positioning. 3-04 Reference Function Default value: [0] Sum Parameter type:...
Page 126
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 20: Preset Referenece Bits (continued) Preset ref. bit Preset ref. 6 Preset ref. 7 3-11 Jog Speed [Hz] Default value: Size related Parameter type: Range, 0 - par. 4-14 Hz Setup: All setups Conversion index:...
Page 127
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The actual reference, X, is increased or decreased with percentage Y, which gives the resulting actual reference, Z. The actual reference (X) is the sum of the inputs selected in: Parameter 3-15 Reference Resource 1.
Page 128
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [23] Analog Input X42/1 [24] Analog Input X42/3 [25] Analog Input X42/5 [29] Analog Input X48/2 [30] Ext. closed loop 1 [31] Ext. closed loop 2 [32] Ext.
Page 129
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [23] Analog Input X42/1 [24] Analog Input X42/3 [25] Analog Input X42/5 [29] Analog Input X48/2 [30] Ext. closed loop 1 [31] Ext. closed loop 2 [32] Ext.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [24] Analog Input X42/3 [25] Analog Input X42/5 [29] Analog Input X48/2 [30] Ext. closed loop 1 [31] Ext. closed loop 2 [32] Ext. closed loop 3 [35] Digital input select The drive selects AI53 or AI54 as the reference source based on...
Page 131
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 3-41 Ramp 1 Ramp Up Time Default value: Size related Parameter type: Range, 0.10 - 3600 s Setup: All setups Conversion index: Data type: Uint32 Change during operation: True Enter the ramp-up time, that is the acceleration time from 0 RPM to parameter 1-25 Motor Nominal Speed. Select a ramp-up time such that the output current does not exceed the current limit in parameter 4-18 Current Limit during ramping.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter the ramp-down time, that is the deceleration time from parameter 1-25 Motor Nominal Speed–0 RPM. Select a ramp-down time preventing overvoltage from arising in the inverter due to regeneratibe operation of the motor. The ramp-down time should also be long enough to prevent that the generated current exceeds the current limit set in parameter 4-18 Current Limit See ramp-up time in parameter 3-51 Ramp 2 Ramp Up Time.
Page 133
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions P 4-13 RPM high limit Reference P 1-25 Motor speed P 4-11 RPM low limit Time P 3-81 Qramp Qstop Figure 51: Quick Stop Ramp Time 3-84 Initial Ramp Time Default value: Parameter type: Range, 0 - 60 s...
Page 134
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions To protect ball check valves in a stop situation, the check valve ramp can be utilized as a slow ramp rate from parameter 4-11 Motor Speed Low Limit [RPM] or parameter 4-12 Motor Speed Low Limit [Hz] to check valve ramp and speed, which is set in parameter 3-86 Check Valve Ramp End Speed [RPM] or parameter 3-87 Check Valve Ramp End Speed [hz].
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 3-9* Digital Pot.Meter 5.5.6 Use the digital potentiometer function to increase or decrease the actual reference by adjusting the setup of the digital inputs using the functions increase, decrease, or clear. To activate the function, at least 1 digital input must be set to increase or decrease. 3-90 Step Size Default value: 0.1%...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 3-94 Minimum Limit Default value: Parameter type: Range, -200 - 200% Setup: All setups Conversion index: Data type: Int16 Change during operation: True Set the minimum allowed value for the resulting reference. This is recommended if the digital potentiometer is used for fine-tuning of the resulting reference.
Page 137
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 4-10 Motor Speed Direction Default value: [0] Clockwise Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: False NOTICE This parameter cannot be adjusted while the motor is running. Select the motor speed directions required.
Page 138
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter the maximum limit for motor speed. The motor speed high limit can be set to correspond to the manufacturer’s maximum nominal motor speed. The motor speed high limit must exceed the setting in parameter 4-11 Motor Speed Low Limit [RPM]. 4-14 Motor Speed High Limit [Hz] Default value: Size related...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE If [20] ATEX ETR is selected in parameter 1-90 Motor Thermal Protection, set parameter 4-18 Current Limit current limit to 150%. This is a true current limit function that continues in the oversynchronous range. However, due to field weakening the motor torque at current limit will drop accordingly when the voltage increase stops above the synchronized speed of the motor.
Page 140
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions motor ON REF (P 4-18) HIGH (P 4-51) IN RANGE (P 4-50) [RPM] motor HIGH (P 4-11) (P 4-52) (P 4-53) (P 4-13) Figure 56: Adjustable Warnings 4-50 Warning Current Low Default value: Parameter type: Range, 0 - setting in par.
Page 141
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 4-53 Warning Speed High Default value: Size related Parameter type: Range, setting in par. 4-52 - 60000 RPM Setup: Conversion index: All setups Data type: Uint16 Change during operation: True Enter the n value.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter the upper feedback limit. When the feedback exceeds this limit, the display reads Feedb . The signal outputs can be High programmed to produce a status signal on terminal 27 or 29 and on relay output 01 or 02. 4-58 Missing Motor Phase Function Default value: –...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 4-61 Bypass Speed From [Hz] Default value: Size related Parameter type: Range, 0 - setting in par. 4-14 Hz, Array [4] Setup: Conversion index: All setups Data type: Uint16 Change during operation: True Some systems require that certain output frequencies or speeds are avoided due to resonance problems in the system.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Select [1] Enabled in parameter 4-64 Semi-auto Bypass Set-up. Press [Hand On] on the LCP to start the search for frequency bands causing resonances. The motor ramps up according to the ramp set.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Converison index: – Data type: Uint8 Change during operation: True Option Name Description [0]* Input Defines terminal 27 as a digital input. Output Defines terminal 27 as a digital output. 5-02 Terminal 29 Mode Default value: Parameter type:...
Page 146
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 22: Digital Input Functions and Terminals (continued) Digital input function Select Terminal External interlock Start All, terminal 18 Latched start Reversing [10] Start reversing [11] [14] All, terminal 29 Preset reference on [15] Preset ref bit 0...
Page 147
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 22: Digital Input Functions and Terminals (continued) Digital input function Select Terminal Counter B (down) [64] Terminal 29, 33 Reset Counter B [65] Sleep mode [66] Reset preventive maintenance. word [78] PTC card 1 [80]...
Page 148
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 22: Digital Input Functions and Terminals (continued) Digital input function Select Terminal Emcy mode ref bit 2 [192] Emergency setup bit 0 [193] Emergency setup bit 1 [194] Test emcy mode [195] Reset emcy mode [196]...
Page 149
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 23: Digital Inputs, Function Descriptions - 1 (continued) Option Function External interlock Same function as coasting inverse and stop inverse, but this op- tion generates the alarm message External fault on the display when the terminal programmed for coast inverse has signal 0.
Page 150
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 24: Preset Reference Bit (continued) Preset ref. bit Preset ref. 5 Preset ref. 6 Preset ref. 7 Table 25: Digital Inputs, Function Descriptions - 2 Option Function [19] Freeze ref Freezes the actual reference, which is now the point of en- able/condition to be used for [21] Speed up and [22] Speed down.
Page 151
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 27: Digital Inputs, Function Descriptions - 3 Option Function [22] Speed down Same as [21] Speed up. [23] Set-up select bit 0 Select [23] Set-up select bit 0 or select [24] Set-up select bit 1 to select 1 of the 4 set-ups.
Page 152
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 29: Digital Inputs, Function Descriptions - 4 (continued) Option Function [52] Run permissive The input terminal, for which the run permissive has been pro- grammed, must be logic 1 before a start command can be ac- cepted.
Page 153
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 29: Digital Inputs, Function Descriptions - 4 (continued) Option Function [61] Counter A (down) (Terminal 29 or 33 only). Input for decrement counting in the SLC counter. [62] Reset Counter A Input for reset of counter A.
Page 154
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 29: Digital Inputs, Function Descriptions - 4 (continued) Option Function [136] Pump 7 interlock See explanation in [130] Pump1 interlock. [137] Pump 8 interlock See explanation in [130] Pump1 interlock. [138] Pump 9 interlock See explanation in [130] Pump1 interlock.
Page 155
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 5-10 Terminal 18 Digital Input Default value: – Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Select the function from the available digital input range. All functions are described in Table Table Table...
Page 156
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [52] Run permissive [53] Hand start [54] Auto start [55] DigiPot increase [56] DigiPot decrease [57] DigiPot clear [62] Reset counter A [65] Reset counter B [66] Sleep mode [78] Reset maint.
Page 157
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [145] Pump 7 inverse interlock [146] Pump 8 inverse interlock [147] Pump 9 inverse interlock [190] Emcy mode ref bit 0 [191] Emcy mode ref bit 1 [192] Emcy mode ref bit 2 [193]...
Page 158
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description DC-brake inverse Stop inverse External interlock Start Latched start [10] Reversing [11] Start reversing [14] [15] Preset reference on [16] Preset ref bit 0 [17] Preset ref bit 1 [18] Preset ref bit 2 [19]...
Page 159
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [62] Reset counter A [63] Counter B (up) [64] Counter B (down) [65] Reset counter B [66] Sleep mode [78] Reset maint. word [80] PTC card 1 [85] Latched pump derag [86]...
Page 160
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [191] Emcy mode ref bit 1 [192] Emcy mode ref bit 2 [193] Emergency mode setup bit 0 [194] Emergency mode setup bit 1 [195] Test emcy mode [196] Reset emcy mode 5-14 Terminal 32 Digital Input...
Page 161
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The options for this parameter are the same as those listed for parameter 5-10 Terminal 18 Digital Input. Parameter 5-19 Terminal 37 Safe Stop Default value: [1] Safe stop alarm Parameter type: Option Setup:...
Page 162
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 30: Overview of Functions, Alarms, and Warnings Function Number Relay No function – – Safe Torque Off alarm [1]* – Safe Torque Off [A68 Safe Torque Off warning – Safe Torque Off [W68 PTC 1 alarm PTC 1 Safe Torque Off [A71]...
Page 163
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [17] Preset ref bit 1 [18] Preset ref bit 2 [19] Freeze reference [20] Freeze output [21] Speed up [22] Speed down [23] Set-up select bit 0 [24] Set-up select bit 1 [34]...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint8 Change during operation: True The options for this parameter are the same as those listed for parameter 5-20 Terminal X46/1 Digital Input. 5-23 Terminal X46/7 Digital Input Default value: Parameter type: Size related...
Page 166
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint8 Change during operation: True Select the function from the available digital output range. Option Name Description No operation Default for all digital outputs and relay outputs. Control ready The control board receives supply voltage.
Page 167
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [21] Thermal warning The thermal warning turns on when the temperature exceeds the limit in the motor, the drive, the brake resistor, or the thermistor. [25] Reverse Reversing.
Page 168
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [59] Remote,enable,no TW [60] Comparator 0 See parameter group 13-1* Comparators. If comparator 0 is evaluated as true, the output goes high. Otherwise, it is low. [61] Comparator 1 See parameter group 13-1* Comparators.
Page 169
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [79] Logic rule 9 See parameter group 13-4* Logic Rules. If logic rule 9 is evaluated as true, the output goes high. Otherwise, it is low. [80] SL digital output A See parameter group 13-52 SL Controller Action.
Page 170
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [160] No alarm The output is high when no alarm is present. [161] Running reverse The output is high when the drive is running counterclockwise (the logical product of the status bits running AND reverse). [164] Local ref active, not OFF [165]...
Page 171
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [194] Broken belt A broken-belt condition has been detected. Enable this function in parameter 22-60 Broken Belt Function. [195] Bypass valve control The bypass valve control (digital/relay output in the drive) is used for compressor systems to unload the compressor during start-up by using a bypass valve.
Page 172
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [201] Pump 1 running One or more of the pumps controlled by the cascade controller are running. The function also depends on the setting in parameter 25-05 Fixed Lead Pump. If set to [0] No, Pump 1 refers to the pump controlled by relay1, and so on.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [250] Emcy mode limits During emergency mode operation, 1 of the critical alarms has been activated and suppressed by emergency mode. This may lead to reduced drive performance and expected operation lifetime before service is required.
Page 174
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 5-40 Function Relays Default value: – Parameter type: Option, Array [20] Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Select options to define the function of the relays. The selection of each mechanical relay is realized in an array parameter. Option Name Description...
Page 175
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [18] Out of feedb. range Feedback is outside the range set in parameter 4-56 Warning Feedback Low and parameter 4-57 Warning Feedback High. [19] Below feedback, low Feedback is below the limit set in parameter 4-56 Warning Feedback Low.
Page 176
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [41] Below reference, low Active when the actual speed is below speed reference setting. [42] Above ref, high Active when actual speed is above speed reference setting. [45] Bus ctrl.
Page 177
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [68] Comparator 8 See parameter group 13-1* Comparators . If comparator 8 in SLC is true, the output goes high. Otherwise, it is low. [69] Comparator 9 See parameter group 13-1* Comparators .
Page 178
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [81] SL digital output B See parameter 13-52 SL Controller Action. Output B is low on smart logic action [33] Set digital out B low. Output B is high on smart logic action [39] Set digital out B high.
Page 179
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [165] Local ref active The output is high when parameter 3-13 Reference Siteis set to [2] Local or when parameter 3-13 Reference Site is set to [0] Linked to hand/auto at the same time as the LCP is in hand-on mode.
Page 180
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [196] Fire mode The drive operates in fire mode. See parameter group 24-0* Fire Mode . [197] Fire mode was act. The drive has been operating in fire mode. In software version 7.2X, this output is only active 1 min after fire mode is stopped.
Page 181
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [246] RS flipflop 6 See parameter group 13-1* Comparators . [247] RS flipflop 7 See parameter group 13-1* Comparators . 5-41 On Delay, Relay Default value: Parameter type: 0.01 s Range, 0.01 - 600 s, Array [20] Setup:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions If the selected event condition changes before the on delay or off delay timer expires, the relay output is unaffected. 5-5* Pulse Input 5.7.5 The pulse input parameters are used to define an appropriate window for the impulse reference area by configuring the scaling and filter settings for the pulse inputs.
Page 183
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Int32 Change during operation: True Enter the low reference value limit for the motor shaft speed [RPM]. This is also the lowest feedback value, see also parameter 5-57 Term. 33 Low Ref./Feedb.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 5-57 Term. 33 Low Ref./Feedb. Value Default value: 0 ReferenceFeedbackUnit Parameter type: Range, -999999.999 - 999999.999 ReferenceFeedbackUnit Setup: All setups Conversion index: Data type: Int32 Change during operation: True Enter the low reference value [RPM] for the motor shaft speed. This is also the low feedback value, see also parameter 5-52 Term. 29 Low Ref./Feedb.
Page 185
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Output value High output value P 5-60(term27) P 5-63(term29) High freq. Output P 5-62(term27) (Hz) P 5-65(term29) Figure 61: Pulse Output 5-60 Terminal 27 Pulse Output Variable Default value: [0] No operation Parameter type: Option Setup:...
Page 186
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 5-62 Pulse Output Max Freq #27 Default value: 5000 Hz Parameter type: Range, 0 - 32000 Hz Setup: All setups Conversion index: Data type: Uint32 Change during operation: True Set the maximum frequency for terminal 27 corresponding to the output variable selected in parameter 5-60 Terminal 27 Pulse Output Variable.
Page 187
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint32 Change during operation: True Set the maximum frequency for terminal 27 corresponding to the output variable selected in parameter 5-60 Terminal 27 Pulse Output Variable. 5-66 Terminal X30/6 Pulse Output Variable Default value: [0] No operation Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 5-8* I/O Options 5.7.7 AHF capacitor connect output function for digital and relay outputs Functional description: Connect capacitors at 20% nominal power. Hysteresis ±50% of 20% nominal power (=minimum 10% and maximum 30% nominal power). Off delay timer = 10 s.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 5-80 AHF Cap Reconnect Delay Default value: 25 s Parameter type: Range, 1 - 120 s Setup: 2 setups Conversion index: Data type: Uint16 Change during operation: True Guarantees a minimum off-time for the capacitors. The timer starts once the AHF capacitor disconnects and has to expire before the output is allowed to be on again.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 5-95 Pulse Out #29 Bus Control Default value: Parameter type: Range, 0 - 100% Setup: All setups Conversion index: Data type: Change during operation: True Set the output frequency transferred to output terminal 29 when the terminal is configured as [45] Bus Controlled in parameter 5-63 Terminal 29 Pulse Output Variable.
Page 191
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 6-00 Live Zero Timeout Time Default value: 10 s Parameter type: Range, 1 - 99 s Setup: All seutps Conversion index: Data type: Uint8 Change during operation: True Enter the live zero timeout in s. Live zero timeout time is active for analog inputs, that is terminal 53 or terminal 54, used as reference or feedback sources.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Ref./Feedback [RPM] Par 6-xx 1500 High R ef./ Feedb . Value 1200 Par 6-xx Low R ef ./ Feedb . Value 10 V Par 6-xx Analog input Low voltage or low current Par 6-xx High voltage or...
Page 193
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Int16 Change during operation: True Enter the low voltage value. This analog input scaling value should correspond to the minimum reference value set in parameter 6-14 Terminal 53 Low Ref./Feedb. Value. 6-11 Terminal 53 High Voltage Default value: 10 V...
Page 194
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter the analog input scaling value that corresponds to the maximum reference feedback value set in parameter 6-11 Terminal 53 High Voltage and parameter 6-13 Terminal 53 High Current. 6-16 Terminal 53 Filter Time Constant Default value: 0.005 s Parameter type:...
Page 195
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter the high voltage value. This analog input scaling value should correspond to the high reference feedback value set in parameter 6-25 Terminal 54 High Ref./Feedb. Value. 6-22 Terminal 54 Low Current Default value: 4 mA Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE This parameter cannot be adjusted while the motor is running. Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal 54. Increasing the value improves dampening but also increases the time delay through the filter.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Int32 Change during operation: True Sets the analog input scaling value to correspond to the low voltage value (set in parameter 6-30 Terminal X30/11 Low Voltage). 6-35 Term. X30/11 High Ref./Feedb. Value Default value: Parameter type: 100 ReferenceFeedbackUnit...
Page 198
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Int16 Change during operation: True Sets the analog input scaling value to correspond to the low reference feedback value set in parameter 6-44 Term. X30/12 Low Ref./ Feedb. Value. 6-41 Terminal X30/12 High Voltage Default value: 10 V...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Disables the live zero monitoring, for example, if the analog outputs are used as part of a decentral I/O system (when an analog output does not fulfil any control function, but feeds a data storage device).
Page 200
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [107] Speed 0–HighLim 0–Speed high limit (parameter 4-13 Motor Speed High Limit [RPM] and parameter 4-14 Motor Speed High Limit [Hz], 0— 20 mA. [108] Torque ±160% 0–20 mA. [109] Out frq 0–f [113]...
Page 201
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [157] Flow rate 4–20mA [184] Mirror AI53 mA [185] Mirror AI54 mA [210] Sensorless signal [254] DC link With this parameter selected, the terminal output shows the scaled DC-link voltage.
Page 202
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 6-51 Terminal 42 Output Min Scale Default value: Parameter type: Range, 0 - 200% Setup: All setups Conversion index: Data type: Int16 Change during operation: True Scale for the minimum output (0 mA or 4 mA) of the analog signal at terminal 42. Set the value to be the percentage of the full range of the variable selected in parameter 6-50 Terminal 42 Output.
Page 203
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 20 mA 0/4 mA 100% 50Hz 100Hz Figure 66: Example 1 Example 2 Variable = feedback, range = -200% to +200%. Range needed for output = 0–100%. Output signal 0 mA or 4 mA is needed at 0% (50% of range). Set parameter 6-51 Terminal 42 Output Min Scaleto 50%. Output signal 20 mA is needed at 100% (75% of range).
Page 204
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 20 mA 10 mA 0/4 mA 100% 200% Min ref Max ref Max ref X 20/10 Figure 68: Example 3 6-53 Term 42 Output Bus Ctrl Default value: Parameter type: Range, 0 - 100% Setup: All setups...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 34: Readout Parameters Selection 0–20 mA 4–20 mA Motor current (I [103] [133] Torque limit (0–T [104] [134] Rated torque (0–T [105] [135] Power (0–P [106] [136] nom) Speed (0–Speed [107] [137] Option...
Page 206
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [107] Speed 0–HighLim 0–Speed high limit (parameter 4-13 Motor Speed High Limit [RPM] and parameter 4-14 Motor Speed High Limit [Hz], 0— 20 mA. [108] Torque ±160% 0–20 mA. [109] Out frq 0–f [113]...
Page 207
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [157] Flow rate 4–20mA [184] Mirror AI53 mA [185] Mirror AI54 mA [210] Sensorless signal [254] DC link With this parameter selected, the terminal output shows the scaled DC-link voltage.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: True Holds the preset level of output X30/8. If a timeout function is selected in parameter 6-60 Terminal X30/8 Output, the output is preset to this level if a fieldbus timeout occurs.
Page 209
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [116] Cascade reference [117] Shaft power [118] Shaft power 4–20 mA [130] Out frq 0–100 4–20mA 0–100 Hz. [131] Reference 4–20mA Minimum reference–maximum reference. [132] Feedback 4–20mA -200% to 200% of parameter 3-03 Maximum Reference. [133] Motor cur.
Page 210
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 6-71 Terminal X45/1 Min. Scale Default value: Parameter type: Range, 0 - 200% Setup: All setups Conversion index: Data type: Int16 Change during operation: True Scale the minimum output of the selected analog signal at terminal X45/1 as a percentage of the maximum signal value. For example, if 0 mA (or 0 Hz) is required at 25% of the maximum output value, then program 25%.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 6-74 Terminal X45/1 Output Timeout Preset Default value: Parameter type: Range, 0 - 100% Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: True Holds the preset level of analog output 3 (terminal X45/1). If there is a fieldbus timeout and a timeout function is selected in parameter 6-70 Terminal X45/1 Output, the output is preset to this level.
Page 212
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [114] Ext. closed loop 2 0–100% (0–20 mA). [115] Ext. closed loop 3 0–100% (0–20 mA). [116] Cascade reference [117] Shaft power [118] Shaft power 4–20 mA [130] Out frq 0–100 4–20mA 0–100 Hz.
Page 213
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [254] DC link With this parameter selected, the terminal output shows the scaled DC-link voltage. See also the tables and illustration in parameter 6-50 Terminal 42 Output. [255] DC link 4–20mA The function is the same as [254] DC Link 0–20 mA.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Parameter Group 7-** Controllers Speed PID Droop 5.9.1 This feature implements precise torque sharing between multiple motors on a common mechanical shaft. Speed PID droop is useful for marine and mining applications where redundancy and higher dynamics are required. Speed PID droop allows to reduce inertia by utilizing multiple small motors instead of 1 large motor.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enabling PID droop To enable speed PID droop: Run the drive in 1 of the following modes: Flux closed loop (parameter 1-01 Motor Control Principle, [3] Flux w/ motor feedb). ¢...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Drive 1 Speed Torque Setpoint Ramp Calculation Drive 2 Speed Torque Setpoint External Setpoint Ramp Calculation Droop Drive 3 Torque Speed Setpoint Ramp Calculation Droop Figure 71: Concept of Speed Trim The drawing shows a single-source setup where the master sends the torque signal to all followers.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 7-03 Speed PID Integral Time Default value: Size related Parameter type: Range, 1.0 - 20000 ms Setup: All setups Conversion index: Data type: Uint32 Change during operation: True Enter the speed controller integral time, which determines the time the internal PID control takes to correct errors. The greater the error, the more quickly the gain increases.
Page 218
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Digital and ctrl.word Use both digital input and control word. Digital only Use digital inputs only. Controlword only Use control word only. 8-02 Control Word Source Default value: –...
Page 219
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 8-04 Control Word Timeout Function Default value: [0] Off Parameter type: Option Setup: 1 setup Conversion index: – Data type: Uint8 Change during operation: True Select the timeout function. The timeout function activates when the control word and reference fails to be updated within the time period specified in parameter 8-03 Control Word Timeout Time.
Page 220
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Select the action after receiving a valid control word following a timeout. This parameter is active only when parameter 8-04 Control Word Timeout Function is set to: [7] Setup 1 [8] Setup 2 [9] Setup 3 [10] Setup 4...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 8-08 Readout Filtering Default value: – Parameter type: Option, Array [1] Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Use this function if the speed feedback value readouts on the fieldbus fluctuate. Select [1] Motor Data LP-Filter if the function is required. A power cycle is required for changes to take effect.
Page 222
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Select the interpretation of the control and status words corresponding to the installed fieldbus. Only the selections valid for the fieldbus installed in slot A are visible in the LCP display. For guidelines in selection of [0] FC profile and [1] PROFIdrive profile, refer to the product- specific design guide.
Page 223
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [14] T32DI status The bit indicates the status of terminal 32. 0 indicates that the terminal is low. 1 indicates that the terminal is high. [15] T33DI status The bit indicates the status of terminal 33.
Page 224
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [70] Logic rule 0 See parameter group 13-4* Logic Rules. If logic rule 0 is evaluated as true, the output goes high. Otherwise, it is low. [71] Logic rule 1 See parameter group 13-4* Logic Rules.
Page 225
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [85] SL digital out F See parameter group 13-52 SL Controller Action. The output goes high whenever the smart logic action [43] Set digital out F high is executed.
Page 226
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description CTW valid, active low If set to 1, the drive ignores the remaining bits of the control word. External interlock [10] Bit 10=0 >CTW timeout [15] Relay 1 [16] Relay 2 [20]...
Page 227
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* 10 Volts low warning Live zero warning No motor warning Mains phase loss warning DC link voltage high warning DC link voltage low warning DC overvoltage warning DC undervoltage warning Inverter overloaded warning [10]...
Page 228
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [58] AMA internal fault warning [59] Current limit warning [60] External interlock warning [61] Feedback error warning [62] Frequency max warning [64] Voltage limit warning [65] Controlboard overtemp warning [66] Heatsink temp low warning [68]...
Page 229
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [10032] Phase W missing alarm [10033] Inrush fault alarm [10034] Fieldbus com faul alarm [10036] Mains failure alarm [10037] Phase imbalance alarm [10038] Internal fault [10039] Heatsink sensor alarm [10045] Earth fault 2 alarm [10046]...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint32 Change during operation: True Select 0 to read out the actual fieldbus product code according to the mounted fieldbus option. Select 1 to read out the actual vendor ID. 5.10.3 8-2* Counters 8-20 Invalid Memory Write Counter...
Page 231
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter the address for the drive (standard) port. Valid range: Depends on the selected protocol. 8-32 FC Port Baud Rate Default value: – Parameter type: Option Setup: 1 setup Conversion index: –...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 8-35 Minimum Response Delay Default value: 10 ms Parameter type: Range, 5 - 10000 ms Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: True Specify the minimum delay time between receiving a request and transmitting a response. This is used for overcoming modem turnaround delays.
Page 233
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: True Option Name Description [1]* Standard telegram 1 Enables use of freely configurable telegrams or standard telegrams for the FC port. [100] None [101]...
Page 234
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: – Data type: Uint8 Change during operation: False NOTICE This parameter cannot be adjusted while the motor is running. Option Name Description [0]* Write to active setup Commit transaction Commit all parameters that have been sent during BTM mode.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: False Select the BTM timeout after a BTM transaction has been started. Timeout is between each acyclic write of parameters. 8-48 BTM Maximum Errors Default value: Parameter type: Range, 0 - 21...
Page 236
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 8-51 Quick Stop Select Default value: – Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Select the control of the quick stop function via the terminals and/or via the bus. Option Name Description...
Page 237
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Logic AND The fieldbus/serial communication port and a digital input trigger the start function. [3]* Logic OR The fieldbus/serial communication port or a digital input triggers the start function. 8-54 Reversing Select Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Select the trigger for the preset reference selection. Option Name Description Digital input A digital input triggers the preset reference selection. A serial communication port or the fieldbus triggers the preset reference selection.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE This parameter is active only when parameter 8-30 Protocol is set to [5] BACnet or [9] FC Option. Define how many info/data frames the device is allowed to send while holding the token. 8-74 I-AM Service Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 8-81 Bus Error Count Default value: Parameter type: Range, 0 - 4294967295, Array Setup: Conversion index: All setups Data type: Uint32 Change during operation: True This parameter shows the number of telegrams with faults (for example, CRC fault) detected on the bus. Parameter 8-82 Slave Messages Rcvd Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Change during operation: True This parameter allows setting of a bus feedback value via the serial communication port or options. The feedback value forms part of the feedback handling. Bus feedback may be selected as feedback source. 8-97 Response Error Codes Default value: Parameter type:...
Page 242
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [342] Ramp 1 ramp down time [351] Ramp 2 ramp up time [352] Ramp 2 ramp down time [380] Jog ramp time [381] Quick stop ramp time [411] Motor speed low limit [RPM] [412]...
Page 243
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: 2 setups Conversion index: – Data type: Uint16 Change during operation: True Select the parameters to be assigned to PCD 3–10 of the telegrams. The number of available PCDs depends on the telegram type. Values in PCD 3–10 are written to the selected parameters as data.
Page 244
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1622] Torque [%] [1623] Motor shaft power [kW] [1624] Calibrated stator resistance [1626] Power filtered [kW] [1627] Power filtered [hp] [1630] DC link voltage [1632] Brake energy /s [1633] Brake energy average [1634]...
Page 245
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1669] Pulse output #27 [Hz] [1670] Pulse output #29 [Hz] [1671] Relay output [bin] [1672] Counter A [1673] Counter B [1675] Analog in X30/11 [1676] Analog in X30/12 [1677] Analog out X30/8 [mA] [1678]...
Page 246
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1840] Analog input X49/1 [1841] Analog input X49/3 [1842] Analog input X49/5 [1843] Analog input X49/7 [1844] Analog out X49/9 [1845] Analog out X49/11 [1846] X49 digital output [bin] [1847] Last warning [1848]...
Page 247
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [106] PPO 6 [107] PPO 7 [108] PPO 8 9-23 Parameters for Signals Default value: Parameter type: [0] None Option, Array [1000] Setup: All setups Conversion index: –...
Page 248
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [597] Pulse out #30/6 bus control [615] Terminal 53 high ref./feedb. value [625] Terminal 54 high ref./feedb. value [653] Term 42 output bus ctrl [663] Terminal X30/8 bus control [673] Terminal X45/1 bus control [683]...
Page 249
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1622] Torque [%] [1623] Motor shaft power [kW] [1624] Calibrated stator resistance [1626] Power filtered [kW] [1627] Power filtered [hp] [1630] DC link voltage [1632] Brake energy /s [1633] Brake energy average [1634]...
Page 250
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1669] Pulse output #27 [Hz] [1670] Pulse output #29 [Hz] [1671] Relay output [bin] [1672] Counter A [1673] Counter B [1675] Analog in X30/11 [1676] Analog in X30/12 [1677] Analog out X30/8 [mA] [1678]...
Page 251
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1836] Analog input X48/2[mA] [1837] Temp. input X48/4 [1838] Temp. input X48/7 [1839] Temp. input X48/10 [1840] Analog input X49/1 [1841] Analog input X49/3 [1842] Analog input X49/5 [1843] Analog out X49/7 [1844]...
Page 252
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [3409] PCD 9 write to MCO [3410] PCD 10 write to MCO [3421] PCD 1 read from MCO [3422] PCD 2 read from MCO [3423] PCD 3 read from MCO [3424] PCD 4 read from MCO [3425]...
Page 253
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Parameters can be edited via: PROFIBUS The standard RS485 interface The LCP Option Name Description Disabled [1]* Enabled 9-28 Process Control Default value: [1] Enable cyclic master Parameter type: Option Setup: Conversion index: 2 setups...
Page 254
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True This buffer contains the alarm word for all alarms and warnings that have occurred since the last reset or power-up. The buffer capacity is maximum 8 error events.
Page 255
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 35: PROFIBUS Warning Word (continued) Description Wrong ID sent by PLC. Internal fault occurred. Not configured. Timeout active. Warning 34, Fieldbus Fault is active. 9-63 Actual Baud Rate Default value: Parameter type: [255] No baud rate found Option...
Page 256
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The device identification parameter. The data type is array [n] of unsigned16. The assignment of the 1st subindexes is defined and shown in the following table. Index Content Value Manufacturer 128 (for ) Device type Version...
Page 257
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 9-70 Programming Set-up Default value: [9] Active set-up 1 Parameter type: Option Setup: Conversion index: All setups – Data type: Uint8 Change during operation: True Select the setup to be programmed during operation. Option Name Description...
Page 258
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* No action Power-on reset Power-on reset prep Comm option reset 9-80 Defined Parameters (1) Default value: Parameter type: Range, 0 - 9999, Array [116] Setup: All setups Conversion index: Data type: Change during operation:...
Page 259
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 9-85 Defined Parameters (6) Default value: Parameter type: Range, 0 - 9999, Array [116] Setup: Conversion index: All setup Data type: Uint16 Change during operation: False This parameter shows a list of all the defined drive parameters available for PROFIBUS. 9-90 Changed Parameters (1) Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: 2 setups Conversion index: Data type: Uint8 Change during operation: True Select the station address. Every station connected to the same network must have an unambiguous address. 10-05 Readout Transmit Error Counter Default value: Parameter type: Range, 0 - 255...
Page 262
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Instance 100/150 Instance 101/151 Instance 20/70 Instance 21/71 Instance 102/152 10-11 Process Data Config Write Default value: – Parameter type: Option, Array [4] Setup: All setups Conversion index: –...
Page 263
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [595] Pulse out #29 bus control [597] Pulse out #30/6 bus control [615] Terminal 53 high ref./feedb. value [625] Terminal 54 high ref./feedb. value [653] Terminal 42 output bus control [663] Terminal X30/8 output bus control [673]...
Page 264
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1501] Running hours [1502] kWh counter [1600] Control word [1601] Reference [unit] [1602] Reference % [1603] Status word [1605] Main actual value [%] [1609] Custom readout [1610] Power [kW] [1611] Power [hp]...
Page 265
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1645] Motor phase U current [1646] Motor phase V current [1647] Motor phase W current [1648] Speed ref. after ramp [RPM] [1650] External reference [1652] Feedback[unit] [1653] Digi pot reference [1654] Feedback 1 [unit]...
Page 266
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1690] Alarm word [1691] Alarm word 2 [1692] Alarm word [1693] Alarm word 2 [1694] Ext. status word [1695] Ext. status word 2 [1696] Maintenance word [1697] Alarm word 3 [1698] Warning word 3...
Page 267
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [2796] Extended cascade relay output [bin] [2969] Flow [3421] PCD 1 read from MCO [3422] PCD 2 read from MCO [3423] PCD 3 read from MCO [3424] PCD 4 read from MCO [3425] PCD 5 read from MCO...
Page 268
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 36: Warning Bits Description Bus not active Explicit connection timeout I/O connection Retry limit reached Actual is not updated CAN bus off I/O send error Initialization error No bus supply Bus off Error passive Error warning...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* 10-2* COS Filters 5.12.3 10-20 COS Filter 1 Default value: Parameter type: Range, 0 - 65535 Setup: All setups Conversion index: Data type: Uint16 Change during operation: False Sets up the filter mask for the status word.
Page 270
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: 2 setups Conversion index: Data type: Uint8 Change during operation: True View array parameters. This parameter is only valid when a VLT® DeviceNet MCA 104 is installed. 10-31 Store Data Value Default value: [0] Off Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 10-34 DeviceNet Product Code Default value: Size related Parameter type: Range, 0 - 65535 Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: True Use this parameter for reading out the actual DeviceNet product code. 10-39 Devicenet F Parameters Default value: Parameter type:...
Page 272
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 12-02 Subnet Mask Default value: Parameter type: Range, 0 - 4294967295 Setup: 1 setup Conversion index: Data type: OctStr[4] Change during operation: True Configure the IP subnet mask of the option. Read-only if parameter 12-00 IP Address Assignment is set to [1] DHCP or [2] BOOTP. 12-03 Default Gateway Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 12-1* Ethernet Link Parameters 5.13.2 12-10 Link Status Default value: [0] No link Parameter type: Option, Array [2] Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True This parameter is read-only.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* None 10 Mbps 100 Mbps 12-18 Supervisor MAC Default value: Parameter type: Range, 0 - 2147483647, Array Setup: Conversion index: 2 setups Data type: OctStr[6] Change during operation: True MAC addresses of currently active supervisors.
Page 275
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [303] Maximum reference [341] Ramp 1 ramp up time [342] Ramp 1 ramp down time [351] Ramp 2 ramp up time [352] Ramp 2 ramp down time [380] Jog/homing ramp time jog ramp time [381]...
Page 276
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 12-22 Process Data Config Read Default value: – Parameter type: Option, Array [20] Setup: All setups Conversion index: – Data type: Uint16 Change during operation: True Option Name Description None [15] Readout: actual setup [894]...
Page 277
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1622] Torque [%] [1623] Motor shaft power [kW] [1624] Calibrated stator resistance [1626] Power filtered [kW] [1627] Power filtered [hp] [1630] DC link voltage [1632] Brake energy /s [1633] Brake energy average [1634]...
Page 278
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1669] Pulse output #27 [Hz] [1670] Pulse output #29 [Hz] [1671] Relay output [bin] [1672] Counter A [1673] Counter B [1675] Analog in X30/11 [1676] Analog in X30/12 [1677] Analog out X30/8 [mA] [1678]...
Page 279
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1840] Analog input X49/1 [1841] Analog input X49/3 [1842] Analog input X49/5 [1843] Analog out X49/7 [1844] Analog out X49/9 [1845] Analog out X49/11 [1846] X49 Digital output [bin] [1847] Last warning [1848]...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint8 Change during operation: True Activates a function that always stores received parameter data in the non-volatile memory (EEPROM). Option Name Description [0]* 12-3* EtherNet/IP 5.13.4 12-30 Warning Parameter Default value: Parameter type: Range, 0 - 2147483647...
Page 281
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: True Shows the reference source in instance 21/71. Option Name Description [0]* 12-32 Net Control Default value: [0] Off Parameter type: Option Setup:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 12-37 COS Inhibit Timer Default value: Parameter type: Range, 0 - 65535 Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Read-only change-of-state inhibit timer. If the option is configured for COS operation, this inhibit timer can be configured in the forward open telegram to prevent that continuously changing PCD data generates extensive network traffic.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 38: 16-Bit Status Word, Modbus TCP (continued) Description Bit = [0] Bit = [1] SMTP server Disabled Enabled Cable diagnosis Disabled Enabled Auto crossover Disabled Enabled IPMG Disabled Enabled 12-41 Slave Message Count Default value: Parameter type:...
Page 284
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: True Select which interface BACnet/IP should use. If [0] All datalinks is selected, the BACnet/IP automatically detects which BACnet layer to use.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint32 Change during operation: True This parameter shows different message counters: Index 0: Total number of received and sent messages Index 1: Total number of received bus messages Index 2: Total number of sent messages Index 3: Total number of error messages Index 4: Total number of retired (timed out) messages...
Page 286
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Use this parameter to either enable or disable the SNMP agent. Option Name Description Disabled Disable the SNMP agent. [1]* Enabled Enable the SNMP agent. 12-84 Address Conflict Detection Default value: [1] Enabled Parameter type: Option...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True Use this parameter for configuring the TCP port number for the transparent socket channel. Configuring the TCP port number enables transparent sending of FC telegrams on Ethernet via TCP. If the parameter is set to 0 (default value), the function is disabled. 12-9* Advanced Ethernet Services 5.13.9 12-90 Cable Diagnostics...
Page 288
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Disabled The IGMP snooping function is disabled. [1]* Enabled The IGMP snooping function is enabled. 12-93 Cable Error Length Default value: Parameter type: Range, 0 - 65535, Array [2] Setup: 1 setup Conversion index:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Disable Mirror port 1 to 2 Mirror port 2 to 1 [10] Port 1 disabled [11] Port 2 disabled [254] Mirror int. port to 1 [255] Mirror int. port to 2 12-97 QoS Priority Default value: Size related...
Page 290
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Smart logic control (SLC) is a sequence of user-defined actions (see parameter 13-52 SL Controller 1 Action) executed by the SLC when the associated user-defined event (see parameter 13-51 SL Controller 1 Event) is evaluated as true by the SLC. The condition for an event can be a particular status, or that the output from a logic rule or a comparator operand becomes true.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Start event P13-01 State 1 13-51.0 13-52.0 State 2 13-51.1 Stop 13-52.1 event P13-02 Stop event P13-02 State 4 13-51.3 13-52.3 State 3 13-51.2 13-52.2 Stop event P13-02 Figure 73: Example of Events and Actions Starting and stopping the SLC Start and stop the SLC by selecting [1] On or [0] Off in parameter 13-00 SL Controller Mode.
Page 292
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description False Select the boolean (true or false) input to activate smart logic control. Enters the fixed value False. True Enters the fixed value True. Running The motor runs. In range The motor runs within the programmed current and speed ranges set in parameter 4-50 Warning Current Low to parameter...
Page 293
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [22] Comparator 0 Use the result of comparator 0. [23] Comparator 1 Use the result of comparator 1. [24] Comparator 2 Use the result of comparator 2. [25] Comparator 3 Use the result of comparator 3.
Page 294
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [91] ECB bypass mode [92] ECB test mode [93] Emergency mode [94] RS Flipflop 0 See parameter group 13-1* Comparators. [95] RS Flipflop 1 See parameter group 13-1* Comparators. [96] RS Flipflop 2 See parameter group 13-1* Comparators.
Page 295
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint8 Change during operation: True Select the boolean (true or false) input to deactivate smart logic control. Option Name Description False Enter the fixed value of false in the logic rule. True Enter the fixed value of true in the logic rule.
Page 296
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [30] SL time-out 0 Use the result of timer 0 in the logic rule. [31] SL time-out 1 Use the result of timer 1 in the logic rule. [32] SL timeout 2 Use the result of timer 2 in the logic rule.
Page 297
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [77] Digital input X30/3 [78] Digital input X30/4 [80] No flow [81] Dry pump [82] End of curve [83] Broken belt [90] ECB drive mode [91] ECB bypass mode [92] ECB test mode [93]...
Page 298
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [129] Digital input X46/9 [130] Digital input X46/11 [131] Digital input X46/13 [140] ATEX ETR cur. warning Available if parameter 1-90 Motor Thermal Protection is set to [20] ATEX ETR or [21] Advanced ETR. If alarm 164, ATEX ETR cur.lim.alarm is active, the output is 1.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Option Name Description [0]* Do not reset SLC Retain programmed settings in parameter group 13-** Smart Logic Reset SLC Reset all parameters in parameter group 13-** Smart Logic 13-1* Comparators...
Page 300
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Motor power Motor voltage DC-link voltage Motor thermal The value is in %. [10] Drive thermal The value is in %. [11] Heat sink temp. The value is in %. [12] Analog input AI53 The value is in %.
Page 301
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [26] Flow totalized volume [27] Flow actual volume [28] Flow [29] Number of pump running [30] Counter A [31] Counter B [34] Analog input X48/2 [35] Temp input X48/4 [36] Temp input X48/7 [37]...
Page 302
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [61] Below reference, low The motor runs at a reference which is less than the value in parameter 4-54 Warning Reference Low. [62] Above ref, high The motor runs at a reference which exceeds the value in parameter 4-55 Warning Reference High.
Page 303
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [100] Comparator 0 The result of comparator 0. [101] Comparator 1 The result of comparator 1. [102] Comparator 2 The result of comparator 2. [103] Comparator 3 The result of comparator 3.
Page 304
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [133] Digital input DI29 Digital input 29 (high=true) [134] Digital input DI32 Digital input 32 (high=true). [135] Digital input DI33 Digital input 33 (high=true). [136] RS flipflop 0 [137] RS flipflop 1 [138]...
Page 305
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [182] Start command Active when there is an active start command and no stop command. [183] Drive stopped A stop command (jog, stop, qstop, coast) is issued – and not from the SLC itself.
Page 306
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [248] Actual vol in trillions [249] Therm. sensor temp. 13-11 Comparator Operator Default value: Parameter type: – Option, Array [10] Setup: 2 setups Conversion index: – Data type: Change during operation: Uint8 True...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: 2 setups Conversion index: Data type: Int32 Change during operation: True Enter the trigger level for the variable that is monitored by this comparator. This is an array parameter containing comparator values 0–9. 13-1* RS Flip Flops 5.14.4 The reset/set flip flops hold the signal until set/reset.
Page 309
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [10] Out of speed range [11] Below speed low See parameter group 5-3* Digital Outputs for further description. [12] Above speed high See parameter group 5-3* Digital Outputs for further description. [13] Out of feedb.
Page 310
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [41] Reset trip This event is true if the drive is tripped (but not trip locked) and [Reset] is pressed. [42] Auto-reset trip This event is true if the drive is tripped (but not trip locked) and an automatic reset is issued.
Page 311
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [96] RS flipflop 2 See parameter group 13-1* Comparators. [97] RS flipflop 3 See parameter group 13-1* Comparators. [98] RS flipflop 4 See parameter group 13-1* Comparators. [99] RS flipflop 5 See parameter group 13-1* Comparators.
Page 312
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [228] Comparator 6 Use the result of comparator 6 in the logic rule. [229] Comparator 7 Use the result of comparator 7 in the logic rule. [230] Comparator 8 Use the result of comparator 8 in the logic rule.
Page 313
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Out of current range See parameter group 5-3* Digital Outputs for further description. Below I See parameter group 5-3* Digital Outputs for further description. Above I See parameter group 5-3* Digital Outputs for further description. high [10] Out of speed range...
Page 314
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [39] Start command This event is true if the drive is started (either via digital input, fieldbus, or other). [40] Drive stopped This event is true if the drive is stopped or coasted (either via digital input, fieldbus, or other).
Page 315
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [93] Emergency mode [94] RS flipflop 0 See parameter group 13-1* Comparators. [95] RS flipflop 1 See parameter group 13-1* Comparators. [96] RS flipflop 2 See parameter group 13-1* Comparators. [97] RS flipflop 3 See parameter group 13-1* Comparators.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [142] ATEX ETR freq. warning Available if parameter 1-90 Motor Thermal Protection is set to [20] ATEX ETR or [21] Advanced ETR. If alarm 163, ATEX ETR cur.lim.warning is active, the output is 1.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter the value to define the duration of the false output from the programmed timer. A timer is only false if it is started by an action (that is [29] Start timer 1) and until the given timer value has elapsed. 13-4* Logic Rules 5.14.6 Combine up to 3 boolean inputs (true/false inputs) from timers, comparators, digital inputs, status bits, and events using the logical...
Page 318
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [10] Out of speed range [11] Below speed low [12] Above speed high [13] Out of feedb. range [14] Below feedb. low [15] Above feedb. high [16] Thermal warning [17] Mains out of range...
Page 319
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [43] OK key [OK] is pressed. Only available on the graphical LCP. [44] Reset key [Reset] is pressed. Only available on the graphical LCP. [45] Left key [◄] is pressed.
Page 320
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [100] RS Flipflop 6 See parameter group 13-1* Comparators. [101] RS Flipflop 7 See parameter group 13-1* Comparators. [102] Verifying flow [103] Relay 1 [104] Relay 2 [105] Relay 3 [106]...
Page 322
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description NOT AND NOT Evaluates the expression NOT [13-40] AND NOT [13-42]. NOT OR NOT Evaluates the expression NOT [13-40] OR NOT [13-42]. 13-42 Logic Rule Boolean 2 Default value: Parameter type: –...
Page 324
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [73] SL time-out 6 [74] SL time-out 7 [75] Start command given [76] Digital input X30/2 [77] Digital input X30/3 [78] Digital input X30/4 [80] No flow [81] Dry pump [82]...
Page 325
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [125] Digital input X46/1 [126] Digital input X46/3 [127] Digital input X46/5 [128] Digital input X46/7 [129] Digital input X46/9 [130] Digital input X46/11 [131] Digital input X46/13 [140] ATEX ETR cur.
Page 326
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [244] SL digital output E [245] SL digital output F 13-43 Logic Rule Operator 2 Default value: Parameter type: – Option, Array [10] Setup: 2 setups Conversion index: –...
Page 327
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description False Select the 3rd boolean (true or false) input for the selected logic rule. See parameter 13-01 Start Event and parameter 13-02 Stop Event for more information. True Running In range...
Page 328
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [31] SL time-out 1 [32] SL time-out 2 [33] Digital input DI18 [34] Digital input DI19 [35] Digital input DI27 [36] Digital input DI29 [37] Digital input DI32 [38] Digital input DI33 [39]...
Page 329
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [82] End of curve [83] Broken belt [90] ECB drive mode [91] ECB bypass mode [92] ECB test mode [93] Emergency mode [94] RS Flipflop 0 See parameter group 13-1* Comparators. [95] RS Flipflop 1 See parameter group 13-1* Comparators.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [140] ATEX ETR cur. warning Available if parameter 1-90 Motor Thermal Protection is set to [20] ATEX ETR or [21] Advanced ETR. If alarm 164, ATEX ETR cur.lim.alarm is active, the output is 1.
Page 331
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description False Select the boolean (true or false) input for the selected logic rule. See parameter 13-02 Stop Event for more information. True Running In range On reference Torque limit Current limit Out of current range...
Page 332
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [32] SL time-out 2 [33] Digital input DI18 [34] Digital input DI19 [35] Digital input DI27 [36] Digital input DI29 [37] Digital input DI32 [38] Digital input DI33 [39] Start command [40]...
Page 333
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [83] Broken belt [90] ECB drive mode [91] ECB bypass mode [92] ECB test mode [93] Emergency mode [94] RS Flipflop 0 See parameter group 13-1* Comparators. [95] RS Flipflop 1 See parameter group 13-1* Comparators.
Page 334
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [140] ATEX ETR cur. warning Available if parameter 1-90 Motor Thermal Protection is set to [20] ATEX ETR or [21] Advanced ETR. If alarm 164, ATEX ETR cur.lim.alarm is active, the output is 1.
Page 335
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Select the action corresponding to the SLC event. Actions are executed when the corresponding event (defined in parameter 13-51 SL Controller 1 Event) is evaluated as true. The following actions are available: Option Name Description...
Page 336
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [33] Set digital out B low Any output with digital output 2 selected is low (off ) [34] Set digital out C low Any output with digital output 3 selected is low (off ) [35] Set digital out D low Any output with digital output 4 selected is low (off )
Page 339
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [73] SL time-out 6 [74] SL time-out 7 [75] Start command given [76] Digital input X30/2 [77] Digital input X30/3 [78] Digital input X30/4 [80] No flow [81] Dry pump [82]...
Page 340
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [125] Digital input X46/1 [126] Digital input X46/3 [127] Digital input X46/5 [128] Digital input X46/7 [129] Digital input X46/9 [130] Digital input X46/11 [131] Digital input X46/13 [140] ATEX ETR cur.
Page 341
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [244] SL digital output E [245] SL digital output F 13-54 SL Controller 2 Action Default value: Parameter type: – Option, Array [20] Setup: 2 setups Conversion index: –...
Page 342
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [27] Coast The drive coasts immediately. All stop commands including the coast command stop the SLC. [28] Freeze output Freezes the output frequency of the drive. [29] Start timer 0 Start timer 0, see parameter 13-20 SL Controller Timer for further description.
Page 343
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [74] Start timer 7 Starts timer 7, see parameter 13-20 SL Controller Timer for further description. [75] Start timer 8 Starts timer 8, see parameter 13-20 SL Controller Timer for further description.
Page 344
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [14] Below feedb. low [15] Above feedb. high [16] Thermal warning [17] Mains out of range [18] Reversing [19] Warning [20] Alarm (trip) [21] Alarm (trip lock) [22] Comparator 0 [23]...
Page 345
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [47] Up key [▲] is pressed. Only available on the graphical LCP. [48] Down key [▼] is pressed. Only available on the graphical LCP. [50] Comparator 4 Use the result of comparator 4.
Page 347
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [236] SL time-out 8 [237] SL time-out 9 [238] RS flipflop 8 [239] RS flipflop 9 [240] SL digital output A [241] SL digital output B [242] SL digital output C [243] SL digital output D...
Page 348
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [17] Select preset ref 7 Select preset reference 7. If the active preset reference is changed, it merges with other preset reference commands coming from either digital inputs or via fieldbus. [18] Select ramp 1 The value is in %.
Page 349
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [64] Counter B (up) [65] Counter B (down) [70] Start timer 3 Starts timer 3, see parameter 13-20 SL Controller Timer for further description. [71] Start timer 4 Starts timer 4, see parameter 13-20 SL Controller Timer for further description.
Page 350
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Current limit Out of current range Below I low Above I high [10] Out of speed range [11] Below speed low [12] Above speed high [13] Out of feedb. range [14] Below feedb.
Page 351
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [39] Start command [40] Drive stopped [41] Reset trip [42] Auto-reset trip [43] OK key [OK] is pressed. Only available on the graphical LCP. [44] Reset key [Reset] is pressed.
Page 352
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [96] RS Flipflop 2 See parameter group 13-1* Comparators. [97] RS Flipflop 3 See parameter group 13-1* Comparators. [98] RS Flipflop 4 See parameter group 13-1* Comparators. [99] RS Flipflop 5 See parameter group 13-1* Comparators.
Page 354
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Select set-up 4 Changes the active setup to setup 4. If the setup is changed, it merges with other setup commands coming from either the digital inputs or via fieldbus. [10] Select preset ref 0 Select preset reference 0.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [40] Set digital out C high Any output with digital output 3 selected is high (closed). [41] Set digital out D high Any output with digital output 4 selected is high (closed). [42] Set digital out E high Any output with digital output 5 selected is high (closed).
Page 356
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Use the following parameters to configure the drive to show a message and perform an action when a specific event occurs: Parameter 13-90 Alert Trigger – the event that triggers the user-defined action and message. Parameter 13-91 Alert Action –...
Page 357
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 40: Example of Setting up Triggers, Actions, and Readouts (continued) Name Setup 1 1391.4 Alert Action [0] Info 1391.5 Alert Action [0] Info 1391.6 Alert Action [0] Info 1391.7 Alert Action [0] Info 1391.8...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Stop & warning Jogging Jogging & warning Max speed Max speed & warn [10] Stop and trip [11] Stop and trip w manual reset [12] Trip [13] Trip w manual reset [14] Trip lock...
Page 361
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint8 Change during operation: True Select the switching pattern: 60° AVM or SFAVM. NOTICE The drive may adjust the switching pattern automatically to avoid a trip. Option Name Description 60 AVM...
Page 362
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [12] 12.0 kHz [13] 14.0 kHz [14] 16.0 kHz 14-02 Switching Pattern Shift Frequency Default value: Size related Parameter type: Range, 15 - 590 Hz Setup: Conversion index: All setups Data type: Uint16...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 14-04 Acoustic Noise Reduction Default value: [0] Off Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Option Name Description [0]* No change of the acoustic motor switching noise. Select to reduce the acoustic noise from the motor.
Page 364
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Parameter 14-10 Mains Failure is typically used where short mains interruptions (voltage dips) are present. At 100% load and a short voltage interruption, the DC voltage on the main capacitors drops quickly. For larger drives, it only takes a few milliseconds before the DC level drops to about 373 V DC, and the IGBTs cut off and lose the control of the motor.
Page 365
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description U DC SP-11*1.35 n [RPM] t [S] t [S] Figure 78: Kinetic Back-up A Normal operation B Mains failure C Kinetic backup D Mains return E Normal operation: Ramping The DC level during [4] Kinetic backup equals parameter 14-11 Mains Fault Voltage Level x 1.35.
Page 366
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description U DC 790 V U DC SP-11*1.35 t [S] n [RPM] t [S] Figure 79: Kinetic Back-up Trip A Normal operation B Mains failure C Kinetic backup D Trip Alarm Kin.
Page 367
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description If mains returns while in kinetic back-up at a speed below parameter 14-15 Kin. Back-up Trip Recovery Level, the drive ramps down to 0 RPM using the ramp and then trips. If the ramp is slower than the system ramping down on its own, the ramping is done mechanically and U is at the normal level (U...
Page 368
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description A Normal operation B Mains failure C Kinetic backup D Mains return E Kinetic backup ramping to Trip trip NOTICE For best performance of controlled ramp down and kinetic backup, set parameter 1-03 Torque Characteristics to [0] Compressor or [1] Variable torque(no automatic energy optimization should be active).
Page 369
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions DC voltage Output speed RPM Overvoltage control level Par 14-11 Time Mains Figure 85: Kinetic Backup, Short Mains Failure shows riding through as long as the energy in the system allows it. Figure 85 DC voltage Output speed RPM...
Page 370
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Operation under severe mains imbalance conditions reduces the lifetime of the motor. Conditions are considered severe if the motor is operated continuously near nominal load (for example, a pump or a fan running near full speed). Select the level of operation when mains imbalance conditions occur.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 14-17 Fast Mains Phase Loss Level Default value: 100% Parameter type: Range, 0 - 500% Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: True Set the level at which the functions Fast Mains Phase Loss Trip or Fast Mains Phase Loss Warning (see parameter 14-12 Response to Mains Imbalance) should be activated.
Page 372
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Automatic reset x 2 Automatic reset x 3 Automatic reset x 4 Automatic reset x 5 Automatic reset x 6 Automatic reset x 7 Automatic reset x 8 Automatic reset x 9 [10]* Automatic reset x 10...
Page 373
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Parameter 14-22 Operation Mode is automatically set to normal operation. Carry out a power cycle to start up in normal operation after a control card test. If the test is OK LCP readout: Control card OK.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Clear service logs NOTICE Save the log information using MCT 10 Set-up Software before clearing the service logs. Select this option and perform a power cycle to clear the log. Clear param.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 14-30 Current Lim Ctrl, Proportional Gain Default value: 100% Parameter type: Range, 5 - 500% Setup: All setups Conversion index: Data type: Uint16 Change during operation: False Enter the proportional gain value for the current limit controller. Selection of a high value makes the controller react faster. Too high a setting leads to controller instability.
Page 376
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Automatic energy optimization is only active if parameter 1-03 Torque Characteristics is set to either [2] Auto energy optim. CT or [3] Auto energy optim. VT. 14-40 VT Level Default value: Parameter type: Range, 40 - 90% Setup:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The Cos(phi) setpoint is automatically set for optimum AEO performance. This parameter should normally not be altered. However, in some situations it may be necessary to enter a new value to fine-tune. 14-44 d-axis Reference Gain Default value: 100%...
Page 378
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Disables DC-link compensation. Enables DC-link compensation. Advanced Improved compensation of DC-link ripple caused by mains frequency and phase imbalance. NOTICE Parameter 0-03 Regional Setting must be set correctly according to the actual mains grid.
Page 379
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Select the drive action if a fan fault is detected. Option Name Description Disabled [1]* Warning Trip 14-55 Output Filter Default value: [0] No filter Parameter type: Option Setup: All setups Conversion index: –...
Page 380
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Sine-Wave Filter Fixed NOTICE SINE-WAVE FILTER FIXED SETTING Ensures that the filter is operated within the safe range of switching frequencies. Use the setting only for VLT® MCC 101 Sine-wave Filters.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Set the C (capacitance) value of the output filter in uF, when using VLT® MCC 101 Sine-wave filter and VLT® MCC 201 All-mode filter. See the filter product label for the capacitance value. The value is the equivalent star-connected capacitance of the filter. When the filters are installed in parallel, enter the combined capacitance value of the paralleled filter.
Page 382
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Current % of rated Time Desired current>100% Inverter load counter 90.7 Time Warning Warning 130BA260.10 Figure 88: Output Current in Overload Condition If the motor is unable to run continuously with the demanded capacity, run it at reduced speed for a while. Select parameter 14-61 Function at Inverter Overload to automatically reduce motor speed until the output current is below 100% of the rated current (set in parameter 14-62 Inv.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 14-62 Inv. Overload Derate Current Default value: Parameter type: Range, 50 - 100% Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Enter the current level (in % of rated output current for the drive) when running with reduced motor speed after load on the drive has exceeded the allowable limit (110% for 60 s).
Page 384
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Use [0] Off with caution as it ignores all warnings and alarms for the selected source. Warning Trip Changing a fault level from default option [3] Trip Lock to [2] Trip leads to the automatic reset of the alarm.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 41: Possible Actions when Selected Alarms Appear (continued) Failure Parameter Alarm Warning Trip Trip lock Trip with delayed reset Heat sink sen- 1490.14 – – – Power card 1490.15 –...
Page 386
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 15-03 Power Up's Default value: Parameter type: Range, 0 - 2147483647 Setup: All setups Conversion index: Data type: Uint32 Change during operation: False View the number of times the drive has been powered up. 15-04 Over Temp's Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Do not reset No reset of running hours and number of starts counter is required. Reset counter To reset the running hours and numbers of starts counter to 0, select [1] Reset and press [OK] (see parameter 15-01 Running Hours and parameter 15-08 Number of starts).
Page 388
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1611] Power [hp] [1612] Motor voltage [1613] Frequency [1614] Motor current [1616] Torque [Nm] [1617] Speed [RPM] [1618] Motor thermal [1620] Motor angle [1622] Torque [%] [1624] Calibrated Stator Resistance [1626] Power filtered [kW]...
Page 389
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1675] Analog in X30/11 [1676] Analog in X30/12 [1677] Analog out X30/8 [mA] [1687] Bus readout alarm/warning [1689] Configurable alarm/warning word [1690] Alarm word [1691] Alarm word 2 [1692] Warning word [1693]...
Page 390
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 15-11 Logging Interval Default value: Size related Parameter type: Range, 0.000 - 0.000, Array [4] Setup: 2 setups Conversion index: Data type: Time diff wo DateID[4] Change during operation: True Enter the interval in ms between each sampling of the variables to be logged.
Page 392
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint8 Change during operation: True Before a trigger event, enter the percentage of all samples which should be retained in the log. See also parameter 15-12 Trigger Event and parameter 15-13 Logging Mode.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 42: Logged Channels Polling Color Name CH 1 Light gray Frequency CH 2 Dark gray Speed [RPM] CH 3 Reference [%] CH 4 Orange DC-link voltage CH 5 Yellow Motor current CH 6 Khaki...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Reading the Service Log Information 5.16.6 See the VLT® Motion Control Tool MCT 10 to read the service log information. Procedure Open the MCT 10 software. Select a drive. Select the Service Log plug-in. Click Read from drive.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Alarms that Trigger a Service Log Record 5.16.7 Table 43: Alarms Triggering a Service Log Record Alarm title Mains phase loss DC voltage high DC voltage low DC overvolt DC undervolt Inverter overld.
Page 398
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Warning word Alarm word Status word Control word Extended status word Events are logged with value and time stamp in ms. The time interval between 2 events depends on how often events occur (maximum once every scan time).
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint32 Change during operation: False View the time at which the logged event occurred. Time is measured in ms since drive start. This is an array parameter containing event times 0-49.
Page 400
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: TimeOfDay Change during operation: False Array parameter; Date & Time 0–9: This parameter shows when the logged event occurred. 15-34 Alarm Log: Setpoint Default value: Parameter type: 0 ProcessCtrlUnit Range, -999999.999 - 999999.999 ProcessCtrlUnit, Array [10]...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [131] lb/min [132] lb/h [140] ft/s [141] ft/min [145] [160] °F [170] [171] lb/in [172] in WG [173] ft WG [174] in HG [180] 15-38 Alarm Log: Speed Default value: 0 RPM Parameter type:...
Page 403
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 15-42 Voltage Default value: Parameter type: Range, 0 - 20 Setup: All setups Conversion index: Data type: VisStr[20] Change during operation: False View the voltage. The readout is identical to the drive power field of the type code definition, characters 11-12. 15-43 Software Version Default value: Parameter type:...
Page 404
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 15-48 LCP ID No Default value: Parameter type: Range, 0 - 20 Setup: All setups Conversion index: Data type: VisStr[20] Change during operation: False View the LCP ID number. 15-49 SW ID Control Card Default value: Parameter type: Range, 0 - 20...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 15-58 Smart Setup Filename Default value: Size related Parameter type: Range, 0 - 20 Setup: All setups Conversion index: Data type: VisStr[16] Change during operation: True Shows the Smart Setup file name. 15-59 Filename Default: Size related...
Page 406
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: VisStr[18] Change during operation: False View the installed option serial number. 15-64 Application Version Default value: Parameter type: Range, 0 - 30, Array [8] Setup: All setups Conversion index: Data type: Change during operation: VisStr[30]...
Page 407
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: VisStr[30] Change during operation: False View the type code string for the option installed in slot C and a translation of the type code string. For example, for type code string CXXXX, the translation is No option.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 15-87 kWh Counter Hires Default value: 0 kWh Parameter type: Range, 0 - 2147483647 kWh Setup: All setups Conversion index: Data type: Uint32 Change during operation: False Register the power consumption of the motor as an average value over 1 hour. Reset the counter in parameter 15-06 Reset kWh Counter. The decimal places are reset at power-up.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions This parameter contains data used by the VLT® Motion Control Tool MCT 10. Parameter Group 16-** Data Readouts 5.17 16-0* General Status 5.17.1 16-00 Control Word Default value: Parameter type: Range, 0 - 65535 Setup: All setups...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 16-09 Customer Readout Default value: 0 CustomReadoutUnit Parameter type: Range, -999999.99 CustomReadoutUnit - 999999.99 Setup: All setups Conversion index: Data type: Int32 Change during operation: False View the value of custom readout from parameter 0-30 Unit for Userdefined Readout to parameter 0-32 Custom Readout Max Value. 16-1* Motor Status 5.17.2 16-10 Power [kW]...
Page 411
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 16-14 Motor Current Default value: Parameter type: Range, 0 - 10000 A Setup: All setups Conversion index: Data type: Int32 Change during operation: False View the motor current measured as an average value, I .
Page 412
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 16-19 Thermistor Sensor Temperature Default value: 0 °C Parameter type: Range, 0 - 0 °C Setup: All setups Conversion index: Data type: Int16 Change during operation: False Returning the actual temperature on KTY sensor built into the motor. See parameter group 1-9* Motor Temperature. 16-20 Motor Angle Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 16-27 Power Filtered [hp] Default value: 0 hp Parameter type: Range, 0 - 10000 hp Setup: All setups Conversion index: Data type: Int32 Change during operation: False Shows the calibrated stator resistance. 16-3* Drive Status 5.17.3 16-30 DC Link Voltage...
Page 414
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions View the percentage load on the inverter. 16-36 Inv. Nom. Current Default value: Size related Parameter type: Range, 0.01 - 10000 A Setup: All setups Conversion index: Data type: Uint32 Change during operation: False View the inverter nominal current, which must match the nameplate data on the connected motor.
Page 415
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 16-42 Service Log Counter Default value: Parameter type: Range, 0 - 24 Setup: All setups Conversion index: Data type: Uint8 Change during operation: True Shows the number of service logs stored in the ServiceLog file. If the ServiceLog file is full, clear the logged data by selecting option [5] Clear service logs in parameter 14-22 Operation Mode.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Int32 Change during operation: False This parameter specifies the reference given to the drive after the speed ramp. 16-49 Current Fault Source Default value: Parameter type: Range, 0 - 8 Setup: All setups Conversion index:...
Page 417
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 16-54 Feedback 1 [Unit] Default value: 0 ProcessCtrlUnit Parameter type: Range, -999999.999 ProcessCtrlUnit - 999999.999 ProcessCtrlUnit Setup: Conversion index: Data type: Int32 Change during operation: False View the value of feedback 1, see parameter group 20-0* Feedback. The value is limited by the settings in parameter 20-13 Minimum Reference/Feedb.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions This parameter shows the actual operating setpoint after it has been modified by flow compensation. 16-6* Inputs and Outputs 5.17.5 16-60 Digital Input Default value: Parameter type: Range, 0 - 65535 Setup: All setup Conversion index:...
Page 419
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 0 0 0 0 0 Figure 91: Relay Settings 16-61 Terminal 53 Switch Setting Default value: [0] Current Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: False View the setting of input terminal 53.
Page 420
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 16-63 Terminal 54 Switch Setting Default value: [0] Current Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: False View the setting of terminal 54. Option Name Description...
Page 421
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Int32 Change during operation: False View the actual value of the frequency applied at terminal 33 as an impulse input. 16-69 Pulse Output #27 [Hz] Default value: Parameter type: Range, 0 - 40000...
Page 422
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions View the present value of counter A. Counters are useful as comparator operands, see parameter 13-10 Comparator Operand. Reset or change the value either via digital inputs (parameter group 5-1* Digital Inputs) or by using an SLC action (parameter 13-52 SL Controller Action).
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Int16 Change during operation: False Shows the actual output value at terminal X45/3. The value shown reflects the selection in parameter 6-80 Terminal X45/3 Output. 16-8* Fieldbus &...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions View the 2-byte status word (STW) sent to the fieldbus master. Interpretation of the status word depends on the fieldbus option installed and the control word profile selected in parameter 8-10 Control Word Profile. 16-87 Bus Readout Alarm/Warning Default value: Parameter type:...
Page 425
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 16-93 Warning Word 2 Default value: Parameter type: Range, 0 - 4294967295 Setup: All setups Conversion index: Data type: Uint32 Change during operation: False Show the warning word sent via the serial communication port in hex code. 16-94 Ext.
Page 426
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Bit 16: Maintenance text 3 Bit 17: Maintenance text 4 The following table details the display of the maintenance word. Table 45: Maintenance Word Position 4⇒ Valve Fan bearings Pump bearings Motor bearings Position 3⇒...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 16-97 Alarm Word 3 Default value: Parameter type: Range, 0 - 4294967295 Setup: All setups Conversion index: Data type: Uint32 Change during operation: False Shows the alarm word sent via the serial communication port in hex code. 16-98 Warning Word 3 Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 18-02 Maintenance Log: Time Default value: Parameter type: Range, 0 - 2147483647 s, Array [10] Setup: Conversion index: All setups Data type: Uint32 Change during operation: False Shows when the logged event occurred. Time is measured in s since last power-up. 18-03 Maintenance Log: Date and Time Default value: Size related...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 18-11 Emergency Mode Log: Time Default value: Parameter type: Range, 0 - 2147483647 s, Array [10] Setup: Conversion index: All setups Data type: Uint32 Change during operation: False This parameter shows at which time the logged event occurred. Time is measured in seconds since the drive was started. 18-12 Emergency Mode Log: Date and Time Default value: Size related...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 18-16 Operating Hours Default value: Parameter type: Range, 0 - 2147483647, Array [10] Setup: Conversion index: All setups Data type: Uint32 Change during operation: False Shows operating hours of the drive at the instance when the parameter was changed. 18-17 Running Hours Default value: Parameter type:...
Page 431
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Int32 Change during operation: False Readout of the value of the signal applied to terminal X42/3 on the analog I/O card. The units of the value shown in the LCP correspond to the mode selected in parameter 26-01 Terminal X42/3 Mode.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions View the actual current measured at input X48/2. 18-37 Temp. Input X48/4 Default value: Parameter type: Range, -500 - 500 Setup: All setups Conversion index: Data type: Int16 Change during operation: True View the actual temperature measured at input X48/4.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 18-42 Analog Input X49/5 Default value: Parameter type: Range, -20 - 20 Setup: All setups Conversion index: Data type: Int32 Change during operation: False View the actual value at input X49/5 either as a voltage, current, or a temperature value. 18-43 Analog Input X49/7 Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True This parameter shows the last warning. 18-48 Last Warning Count Default value: Parameter type: Range, 0 - 65535 Setup: All setups Conversion index: Data type: Change during operation: Uint16...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Shows the signal states from the active digital inputs. 0 = No signal 1 = Connected signal 18-7* Rectifier Status 5.18.9 18-70 Mains Voltage Default value: Parameter type: Range, 0 - 1000 V, Array [4] Setup: All setups Conversion index:...
Page 436
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The indices are as follows: 0 = inrush1 1 = inrush2 2 = inrush3 3 = inrush4 18-75 Rectifier DC Volt Default value: Parameter type: Range, 0 - 10000 V Setup: Conversion index: All setups...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions View the maximum measured imbalance for the 3 mains line-to-line measurements. The indices are as follows: 0 = inrush1 1 = inrush2 18-79 Rectifier DC Volt. 2 Default value: Parameter type: Range, 0 - 1000 V, Array [4] Setup: All setups...
Page 438
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setpoint to Reference Handling Setpoint 1 P 20-21 Setpoint 2 P 20-22 Multi setpoint min. Setpoint 3 Multi setpoint max. P 20-23 Feedback Feedback 1 only Feedback 1 Feedback conv. Feedback 1 Source Feedback 2 only P 20-01...
Page 439
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [10] Analog input X42/3 [11] Analog input X42/5 [15] Analog input X48/2 [16] Analog input X49/1 [17] Analog input X49/3 [18] Analog input X49/5 [99] Normal feedback [100] Bus feedback 1 [101]...
Page 440
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE This parameter is only available when using pressure to temperature feedback conversion. If option [0] Linear is selected in parameter 20-01 Feedback 1 Conversion, the setting of any option in parameter 20-02 Feedback 1 Source Unit does not matter as a conversion is 1-to-1.
Page 442
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Up to 3 different feedback signals can be used to provide the feedback signal for the PID controller of the drive. This parameter defines which input is used as the source of the 2nd feedback signal. Analog input X30/11 and analog input X30/12 refer to inputs on VLT® General Purpose I/O MCB 101.
Page 443
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Linear Linear has no effect on the feedback. Square root Commonly used when a pressure sensor is used to provide flow feedback. 20-05 Feedback 2 Source Unit Default value: –...
Page 444
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [40] [41] m/min [45] [60] °C [70] mbar [71] [72] [73] [74] m WG [75] mm Hg [80] [120] [121] gal/s [122] gal/min [123] gal/h [124] [125] [126] /min [127]...
Page 445
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 20-06 Feedback 3 Source Default value: [2] Analog input 54 Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True NOTICE If feedback is not used, set its source to [0] No function. Parameter 20-20 Feedback Function determines how the PID controller uses the 3 possible feedback.
Page 446
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [201] Ext. closed loop 2 [202] Ext. closed loop 3 20-07 Feedback 3 Conversion Default value: Parameter type: [0] Linear Option Setup: All setups Conversion index: – Data type: Change during operation: Uint8...
Page 447
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [21] l/min [22] [23] [24] /min [25] [30] kg/s [31] kg/min [32] kg/h [33] t/min [34] [40] [41] m/min [45] [60] °C [70] mbar [71] [72] [73] [74] m WG [75]...
Page 448
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [140] ft/s [141] ft/min [145] [160] °F [170] [171] lb/in [172] in WG [173] ft WG [174] in HG [180] 20-12 Reference/Feedback Unit Default value: – Parameter type: Option Setup: All setups...
Page 449
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [33] t/min [34] [40] [41] m/min [45] [60] °C [70] mbar [71] [72] [73] [74] m WG [75] mm Hg [80] [120] [121] gal/s [122] gal/min [123] gal/h [124] [125]...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [174] in HG [180] 5.19.3 20-2* Feedback/Setpoint This parameter group is used to determine how the PID controller uses the 3 possible feedback signals to control the output frequency of the drive.
Page 451
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Average Sets up the PID controller to use the average of feedback 1, feedback 2, and feedback 3 as the feedback. NOTICE Set any unused feedback to [0] No function in: Parameter 20-00 Feedback 1 Source Parameter 20-02 Feedback 2 Source Parameter 20-06 Feedback 3 Source...
Page 452
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Multi setpoint min Sets up the PID controller to calculate the difference between feedback 1 and setpoint 1, feedback 2 and setpoint 2, and feedback 3 and setpoint 3. It uses the feedback/setpoint pair in which the feedback is the farthest below its corresponding setpoint reference.
Page 453
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Example 1 - Multi-zone, single setpoint In an office building, a VAV (variable air volume) VLT® HVAC Drive system must ensure a minimum pressure at selected VAV boxes. Due to the varying pressure losses in each duct, the pressure at each VAV box cannot be assumed to be the same. The minimum pressure required is the same for all VAV boxes.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 20-22 Setpoint 2 Default value: 0 ProcessCtrlUnit Parameter type: Range, -999999.999 - 999999.999 ProcessCtrlUnit Setup: Conversion index: All setups Data type: Int32 Change during operation: True NOTICE The setpoint entered in this parameter is added to any other references that are enabled. Setpoint 2 is used in closed-loop mode to enter a setpoint reference that is used by the PID controller of the drive.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 20-53 Time Constant Estimate Default value: 1.000 s Parameter type: Range, 0.000 - 100.000 s Setup: All setups Conversion index: Data type: Uint32 Change during operation: True Use this parameter for estimating the system time constant. 20-54 Deadtime Estimate Default value: 10.000 s...
Page 456
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint8 Change during operation: True Select the unit to be used with parameter 18-50 Sensorless Readout [Unit]. Option Name Description [20] [23] [24] /min [25] [71] [73] [74] m WG [75] mm Hg...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 20-7* Autotuning 5.19.6 PID autotuning The closed-loop controller of the drive (parameter group 20-** FC Closed Loop) can be autotuned, which simplifies and saves time during commissioning, while ensuring accurate control adjustment. To use autotuning, configure the drive for closed loop in parameter 1-00 Configuration Mode.
Page 458
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions DCR assumes that the target applications of the drive can be generically modeled as 1st order plus dead-time systems. DRC autotuning is providing the feedback for calculation. τ = time constant of process system K (process system gain).
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions This parameter sets the magnitude of step change during auto tuning. The value is a percentage of full speed. That is, if maximum output frequency in parameter 4-13 Motor Speed High Limit [RPM]/parameter 4-14 Motor Speed High Limit [Hz] is set to 40 Hz, 0.10 is 10% of 50 Hz, which is 5 Hz.
Page 460
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 20-81 PID Normal/Inverse Control Default value: [0] Normal Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Option Name Description [0]* Normal The output frequency of the drive decreases when the feedback is greater than the setpoint reference.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint8 Change during operation: True When the difference between the feedback and the setpoint reference is less than the value of this parameter, the display of the drive shows Run on reference.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Calculate the proportional band (error causing output to change from 0–100%) with this formula: 20-94 PID Integral Time Default value: Parameter type: Range, 0.01 - 10000 s Setup: Conversion index: All setups Data type: Uint32...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The extended closed-loop PID controllers may be interconnected or connected to the PID closed-loop controller to form a dual-loop configuration. To control a modulating device, for example a valve motor, this device must be a positioning servo motor with built-in electronics accepting either a 0–10 V (signal from VLT®...
Page 464
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 21-00 Closed Loop Type Default value: [0] Auto Parameter type: Option Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: True This parameter defines the application response. The default mode should be sufficient for most applications. If the relative application speed is known, it can be selected here.
Page 465
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Int32 Change during operation: True Enter the minimum allowable feedback level in user units as defined: Parameter 21-10 Ext. 1 Ref./Feedback Unit for EXT CL 1. Parameter 21-30 Ext. 2 Ref./Feedback Unit for EXT CL 2. Parameter 21-50 Ext.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 21-1* Closed Loop Ref/Feedback 5.20.3 Drive External reference P 21-13 Ext. Output signal closed-loop Setpoint controller P 6-50 P 21-15 Feedback P 21-14 Output MCB 101 signal P 6-60 21-10 Ext. 1 Ref./Feedback Unit Default value: Parameter type: Option...
Page 467
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [30] kg/s [31] kg/min [32] kg/h [33] t/min [34] [40] [41] m/min [45] [60] °C [70] mbar [71] [72] [73] [74] m WG [75] mm Hg [80] [120] [121] gal/s...
Page 468
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [171] lb/in [172] in WG [173] ft WG [174] in HG [180] 21-11 Ext. 1 Minimum Reference Default value: Parameter type: 0 ExtPID1Unit Range, -999999.999 - par. 21-12 Ext.PID1Unit Setup: All setups...
Page 469
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* No function Use this selection if feedback is not used. Analog input 53 Analog input 54 Analog input X30/11 Analog input X30/12 [11] Local bus reference [20] Digital pot.
Page 470
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Analog input 54 Pulse input 29 Pulse input 33 Analog input X30/11 Analog input X30/12 Analog input X42/1 [10] Analog input X42/3 [11] Analog input X42/5 [15] Analog input X48/2 [16] Analog input X49/1...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Int32 Change during operation: True Readout of the reference value for the closed-loop 1 controller. 21-18 Ext. 1 Feedback [Unit] Default value: 0 ExtPID1Unit Parameter type: Range, -999999.999 - 999999.999 Ext.PID1Unit...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 21-22 Ext. 1 Integral Time Default value: Parameter type: 20 s 0.01 - 10000=Off s Setup: All setups Conversion index: Data type: Change during operation: Uint32 True Over time, the integrator accumulates a contribution to the output from the PID controller as long as there is a deviation between the reference/setpoint and feedback signals.
Page 473
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint8 Change during operation: True Select the unit for the reference and feedback. Option Name Description [0]* None [10] 1/min [11] [12] Pulse/s [20] [21] l/min [22] [23] [24] /min [25]...
Page 474
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [121] gal/s [122] gal/min [123] gal/h [124] [125] [126] /min [127] [130] lb/s [131] lb/min [132] lb/h [140] ft/s [141] ft/min [145] [160] °F [170] [171] lb/in [172] in WG [173]...
Page 475
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE Set the value for parameter 21-32 Ext. 2 Maximum Reference before setting the values for the PID controller in parameter group 20-9* PID Controller. Select the maximum reference for the closed-loop 1 controller. The dynamics of the PID controller depend on the value set in this parameter.
Page 476
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [37] Analog input X49/1 [38] Analog input X49/3 [39] Analog input X49/5 [133] Fieldbus REF 1 21-34 Ext. 2 Feedback Source Default value: Parameter type: [0] No function Option Setup: All setups...
Page 477
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [105] Sensorless pressure Requires setup by VLT® Motion Control Tool MCT 10 with sensorless plug-in. [200] Ext. closed loop 1 [201] Ext. closed loop 2 [202] Ext. closed loop 3 21-35 Ext.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Set a limit for the differentiator gain (DG). The DG increases if there are fast changes. Limit the DG to obtain a pure differentiator gain when changes are slow and a constant differentiator gain when quick changes occur.
Page 480
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [33] t/min [34] [40] [41] m/min [45] [60] °C [70] mbar [71] [72] [73] [74] m WG [75] mm Hg [80] [120] [121] gal/s [122] gal/min [123] gal/h [124] [125]...
Page 481
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [174] in HG [180] 21-51 Ext. 3 Minimum Reference Default value: Parameter type: 0 ExtPID3Unit Range, -999999.999 - par. 21-52 Ext.PID3Unit Setup: All setups Conversion index: Data type: Int32 Change during operation: True...
Page 482
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Analog input X30/11 Analog input X30/12 [11] Local bus reference [20] Digital pot. meter [21] Analog input X30/11 [22] Analog input X30/12 [23] Analog input X42/1 [24] Analog input X42/3 [25] Analog input X42/5...
Page 483
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Analog input X30/11 Analog input X30/12 Analog input X42/1 [10] Analog input X42/3 [11] Analog input X42/5 [15] Analog input X48/2 [16] Analog input X49/1 [17] Analog input X49/3 [18] Analog input X49/5 [99]...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 21-58 Ext. 3 Feedback [Unit] Default value: 0 ExtPID3Unit Parameter type: Range, -999999.999 - 999999.999 Ext.PID3Unit Setup: Conversion index: All setups Data type: Int32 Change during operation: True Readout of the feedback value for the closed-loop 3 controller. 21-59 Ext.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions however, may cause the control to become unstable. The value set is the time needed for the integrator to add the same contribution as the proportional for a certain deviation. If the value is set to 10000, the controller acts as a pure proportional controller with a P- band based on the value set in parameter 20-93 PID Proportional Gain.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Set the time constant for the filtered power readout. A higher value will give a more steady readout but a slower system response to changes. 22-2* No-flow Detection 5.21.2 Sleep mode External sleep mode command...
Page 487
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Figure 95: No-flow Detection Scheme Head Flow Figure 96: No-flow Detection Graph No-flow detection is based on the measurement of speed and power. For a certain speed, the drive calculates the power at no flow. The coherence is based on the adjustment of 2 sets of speed and associated power at no flow.
Page 488
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions is programmed in parameter group 22-3* No-flow Power Tuning. It is also possible to run a parameter 22-20 Low Power Auto Set-up, automatically stepping through the commissioning process, and also automatically storing the data measured. Set the drive for open loop in parameter 1-00 Configuration Mode when carrying out the auto setup (see parameter group 22-3* No-flow Power Tuning).
Page 489
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0*] Enabled NOTICE Do the auto setup when the system has reached normal operating temperature. NOTICE It is important that parameter 4-13 Motor Speed High Limit [RPM] or parameter 4-14 Motor Speed High Limit [Hz] is set to the maximum operational speed of the motor.
Page 490
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Disabled Enabled To set the parameters in parameter group 22-3* No-flow Power Tuning for proper operation, carry out the low-power detection commissioning. 22-22 Low Speed Detection Default value: [0] Disabled Parameter type:...
Page 491
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Enabled for multiple drives For applications with multiple drives. Enable low-speed detection with the following features: • Minimum run time • Minimum sleet time • Boost Enabled multidrive boost For applications with multiple drives.
Page 492
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0*] NOTICE Do not set parameter 14-20 Reset Mode to [13] Infinite auto reset when parameter 22-23 No-flow Function is set to [3] Alarm . Doing so causes the drive to continuously cycle between running and stopping when a no-flow condition is detected.
Page 493
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Commission low-power detection using either parameter group 22-3* No-flow Power Tuning or parameter 22-20 Low Power Auto Set- NOTICE Do not set parameter 14-20 Reset Mode to [13] Infinite auto reset when parameter 22-26 Dry Pump Function is set to [2] Trip. Doing so causes the drive to continuously cycle between running and stopping when a dry-pump condition is detected.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True Set the no-flow speed reference in Hz. 5.21.3 22-4* Sleep Mode If the load on the system allows for stop of the motor and the load is monitored, the motor can be stopped by activating the sleep-mode function.
Page 495
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Figure 97: Sleep-mode Function Systems where the integrated PI controller is used for controlling pressure or temperature, for example, boost systems with a pressure feedback signal applied to the drive from a pressure transducer. Set parameter 1-00 Configuration Mode to [3] Closed Loop and configure the PI controller configured for desired reference and feedback signals.
Page 496
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions If no-flow is detected, the drive increases the setpoint for pressure to ensure a slight overpressure in the system (boost set in parameter 22-45 Setpoint Boost). The feedback from the pressure transducer is monitored, and then this pressure has dropped with a set percentage below the normal setpoint for pressure (P ).
Page 497
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions When low power or low speed is detected, the motor is stopped, but the reference signal (f ) from the external controller is still monitored. Because of the the low pressure created, the controller increases the reference signal to gain pressure. When the reference signal has reached a set value, f , the motor restarts.
Page 498
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions To be used if parameter 0-02 Motor Speed Unit has been set to [0] RPM (parameter not visible if [1] Hz is selected). Only to be used if parameter 1-00 Configuration Mode is set to [0] Open loop and an external controller applies speed reference. Set the reference speed at which the sleep mode should be canceled.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 22-5* End of Curve 5.21.4 The end-of-curve conditions occur when a pump is yielding a too large volume to ensure the set pressure. This situation can occur if a leakage occurs in the distribution pipe system after the pump. Such a leakage causes the pump to operate at the end of the pump characteristic valid for the maximum speed set in parameter 4-13 Motor Speed High Limit [RPM] or parameter 4-14 Motor Speed High Limit [Hz].
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Man. reset trip The drive stops running and activates an end-of-curve alarm (alarm 94, End of Curve). A drive digital output or a fieldbus can communicate an alarm to other equipment. Stop and Trip 22-51 End of Curve Delay Default value:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* End-of-curve monitoring is not active. Warning The drive continues to run, but activates a broken-belt warning (warning 95, Broken Belt). A drive digital output or a fieldbus can communicate a warning to other equipment.
Page 502
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0*] Disabled The timer set in parameter 22-76 Interval between Starts is disabled. Enabled The timer set in parameter 22-76 Interval between Starts is enabled. 22-76 Interval between Starts Default value: Setting in par.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Int32 Change during operation: True Set the feedback value at which the minimum-run-time timer must be overridden. When the feedback drops below this value, the motor is destaged even if the minimum-run-time timer has not expired.
Page 504
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 47: Setpoint Defined by Number of Pumps Parameter used Speed at design point Speed at design point Cascade controller KNOWN UNKNOWN Parameter 22-80 Flow Compensation – Parameter 22-81 Square-linear Curve Approximation –...
Page 505
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE This parameter is invisible in casacde mode. Example 1: Adjustment of this parameter allows the shape of the control curve to be adjusted. 0% = Linear 100% = Ideal shape (theoretical) (head) Control curve (flow)
Page 506
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions From the datasheet showing characteristics for the specific equipment at different speeds, reading across from the H point and DESIGN the Q point allows finding point A, which is the system design working point. The pump characteristics at this point should be DESIGN identified and the associated speed programmed.
Page 507
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Resolution 1 RPM. Enter the speed of the motor in RPM at which flow is 0, and minimum pressure, H , is achieved. Alternatively, enter the speed in Hz in parameter 22-84 Speed at No-Flow [Hz]. If parameter 0-02 Motor Speed Unit is set to RPM, parameter 22-85 Speed at Design Point [RPM] should also be used.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Int32 Change during operation: True Enter the value corresponding to the pressure at rated speed in reference/feedback units. This value can be defined using the pump datasheet. 22-89 Flow at Design Point Default value: Parameter type: Range, 0 - 999999.999...
Page 509
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE The PC-based configuration tool VLT® Motion Control Tool MCT 10 comprises a special guide for easy programming of timed actions. 23-00 ON Time Default value: Parameter type: Size related Range, 0 - 0, Array [10] Setup: 2 setups...
Page 513
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [43] Set digital out F high [60] Reset counter A [61] Reset counter B [62] Counter A (up) [63] Counter A (down) [64] Counter B (up) [65] Counter B (down) [70] Start timer 3...
Page 514
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* All days Working days Non-working days Monday Tuesday Wednesday Thursday Friday Saturday Sunday [10] Day 1 of month [11] Day 2 of month [12] Day 3 of month [13] Day 4 of month [14]...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [33] Day 24 of month [34] Day 25 of month [35] Day 26 of month [36] Day 27 of month [37] Day 28 of month [38] Day 29 of month [39] Day 30 of month [40]...
Page 516
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Untitled - MCT 10 SET - up Software File Edit View Insert Communication Tools Options Help Network Name Setup 1 Setup 2 Setup 3 Setup 4 Project 2310.0 Maintenance Item Motor bearings Motor bearings Motor bearings...
Page 517
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Valve Pressure transmitter Flow transmitter Temperature transm. Pump seals Fan belt [10] Filter [11] Drive cooling fan [12] System health check [13] Warranty [20] Maintenance text 0 [21] Maintenance text 1 [22]...
Page 518
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [21] Maintenance text 1 [22] Maintenance text 2 [23] Maintenance text 3 [24] Maintenance text 4 [25] Maintenance text 5 [28] Clear logs 23-12 Maintenance Base Default value: Parameter type: [0] Disabled Option, Array [20]...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Set the date and time for the next maintenance occurrence if the preventive maintenance event is based on date/time. Date format depends on the setting in parameter 0-71 Date Format while the time format depends on the setting in parameter 0-72 Time Format. ...
Page 520
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions For each of the above 2 functions, the data is stored in several counters allowing for selection time frame and a split on hours, days, or weeks. The period/split (resolution) can be set in parameter 23-50 Energy Log Resolution. The data is based on the value registered by the kWh counter in the drive.
Page 521
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions until 1 day/week/month has passed. The counters contain data for 1 day, 1 week, or 5 weeks back in time and up to the actual time. The logging starts at the date programmed in parameter 23-51 Period Start. In all cases, the period split refers to operating hours (time where the drive is powered up).
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Energy meter 23-5* 23-53 Energy meter (06) Energy meter 23-5* 23-53 Energy meter (05) 23-5* Energy meter 23-53 Energy meter (04) Energy meter 23-5* 23-53 Energy meter (03) 23-5* Energy meter 23-53 Energy meter (02) 23-5*...
Page 523
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The relative value for the operating variable is determined as: Actual/rated x 100% - for power and current. Actual/max x 100% - for output frequency and motor speed. The size of each interval can be adjusted individually, but is 10% for each as default. Power and current can exceed rated value, but those registrations are included in 90–100% (MAX) counter.
Page 524
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [2]* Frequency [Hz] Output frequency to the motor. Reference for the relative value is the maximum output frequency programmed in parameter 4-14 Motor Speed High Limit [Hz]. The actual value can be read in parameter 16-13 Frequency.
Page 525
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Counter [6]: 60–<70% Counter [7]: 70–<80% Counter [8]: 80–<90% Counter [9]: 90–100% or maximum Starts to count at the date/time programmed in parameter 23-63 Timed Period Start, and stops at the date/time programmed in parameter 23-64 Timed Period Stop.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 23-66 Reset Continuous Bin Data Default value: [0] Do not reset Parameter type: Option Setup: All setups Conversion index: – Data type: Uin8 Change during operation: True Select [1] Do reset to reset all values in the energy log counters shown in parameter 23-61 Continuous Bin Data. After pressing [OK], the setting of the parameter value automatically changes to [0] Do not reset.
Page 527
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions As value for the fixed speed case, the rated motor size (kW) is multiplied with a factor (set in %) representing the power produced at fixed speed. The difference between this reference power and the actual power is accumulated and stored. The difference in energy can be read in parameter 23-83 Energy Savings.
Page 528
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Set the value of the investment spent on upgrading the plant with speed control. Use the same currency as in parameter 23-81 Energy Cost. 23-83 Energy Savings Default value: 0 kWh Parameter type: Range, 0 - 0 kWh Setup:...
In no event shall Danfoss be liable to the end user or any other party for any direct or indirect, special, or consequential damage, or loss suffered by such party, which has occurred due to the drive being programmed and operated in emergency mode.
Page 530
[Alarm Log] on the LCP. The log includes up to 10 of the latest events. Warranty-affecting alarms have a higher priority than the other 2 types of events. The emergency mode alarm log can only be reset by a Danfoss authorized service partner. To secure the emergency mode operation documentation, the 1st critical alarms can never be removed.
Page 531
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 24-00 Emergency Mode Function Default value: [0] Disabled Parameter type: Option Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: True NOTICE Alarms are produced or ignored in accordance with the selection in parameter 24-09 Emergency Mode Alarm Handling. Option Name Description...
Page 532
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Open loop When emergency mode is active, the motor runs with a fixed speed based on a reference set. The unit is the same as selected in parameter 0-02 Motor Speed Unit.
Page 533
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [31] kg/min [32] kg/h [33] t/min [34] [40] [41] m/min [45] [60] °C [70] mbar [71] [72] [73] [74] m WG [75] mm HG [80] [120] [121] gal/s [122] gal/min...
Page 534
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [172] in WG [173] ft WG [174] in HG [180] 24-03 Emergency Mode Min Reference Default value: Parameter type: Size related Range, -999999.999 - par. 24-04 EmergencyModeMaxReferenc Setup: All setups Conversion index:...
Page 535
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint8 Change during operation: True Select the external reference input to be used for emergency mode. In open-loop mode, this signal value is added to the preset values in parameter 24-05 Emergency Mode Preset Reference.
Page 536
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Pulse input 29 Pulse input 33 Analog input X30/11 Analog input X30/12 Analog input X42/1 [10] Analog input X42/3 [11] Analog input X42/5 [16] Analog input X49/1 [17] Analog input X49/3 [18]...
Page 537
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Trip+reset, critical alarms Alarms are ignored even though damage may be caused, except for the critical alarms mentioned in the following table. When these alarms occur, the drive trips immediately, followed by an automatic reset and restarts even if the operation leads to an infinite loop of trip and restart.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 50: Emergency Mode Alarm Handling (continued) Alarm number Description Emergency mode alarm handling selected in parameter 24-09 Warranty- Emergency Mode Alarm Handling. Critical alarms cause a trip. affecting alarms in emergency mode Illegal PS config Ignore...
Page 539
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Alarm Auto Resets Auto Reset Disabled Speed Operation Alarm Bypass Delay Timer P24-11 Relay "Bypass" On delay (P5-41) Figure 111: Drive Bypass The status can be read in the extended status word 2, bit number 24. 24-10 Drive Bypass Function Default value: [0] Disabled...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: 2 setups Conversion index: Data type: Uint16 Change during operation: True Programmable in 1 s increments. Once the bypass function is activated in accordance with the setting in parameter 24-10 Drive Bypass Function, the bypass delay timer begins to operate.
Page 541
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Speed Ramp (X) S-Ramp Ramp (X) S-Ramp Ratio at Dec.End Ratio at Accel.End Ramp (X) Linear Ramp (X) S-Ramp S-Ramp Ratio at Jerk compensated Ratio at Dec.End Accel.End Ramp (X) Ramp (X) Up Time Down Time...
Page 542
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions A digital impulse triggers the emergency mode operation with stop on all alarms as option [2] Trip, all alarms/test in parameter 24-09 Emergency Mode Alarms Handling. This test impulse signal can only activate 1 test time period and the normal emergency mode operation takes over as soon as the test time ends, or it stops the test period if the emergency mode signal disappears.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Parameter Group 25-** Cascade Controller 5.24 Introduction to Cascade Controller Parameters 5.24.1 Parameters for configuring the basic cascade controller for sequence control of multiple pumps. For a more application-oriented description and wiring examples, see the section Application Examples, Cascade Controllerin the design guide. For more information on using the advanced cascade controller options, refer to Parameter Group 27-** Cascade CTL Option.
Page 544
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 25-00 Cascade Controller Default value: – Parameter type: Option Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: False For operation of multiple devices (pump/fan) systems where capacity is adapted to actual load with speed control combined with on/off control of the devices.
Page 545
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions To provide equal hours of operation with fixed-speed pumps, the pump used can be cycled. The selection of pump cycling is either first in-last out or equal running hours for each pump. Option Name Description...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 25-2* Bandwidth Settings 5.24.3 Parameters for setting the bandwidth within which the pressure is allowed to operate before staging/destaging fixed speed pumps. These parameters also include various timers to stabilize the control. 25-20 Staging Bandwidth Default value: Size related...
Page 547
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Override bandwidth Setpoint Figure 116: Override Bandwidth Setting the OBW too close to the SBW could defeat the purpose with frequent staging at momentary pressure changes. Setting the OBW too high might lead to unacceptably high or low pressure in the system while the SBW timers are running. The value can be optimized with increased familiarity with the system.
Page 548
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Immediate staging of a fixed-speed pump is not desirable when a momentary pressure drop in the system exceeds the staging bandwidth (SBW). Staging is delayed by the length of the time programmed. If the pressure increases within the SBW before the timer has elapsed, the timer is reset.
Page 549
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions (27-24) SBW destage delay (27-20) Setpoint (27-20) Figure 118: SBW Destaging Delay 25-25 OBW Time Default value: 10 s Parameter type: Range, 0 - 300 s Setup: Conversion index: All setups Data type: Uint16 Change during operation:...
Page 550
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 25-26 Destage at No-Flow Default value: [0] Disabled Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True This parameter ensures that when a no-flow situation occurs, the fixed-speed pumps are destaged 1 by 1 until the no-flow signal disappears.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The destage function ensures that the lowest numbers of pumps are running to save energy and to avoid dead-head water circulation in the variable-speed pump. If the destage function is set to [0] Disabled, parameter 25-30 Destage Function Time is not activated. Option Name Description...
Page 552
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE Use this option only if [1] Soft starter or [2] Star-Delta is selected in parameter 25-02 Motor Start. When adding a fixed-speed pump controlled by a soft starter or a star-delta starter, it is possible to delay the ramp down of the lead pump until a preset time after the start of the fixed-speed pump.
Page 553
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Speed Destaging Lead pump (controlled by drive) Fixed-speed pump (controlled by soft starter) Time P PC-41 Lead pump starts to ramp up Cascade Controller prepares for removing pump Figure 122: Destaging with Ramp-up Delay 25-42 Staging Threshold Default value: Size related...
Page 554
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions is the ratio of parameter 4-11 Motor Speed Low Limit [RPM] or parameter 4-12 Motor Speed Low Limit [Hz], to parameter 4-13 Motor Speed High Limit [RPM] or parameter 4-14 Motor Speed High Limit [Hz], expressed in percent. Destaging threshold must range from to 100%, where n is motor speed low limit and n is motor speed high limit.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Readout of the calculated value for destaging speed. When removing a fixed-speed pump to prevent an overshoot of pressure, the variable-speed pump ramps up to a higher speed. When the variable-speed pump reaches the destaging speed, the fixed-speed pump is destaged.
Page 556
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description At command Alternation of the lead-pump function takes place at an external command signal or a preprogrammed event. See parameter 25-51 Alternation Event for available options. At staging or command Alternation of the lead pump takes place at staging or according to [2] At command.
Page 557
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: VisStr[7] Change during operation: True Readout parameter for the alternation time interval value set in parameter 25-52 Alternation Time Interval. 25-54 Alternation Predefined Time Default value: Parameter type: Size related Range, 0 - 0 Setup:...
Page 558
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The following illustration is an example of the slow transfer-staging. The variable-speed pump (top graph) and 1 fixed-speed pump (bottom graph) run before the staging command. When the [0] Slow transfer command is activated, an alternation is carried out by ramping the variable-speed pump to parameter 4-13 Motor Speed High Limit [RPM] or parameter 4-14 Motor Speed High Limit [Hz], and then decelerated to zero speed.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 25-59 Run on Mains Delay Default value: 0.5 s Parameter type: Range, Par. 25-58 - 5 s Setup: All setups Conversion index: Data type: Uint16 Change during operation: True NOTICE This parameter is only active if the option selected in parameter 25-50 Lead Pump Alternation is different from [0] Off.
Page 560
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: VisStr[4] Change during operation: True Readout of the status for each of the relays assigned to control the pumps. Every element in the array shows a relay. If a relay is activated, the corresponding element is set to On.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions View the interlock status of the connected compressors. 25-9* Service 5.24.7 The parameters in this group are used if there is a service on 1 or more of the pumps controlled. 25-90 Pump Interlock Default value: [0] Off...
Page 562
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 51: Relevant Parameters for Analog Inputs, Outputs, and Relays Terminal Parameters Analog inputs X42/1 Parameter 26-00 terminal X42/1 Mode, parameter 26-10 Terminal X42/1 Low Voltage. X42/3 Parameter 26-01 terminal X42/3 Mode, parameter 26-20 Terminal X42/3 Low Voltage.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 52: Relevant Parameters for Analog Inputs, Outputs, and Relays When Using Fieldbus (continued) Terminal Parameters X42/99 Parameter 18-35 analog Out X42/11 [V]. Analog inputs (read) Parameter 16-62 Analog Input 53. Parameter 16-64 Analog Input 54 Analog output Parameter 6-63 Terminal X30/8 Output Bus Control.
Page 564
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [1]* Voltage Pt 1000 [°C] Pt 1000 [°F] Ni 1000 [°C] Ni 1000 [°F] 26-01 Terminal X42/3 Mode Default value: [1] Voltage Parameter type: Option Setup: All setups Conversion index: –...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE If the input is not in use, set it for voltage. If set for temperature and used as feedback, set the unit for either Celsius or Fahrenheit. Parameter 20-12 Reference/Feedback Unit. Parameter 21-10 Ext.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 26-15 Term. X42/1 High Ref./Feedb. Value Default value: Parameter type: Range, -999999.999 - 999999.999 Setup: Conversion index: All setups Data type: Int32 Change during operation: True Enter the analog input scaling value that corresponds to the high-voltage value set in parameter 26-11 Terminal X42/1 High Voltage. 26-16 Term.
Page 567
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 26-21 Terminal X42/3 High Voltage Default value: 10 V Parameter type: Range, Par. 26-20 - 10 V Setup: All setups Conversion index: Data type: Int16 Change during operation: True Enter the high-voltage value. This analog input scaling value should correspond to the high reference/ feedback value set in parameter 26-25 Term.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Disabled [1]* Enabled 26-3* Analog Input X42/5 5.25.5 Parameters for configuring the scaling and limits for analog input terminal X42/5. 26-30 Terminal X42/5 Low Voltage Default value: 0.007 V Parameter type: Range, 0 - par.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 26-37 Term. X42/5 Live Zero Default value: [1] Enabled Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True This parameter makes it possible to enable the live zero monitoring, for example, where the analog input is the drive control, rather than being used as a decentral I/O system, such as a building management system.
Page 570
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [109] Out frq 0-Fmax [113] Ext. closed loop 1 0–100%, (0–10 V). [114] Ext. closed loop 2 0–100%, (0–10 V). [115] Ext. closed loop 3 0–100%, (0–10 V). [117] Shaft power [139]...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 26-44 Terminal X42/7 Timeout Preset Default value: Parameter type: Range, 0 - 100% Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: True Holds the preset level of terminal X42/7. If a fieldbus and a timeout function are selected in parameter 26-50 Terminal X42/9 Output, the output presets to this level.
Page 572
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [139] Bus ctrl 0–100%, (0–10 V). [141] Bus ctrl t.o. 0–100%, (0–10 V). [147] Main act val [156] Flow rate [254] DC link 26-51 Terminal X42/9 Min. Scale Default value: Parameter type: Range, 0 - 200%...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Holds the preset level of terminal X42/9. If a fieldbus and a timeout function are selected in parameter 26-60 Terminal X42/11 Output, the output presets to this level. 26-6* Analog Out X42/11 5.25.8 Parameter for configuring the scaling and output function for analog output terminal X42/11.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 26-61 Terminal X42/11 Min. Scale Default value: Parameter type: Range, 0 - 200% Setup: All setups Conversion index: Data type: Int16 Change during operation: True Scale the minimum output of the selected analog signal at terminal X42/11 as a percentage of the maximum signal level. For example, if 0 V (or 0 Hz) is required at 25% of the maximum output value, program 25%.
Page 575
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Relay wiring configuration using MCO 101 or MCO 102 For a detailed description of commissioning for mixed pump and master/follower applications (using relay operation), refer to VLT® Cascade Controller Options MCO 101/102 Operating Instructions. Serial communication wiring configuration The serial communication wiring configuration supports the master/follower cascade controller setup controlling up to 8 pumps in total.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Primary master 1 Follower 1 Follower 2 Follower X (up to 7 followers) Figure 124: Serial Communication Wiring Master/Follower Configuration 5.26.2 The master/follower cascade control mode offers the best performance, the most precise control, and maximum energy savings. This mode controls multiple equally sized pumps in parallel runs all pumps at the same speed, and stages the pumps on an off according to system requirements.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 100% 100% 200% 200% Figure 125: Mixed-pump Configuration Unequal Pump Size Configuration 5.26.4 The unequal pump size configuration supports a limited mix of fixed-speed pumps in different sizes. This configuration provides the larges range of system output with the smallest number of pumps.
Page 578
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Ready The pump is available for use by the Cascade Controller. On drive The pump is: • running. • connected to the drive. • controlled by the Cascade Controller. On mains The pump is: •...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* No operation The drive does not issue any commands. Online The pump is available to the Cascade Controller. Alternate - on The drive forces the selected pump to be the lead pump. Offline - off The drive turns off the pump and makes it unavailable for cascading.
Page 580
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Disabled Turns off the Cascade Controller option. Master/follower Select this option to use only variable-speed pumps connected to drives. Selecting this option sets parameter 8-30 Protocol to [23] Modbus multi master.
Page 581
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 27-14 Pump Capacity Default value: Size related Parameter type: Range, 10 - 800%, Array [9] Setup: 2 setups Conversion index: Data type: Uint16 Change during operation: False Enter the capacity of each pump in the system relative to the 1st pump. This is an indexed parameter with 1 entry per pump. The capacity of the 1st pump is 100%.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True NOTICE Ensure that the value in this parameter does not cause overpressure in the system. Enter the time to spin unused pumps. If a fixed-speed pump has not run in the last 72 hours, it is turned on for this time. This function prevents the damage caused by leaving the pump off for too long.
Page 584
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions NOTICE In master/follower applications, the override limit is used as the wake-up condition. OBW (27-71) SBW (27-70) Actual head Setpoint SBW (27-70) OBW (27-71) OBW timer (27-25) Figure 128: OBW Time 27-22 Fixed Speed Only Operating Range Default value: Size related...
Page 586
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 27-24 Destaging Delay Default value: 15 s Parameter type: Range, 0 - 3000 s Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Enter the time during which the system feedback must remain above the operating range before a pump is turned off. If the system is operating with at least 1 variable-speed pump available, parameter 27-20 Normal Operating Range is used.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions F VLT pump Pump switch-off (4-12) Destage timer period (27-27) Figure 131: Destage Function Time 27-3* Staging Speed 5.26.9 The parameters in this group are used for configuring the master/follower control response. 27-30 Auto Tune Staging Speeds Default value: [1] Enabled...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 27-33 Stage Off Speed [RPM] Default value: Size related Parameter type: Range, 0 - 1500 [RPM], Array [11] Setup: Conversion index: All setups Data type: Uint16 Change during operation: True If the lead pump speed is lower than the value in this parameter for the time specified in parameter 27-24 Destaging Delay, and more than 1 variable-speed pump is on, a variable-speed pump is turned off.
Page 590
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Speed Ramping starts Ramp down (27-41) delay Time Staging starts Figure 134: Ramp Down Delay 27-42 Ramp Up Delay Default value: Parameter type: Range, 0 - 12 s Setup: All setups Conversion index: Data type: Change during operation:...
Page 591
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Fixed speed pump Motor speed high Monitor feedback and change to closed loop if setpoint is reached Staging speed (27-43) Variable speed pump Motor speed Time Closed loop Figure 136: Staging Threshold 27-44 Destaging Threshold Default value: Size related...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True Shows the actual staging speed based on the staging threshold. 27-47 Destaging Speed [RPM] Default value: Parameter type: 0 RPM Range, 0 - 0 [RPM] Setup: All setups Conversion index:...
Page 593
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Disabled The Cascade Controller is not allowed to select the best time to alternate the lead pump. 27-51 Alternation Event Default value: – Parameter type: Option Setup: All setups Conversion index:...
Page 594
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Disabled Enabled 27-55 Alternation Predefined Time Default value: Parameter type: Size related Range, 0 - 0 Setup: All setups Conversion index: Data type: TimeOfDayWoDate Change during operation: True Enter the time of day for pump alternation.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 27-6* Digital Inputs 5.26.12 The parameters in this group are for configuring digital inputs. The parameters are only available if VLT® Advanced Cascade Controller MCO 102 is installed. 27-60 Terminal X66/1 Digital Input Default value: –...
Page 596
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [37] Emergency mode [42] Ref source bit 0 [51] hand/auto start [52] Run permissive [53] Hand start [54] Auto start [55] DigiPot increase [56] DigiPot decrease [57] DigiPot clear [62] Reset counter A...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 27-64 Terminal X66/9 Digital Input Default value: – Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True The options for this parameter are the same as those listed for parameter 27-60 Terminal X66/1 Digital Input. 27-65 Terminal X66/11 Digital Input Default value: –...
Page 599
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Navn Description Drive 4 enable Drive 5 enable Drive 6 enable Drive 7 enable Drive 8 enable Pump 1 to drive 1 Pump 1 to drive 2 [10] Pump 1 to drive 3 [11] Pump 1 to drive 4 [12]...
Page 600
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Navn Description [36] Pump 4 to drive 5 [37] Pump 4 to drive 6 [38] Pump 4 to drive 7 [39] Pump 4 to drive 8 [40] Pump 5 to drive 1 [41] Pump 5 to drive 2 [42]...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Set-up 3 Set-up 4 5.26.15 27-9* Readouts This parameter group contains readout parameters for the Cascade CTL Option. 27-91 Cascade Reference Default value: Parameter type: Range, -200 - 200% Setup: All setups Conversion index:...
Page 603
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Coast The system is stopped due to coasting. Alarm The system is operating with an alarm. Staging A staging operation is in progress. [10] Destaging A destaging operation is in progress. [11] Alternating An alternation operation is in progress.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Parameter Group 29-** Water Application Functions 5.27 29-0* Pipe Fill Function 5.27.1 In water supply systems, water hammering can occur when filling the pipes too fast. It is therefore recommended to limit the filling rate. Pipe fill mode eliminates the occurrence of water hammering associated with the rapid exhausting of air from the piping system by filling the pipes at a low rate.
Page 605
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Speed Maximum speed Closed loop Minimum speed Fill rate unit/sec. Inital ramp Filled setpoint Time Figure 140: Vertical Pipe System 29-00 Pipe Fill Enable Default value: Parameter type: [0] Disabled Option Setup: 2 setups...
Page 606
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Set the filling speed for filling horizontal pipe systems. The speed can be selected in Hz or RPM depending on the selection made in parameter 4-11 Motor Speed Low Limit [RPM]/parameter 4-13 Motor Speed High Limit [RPM] or in parameter 4-12 Motor Speed Low Limit [Hz]/parameter 4-13 Motor Speed High Limit [Hz].
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 29-1* Deragging Function 5.27.2 The purpose of the deragging feature is to free the pump blade of debris in wastewater applications so that the pump operates normally. A deragging event is defined as the time when the drive starts to drag to when the deragging finishes. When a derag is started, the drive first ramps to a stop and then an off-delay expires before the 1st cycle begins.
Page 608
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions As timed action (parameter group 23-** TIme-based Functions). On high power (parameter group 29-2* Derag Power Tuning. 29-10 Derag Cycles Default value: Parameter type: Size related Range, 0=Off - 10 Setup: 2 setups Conversion index:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The speed at which the drive derags measured in Hz. 29-15 Derag Off Delay Default value: 10 s Parameter type: Range, 1 - 600 s Setup: All setups Conversion index: Data type: Uint32 Change during operation:...
Page 610
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Power [kW/HP] The calculated power + the power factor (readout) Par. 29-20, Par. 29-21 High speed power Par. 29-30, Par. 29-31 Activate derag Derag power factor Par. 29-22 Low speed power Par.
Page 611
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 29-22 Derag Power Factor Default value: 200% Parameter type: Range, 1 - 400% Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Set a correction if derag detection reacts on a power value that is too low. 29-23 Derag Power Delay Default value: 601 s...
Page 612
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 29-28 High Speed [RPM] Default value: Size related Parameter type: Range, 0.0 - par. 4-13 Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Set the output speed used for registration of derag power at high speed in RPM. 29-29 High Speed [Hz] Default value: Size related...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 29-34 Consecutive Derag Interval Default value: Size related Parameter type: Range, 0 - 3600 s Setup: All setups Conversion index: Data type: Uint16 Change during operation: False Derags are considered to be consecutive if they happen within the interval specified in this parameter. 29-35 Derag at Locked Rotor Default value: [0] Disabled...
Page 614
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Figure 143: Pre/Post-Lube Function, Example Speed curve. Start command (for example, terminal 18). Pre-lube output signal. Start command issued (for example, terminal 18 activated). The start delay timer (parameter 1-71 Start Delay) and the pre-lube timer (parameter 29-41 Pre Lube Time) start running.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True Enter for how long the pre-lube function is to be active. Only use this parameter, when [1] Pre Lube Only is selected in parameter 29-40 Pre/Post Lube Function.
Page 616
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Start command issued (for example, terminal 18 is set to Digital signal from an external device becomes active active). before parameter 29-50 Validation Timeexpires. When parameter 29-51 Verification Time passes, the drive checks the signal from the external device again and then runs normally.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Select the operating mode of the flow monitor function. Option Name Description [0]* Confirmation only The flow confirmation function is only active during the start-up of the pump. Monitor and stop The flow confirmation function is active during and after the pump start-up.
Page 618
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Reading the data The measured data is available via readout parameters: Parameter 29-65 Totalized Volume. Parameter 29-66 Actual Volume. Parameter 29-69 Flow. To show the readout parameters on the LCP, configure the display lines. Comparator operands can use the data from readout parameters as conditions for SLC and as triggers for actions.
Page 619
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Analog input X30/11 Analog input X30/12 Analog input X42/1 Analog input X42/3 Analog input X42/5 Analog input X48/2 Pulse input 29 Pulse input 33 [10] Bus feedback 1 [11] Bus feedback 2 [12]...
Page 620
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [13] /min [14] 29-63 Totalized Volume Unit Default value: Parameter type: [0] Disabled Option Setup: All setups Conversion index: – Data type: Change during operation: Uint8 True Select the unit for parameter 29-65 Totalized Volume.
Page 621
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description acre-in acre-ft 29-65 Totalized Volume Default value: Parameter type: 0 TotalizedVolumeUnit Range, 0 - 2147483647, Array Setup: All setups Conversion index: Data type: Uint32 Change during operation: False Shows the total volume of pumped water.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Do not reset Parameter 29-66 Actual Volume is not reset. Do reset Parameter 29-66 Actual Volume is reset to 0. 29-69 Flow Default value: Parameter type: 0 FlowMeterUnit Range, 0 - 2147483647 FlowMeterUnit...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Protects the motor from the locked rotor condition. The control algorithm detects a possible locked rotor condition in the motor and trips the drive to protect the motor. 30-23 Locked Rotor Detection Time [s] Default value: 0.10 s...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint32 Change during operation: False NOTICE Changing this parameter affects the settings of other parameters. Select the motor frequency from the motor nameplate data. 30-9* Wifi LCP 5.28.4 Use the parameters in this group for configuring the wireless LCP 103.
Page 625
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 30-94 IP Address Default value: Size related Parameter type: Range, 0 - 4294967295 Setup: 1 setup Conversion index: Data type: OctStr[4] Change during operation: True Enter the IP address to connect to. 30-95 Submask Default value: Size related...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 30-99 Wifi Network Mode Default value: [0] Access point Parameter type: Option Setup: 1 setup Conversion index: – Data type: Uint8 Change during operation: True Option Name Description [0]* Access point Client Parameter Group 31-** Bypass Option 5.29...
Page 627
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 31-03 Test Mode Activation Default value: [0] Disabled Parameter type: Option Setup: Conversion index: All setups – Data type: Uint8 Change during operation: True Option Name Description [0]* Disabled Test mode is disabled. Enabled The motor runs in bypass while the drive can be tested into an open circuit.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Shows the value received in PCD6 of the fieldbus telegram. 34-07 PCD 7 Write to MCO Default value: Parameter type: Range, 0 - 65535 Setup: All setups Conversion index: Data type: Uint16 Change during operation: True...
Page 630
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Change during True operation: Shows the value sent in PCD2 of the fieldbus telegram. 34-23 PCD 3 Read from MCO Default value: Parameter type: Range, 0 - 65535 Setup: All setups Conversion index: Data type: Uint8...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True Shows the value sent in PCD8 of the fieldbus telegram. 34-29 PCD 9 Read from MCO Default value: Parameter type: Range, 0 - 65535 Setup: All setups Conversion index:...
Page 632
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Not connected PT100 2-wire PT1000 2-wire PT100 3-wire PT1000 3-wire 35-02 Term. X48/7 Temperature Unit Default value: [60] °C Parameter type: Option Setup: All setups Conversion index: –...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Select the unit to be used with temperature input X48/10 settings and readouts. Option Name Description [60]* °C [160] °F 35-05 Term. X48/10 Input Type Default value: [0] Not connected Parameter type: Option Setup:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal X48/4. A high time constant value improves dampening but also increases the time delay through the filter. 35-15 Term.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True This parameter facilitates the possibility of enabling or disabling the temperature monitor for terminal X48/4. Set the temperature limits in parameter 35-26 Term.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter the reference or feedback value (in RPM, Hz, bar, and so on) that corresponds to the voltage or current set in parameter 35-42 Term. X48/2 Low Current. 35-45 Term. 48/2 High Ref./Feedb. Value Default value: 100 ReferenceFeedbackUnit Parameter type:...
Page 638
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Current [1]* Voltage PT1000 [°C] PT1000 [°F] Ni 1000 [°C] Ni 1000 [°F] 36-01 Term. X49/3 Mode Default value: [1] Voltage Parameter type: Option Setup: All setups Conversion index: –...
Page 639
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Ni 1000 [°C] Ni 1000 [°F] 36-03 Term. X49/7 Mode Default value: Parameter type: [0] Voltage 0–10V Option Setup: All setups Conversion index: – Data type: Change during operation: Uint8 True Select the output mode of analog terminal X49/7.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Select the output mode of analog terminal X49/11. Option Name Description [0]* Voltage 0–10V Voltage 2–10V Current 0–20mA Current 4–20mA Digital 5.32.2 36-1* Analog Input X49/1 36-10 Terminal X49/1 Low Voltage Default value: 0.07 V Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 36-14 Terminal X49/1 Low Ref./Feedb. Value Default value: 0 ReferenceFeedbackUnit Parameter type: Range, -999999.999 - 999999.999 ReferenceFeedbackUnit Setup: All setups Conversion index: Data type: Int32 Change during operation: True Enter the reference or feedback value (in RPM, Hz, bar, and so on) corresponding to the voltage or current set in parameter 36-10 Terminal X49/1 Low Voltage or parameter 36-11 Terminal X49/1 Low Current.
Page 642
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Int16 Change during operation: True Enter the voltage corresponding to the low reference value set in parameter 36-24 Term. X49/3 Low Ref./Feedb. Value. 36-21 Terminal X49/3 Low Current Default value: 4 mA...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter the reference or feedback value (in RPM, Hz, bar, and so on) corresponding to the voltage or current set in parameter 36-22 Terminal X49/3 High Voltage or parameter 36-23 Terminal X49/3 High Current. 36-26 Term.
Page 644
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Enter the voltage corresponding to the high reference value set in parameter 36-35 Term. X49/5 High Ref./Feedb. Value. 36-33 Terminal X49/5 High Current Default value: 20 mA Parameter type: Range, 0 - 20 mA Setup: All setups Conversion index:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Disabled [1]* Enabled 36-4* Output X49/7 5.32.5 36-40 Terminal X49/7 Analogue Output Default value: [0] No operation Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True...
Page 646
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [113] Ext. closed loop 1 0–100%, (0–10 V) [114] Ext. closed loop 2 0–100%, (0–10 V) [115] Ext. closed loop 3 0–100%, (0–10 V) [139] Bus ctrl An output value set from fieldbus process data. The output works independently of internal functions in the drive.
Page 647
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [13] Below current, low The motor current is lower than set in parameter 4-50 Warning Current Low. [14] Above current, high The motor current is higher than set in parameter 4-51 Warning Current High.
Page 648
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [41] Below reference, low Active when the actual speed is below speed reference setting. [42] Above ref, high Active when actual speed is above speed reference setting. [45] Bus ctrl.
Page 649
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [73] Logic rule 3 See parameter group 13-4* Logic Rules. If logic rule 3 in SLC is true, the output goes high. Otherwise, it is low. [74] Logic rule 4 See parameter group 13-4* Logic Rules.
Page 650
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [153] ATEX ETR cur. warning Selectable if parameter 1-90 Motor Thermal Protection is set to [20] ATEX ETR or [21] Advanced ETR . If alarm 163, ATEX ETR cur.lim.warning is active, the output is 1.
Page 651
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [193] Sleep mode The drive/system has entered sleep mode. See parameter group 22-4* Sleep Mode. [194] Broken belt A broken-belt condition has been detected. Enable this function in parameter 22-60 Broken Belt Function.
Page 652
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [243] RS flipflop 3 See parameter group 13-1* Comparators. [244] RS flipflop 4 See parameter group 13-1* Comparators. [245] RS flipflop 5 See parameter group 13-1* Comparators. [246] RS flipflop 6 See parameter group 13-1* Comparators.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Parameter 36-40 Terminal X49/7 Analogue Output = [100] Output Frequency. Parameter 4-19 Max Output Frequency = 200 Hz. Example case 1: 5 V maximum output is required when the output frequency is 200 Hz. Parameter 36-43 Terminal X49/7 Max. Scale x 100% = 200%.
Page 654
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [103] Motor current The value is taken from parameter 16-37 Inv. Max. Current. The inverter maximum current (160% current) is equal to 20 mA. Example: Inverter normal current (11 kW) is 24 A. 160 %=38.4 A. Motor normal current is 22 A, the readout is 11.46 mA.
Page 655
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Drive ready Drive rdy/rem ctrl Stand-by/no warning Running Running/no warning Run on ref/no warn Alarm [10] Alarm or warning [11] At torque limit [12] Out of current range [13] Below current, low [14]...
Page 657
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [153] ATEX ETR cur. warning [154] ATEX ETR freq. warning [155] Verifying flow [160] No alarm [161] Running reverse [164] Local ref active, not OFF [165] Local ref active [166] Remote ref active [167]...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 36-53 Terminal X49/9 Max. Scale Default value: 100% Parameter type: Range, 0 - 200% Setup: All setups Conversion index: Data type: Int16 Change during operation: True Scale the maximum output of terminal X49/9. For example, the scaling is done for the following reasons: To provide an output value lower than the maximum possible value.
Page 660
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* No operation Indicates no signal on the analog output. [52] [100] Output freq. 0–100 0 Hz = 0 mA; 100 Hz = 20 mA. [101] Reference Parameter 3-00 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA Parameter 3-00 Reference Range [-Max - Max] -100% = 0 mA;...
Page 661
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 36-61 Terminal X49/11 Digital Output Default value: [0] No operation Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Option Name Description [0]* No operation Control ready Drive ready...
Page 662
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [35] External interlock [40] Out of ref range [41] Below reference, low [42] Above ref, high [45] Bus ctrl. [46] Bus ctrl, 1 if timeout [47] Bus ctrl, 0 if timeout [51] MCO controlled [59]...
Page 663
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [84] SL digital output E [85] SL digital output F [90] kWh counter pulse [120] Local ref active [150] CBM warning [151] ATEX ETR cur. alarm [152] ATEX ETR freq.
Page 665
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Match the minimum output of terminal X49/11 with a required value. The required value is defined as a percentage of the value selected in parameter 36-60 Terminal X49/11 Analogue Output. To know more about how this parameter works, see parameter 6-52 Terminal 42 Output Max Scale.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions The drive sends the value of this parameter to the output terminal when the terminal is controlled by a fieldbus and a timeout is detected. Parameter Group 40-** Special Settings 5.33 40-2* PM Motor Specific 5.33.1...
Page 667
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: False View the motor voltage when the logged event occurred. 40-44 Fault Log: DC Link Voltage Default value: Parameter type: Range, 0 - 10000 V, Array [10] Setup: Conversion index:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Int32 Change during operation: False View the CBM threshold for this alarm. 40-5* Advanced Control Settings 5.33.3 40-50 Flux Sensorless Model Shift Default value: Parameter type: Size related Option...
Page 669
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions [2] PM, salient IPM ¢ 40-53 Current PID Anti Windup Gain Default value: Size related Paramter type: Range, 0 - 500% Setup: All setups Conversion index: Data type: Int16 Change during operation: True This Flux parameter is active in the drive when the following parameters are set to 1 of the values listed here: Parameter 1-00 Configuration Mode...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 40-6* IPv6 Settings 5.33.4 40-60 IPv6 Address Assignment Default value: [3] Disable Parameter type: Option Setup: 1 setup Conversion index: – Data type: Uint8 Change during operation: True Select the method for assigning the IP address. If selecting [0] Manual, the IP address can be set in parameter 40-61 IPv6 Address. To stop communication via IPv6, select [3] Disable.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 40-64 DHCPv6 Server Default value: Size related Parameter type: Range, 3 - 39 Setup: 1 setup Conversion index: Data type: VisStr[39] Change during operation: True This parameter shows the IP address of the detected DHCPv6 server. 40-65 Lease Expires IPv6 Default value: Size related...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Shows status and configuration information of the current IoT protocol. 40-9* Security 5.33.6 40-90 UUID Default value: Size related Parameter type: Range, 36 - 36 Setup: 1setup Conversion index: Data type: Change during operation: VisStr[36] True...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Int8 Change during operation: True Shows the temperature of an auxiliary component. The elements of the array reference the temperature measurements from the NTC temperature sensors connected to hardware components in the drive.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True Shows the measured speed of fan A on the power card. Each power card has up to 3 fan connections. Place the fan in the drive according to the Operating Guide.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 43-22 FPC Fan C Speed Default value: 0 RPM Parameter type: Range, 0 - 65535, Array [2] Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Shows the speed of the power card fan C. 43-23 FPC Fan D Speed Default value: 0 RPM...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Parameter Group 45-** Condition Based Monitoring 5.35 45-0* Cockpit: Monitor 5.35.1 Use this parameter group to enable condition-based monitoring, define units, baseline computation, input sources, view baseline status, and progress. 45-00 Function Default value: [0] Off...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: TimeOfDay Change during operation: True This parameter shows at which date and time the monitoring function was started. 45-03 Stop Time Default value: Size related Parameter type: Range, 0 - 0, Array [6]...
Page 678
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 45-10 Alarm High Threshold Default value: Parameter type: Range 0 - 655.35%, Array [8] Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Set the maximum threshold limit. The drive triggers a notification when threshold limit is exceeded. Table 55: Options Parameter ID Description...
Page 679
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Set the maximum threshold limit for warning stage 1, in the parameter index. The drive triggers a warning notification when threshold limit is exceeded. Entering a value in the parameter indicates a user specified threshold limit. Table 57: Parameter Index Parameter ID Description...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 61: Parameter Index (continued) 45-16.1 Stator Winding Active 45-16.2 Stator Winding Load 45-16.3 Load Envelope 45-16.4 Sensor 1 Vibration 45-16.5 Sensor 2 Vibration 5.35.3 45-2* Baseline Settings Use the parameters in this group to configure how to capture baseline data. 45-20 Type Default value: Parameter type:...
Page 682
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Not started Baseline run running Online baseline running Baseline completed Baseline failed Online inadequate data 45-22 Progress Default value: Parameter type: Range, 0 - 100% Setup: All setups Conversion index: Data type:...
Page 683
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: True Select a suitable duration for baseline computation. If a value is not selected, by default, the system considers 2 minutes for baseline run and 1 hour for online baseline.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint16 Change during operation: True Use this parameter to set the minimum speed of the drive to begin condition-based monitoring functions. Ensure to set a value which exceeds the minimum speed limit of motor. The minimum limit of motor speed corresponds to the setting in parameter 4-11 Motor Speed Low Limit [RPM].
Page 686
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description [0]* Absolute Absolute value is considered as threshold. Offset Calculates threshold as a sum of the computed baseline data and the offset values. Factor Calculates threshold as baseline data * factor. The values can be specified in parameter 45-33 Alarm High and parameter 45-38 Alarm Low.
Page 687
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Table 66: Options Parameter ID Description 45-34.0 Stator Winding 45-34.1 Load Envelope 45-34.2 Sensor 1 Vibration 45-34.3 Sensor 2 Vibration 45-35 Warning S1 High Default value: Parameter type: Size related Range, 0 - 100% Setup: 2 setups...
Page 688
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 45-37 Warning S2 Low Default value: Size related Parameter type: Range, 0 - 100%, Array [6] Setup: 2 setups Conversion index: Data type: Uint16 Change during operation: True Type the threshold value for computing a warning S2 low notification. Based on the type of warning mode selected by the user, a warning S2 low threshold is calculated.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Gen. now - sensor 3 Based on the selections, threshold for sensor 3 is generated from actual baseline data. Gen. now - sensor 4 Based on the selections, threshold for sensor 4 is generated from actual baseline data.
Page 691
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Option Name Description Analog Input X48/2 Analog Input X49/1 [10] Analog Input X49/3 [11] Analog Input X49/5 Table 72: Option Parameter ID Description 45-50.0 Sensor 1 Vibration 45-50.1 Sensor 2 Vibration 45-51 Sensor 1 Unit Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 45-6* Stator Res. Setting 5.35.7 45-60 Active Threshold Default value: Parameter type: 0 - 100% Setup: 2 setups Conversion index: Data type: Uint16 Change during operation: True Use this parameter to activate the resonance region supply imbalance control. Enter the threshold offset value from the baseline data. 45-61 Load Mode Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 45-9* Actual Readouts 5.35.8 The parameters in this group are readout parameters showing the actual monitoring values. 45-90 Stator [%] Default value: Parameter type: 0 - 655.35% Setup: All setups Conversion index: Data type: Change during operation:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Int32 Change during operation: True This parameter shows the actual sensor 2 monitor value in the selected unit at motor output speed. 45-96 Sensor 3 [%] Default value: Parameter type: Range, 0 - 655.35% Setup:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions This parameter shows the time stamp of the latest modification to a notification threshold. 46-0* General 5.36.2 46-07 Monitoring Min Speed This parameter monitors the minimum speed as defined in parameter 45-45 Threshold Generation. 46-08 Monitoring Max Speed Default value: 0 RPM...
Page 696
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: Uint32 Change during operation: True Set the time in seconds to define duration during which the warning S2 is not triggered. When the value which is monitored exceeds or falls below the warning S2 threshold for more than the time specified in the parameter, a warning S2 is triggered.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 46-24 Resonance Load Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: True 5.36.5 46-3* Load Use the parameters in this group to enter, adjust, and display threshold values for load envelope monitoring function. 46-30 Alarm High Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Set the threshold value which defines a low S1 warning for load envelope monitoring. When the value of the monitored value exceeds the threshold specified in the parameter for the duration of time specified in warning S1 time, a low S1 warning is triggered. The parameter contains 20 index values which can be used to manually configure Load Warning S1 Low Threshold for each individual speed point.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 46-42 Warning S1 High Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Set the threshold value which defines a low alarm for load envelope monitoring. When the value of the monitored value exceeds the threshold specified in the parameter for the duration of time specified in alarm time, a low alarm is triggered.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Set the threshold value which defines a low alarm for load envelope monitoring. When the value of the monitored value exceeds the threshold specified in the parameter for the duration of time specified in alarm time, a low alarm is triggered.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Set the threshold value which defines a warning stage 2 high notification for monitoring. When the value of the monitored value exceeds the threshold specified in the parameter for the duration of time specified in alarm time, a high warning is triggered. The parameter contains 20 index values which can be used to manually configure Warning stage 2 high threshold for each individual speed point.
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions Data type: TimeOfDay Change during operation: True This parameter shows a timestamp of when the previous baseline capturing was stopped. 5.37.2 47-0* Speeds The parameters in this group show the baseline speed points of active and previous baseline data. 47-04 Actual Speed Default value: Parameter type:...
Page 704
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions This parameter shows the average of stator winding readings for the active baseline. 47-09 Actual Min Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 47-21 Previous Mean + 3 Std. Dev. Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False This parameter shows the mean and 3 standard deviations of stator resistance readings for the previous baseline. 47-22 Previous Mean Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions This parameter shows the average of stator resonance load recordings for the active baseline. 47-27 Actual Min Default value: Parameter type: Range, 0 - 655.35%, Array [20] Setup: All setups Conversion index: Data type: Uint16...
Page 708
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions This parameter shows the maximum positive load envelope recordings for the active baseline. An indexed parameter with 20 pointers of positive load envelope recordings with minimum to maximum. 47-33 Actual Mean + 3 Std. Dev. Default value: Parameter type: Range, 0 - 655.35%, Array [20]...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions This parameter shows the maximum value for load envelope readings for the previous baseline. 47-39 Previous Mean + 3 Std. Dev. Default value: Parameter type: Range, 0 - 655.35%, Array [20] Setup: All setups Converison index:...
Page 710
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions This parameter shows the maximum recordings from vibration sensors for the active baseline. 47-45 Actual Mean + 3 Std. Dev. Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 47-51 Previous Mean Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False This parameter shows the average of Sensor 1 readings for the previous baseline. 47-52 Previous Min Default value: Parameter type:...
Page 712
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 47-57 Actual Min Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False This parameter shows the minimum value of recordings from vibration sensors for active baseline. 47-58 Actual Counter Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 47-69 Previous Max Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False This parameter shows the maximum value for Sensor 3 readings for the previous baseline. 47-70 Previous Mean + 3 Std.
Page 715
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 47-75 Actual Mean + 3 Std. Dev. Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False This parameter shows the average and 3 standard deviations for upper threshold of recordings from vibration sensors for active baseline. 47-76 Actual Mean Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 47-81 Previous Mean Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False This parameter shows the average of Sensor 4 readings for the previous baseline. 47-82 Previous Min Default value: Parameter type:...
Programming Guide | VLT® Aqua Drive FC 202 Parameter Descriptions 47-98 Previous Max Speed Default value: 0 RPM Parameter type: Range, 0 - 35700 [RPM] Setup: All setups Conversion index: Data type: Uint16 Change during operation: True This parameter shows the maximum speed of the previous baseline data. Parameter Group 50-** License 5.38 50-00 License Installed...
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Troubleshooting Status Messages Warnings and Alarms 6.1.1 A warning or an alarm is signaled by the relevant indicator light on the front of the drive and indicated by a code on the display. A warning remains active until its cause is no longer present.
Page 719
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode [0] Trip +...
Page 720
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 721
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 722
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 723
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 724
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 725
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 726
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 727
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 728
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 729
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 730
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 731
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 732
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Page 733
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 77: Alarm/Warning Code List (continued) Description Warning Alarm/ Alarm/ Parameter Emergency mode alarm handling Warranty- trip trip lock reference selected in parameter 24-09 affecting Emergency Mode Alarm Handling. alarms in Critical alarms cause a trip emergency mode...
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Indicator Light 6.1.3 Table 78: Indicator Light Warning Yellow Alarm Flashing red Trip locked Yellow and red Alarm Word, Warning Word, and Extended Status Word 6.1.4 Table 79: Description of Alarm Word Alarm word Alarm word 2 Alarm word 3...
Page 735
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 79: Description of Alarm Word (continued) Alarm word Alarm word 2 Alarm word 3 Parameter 16-90 Parameter 16-91 Parameter 16-97 Alarm Word Alarm Word 2 Alarm Word 3 00020000 131072 Internal fault (A38) KTY error –...
Page 736
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 80: Description of Warning Word (continued) Warning word Warning word 2 Warning word 3 Parameter 16-92 Parameter 16-93 Parameter 16-98 Warning Word Warning Word 2 Warning Word 3 00000010 Ctrl. word TO (W17) –...
Page 737
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 80: Description of Warning Word (continued) Warning word Warning word 2 Warning word 3 Parameter 16-92 Parameter 16-93 Parameter 16-98 Warning Word Warning Word 2 Warning Word 3 01000000 16777216 Mains failure (W36) Reserved Sensor 2 S2...
Page 738
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 81: Description of Extended Status Word (continued) Ext. status word Ext. status word 2 Ext. status word 3 Parameter 16-94 Parameter 16-95 Parameter 16-99 Ext. Status Word Ext. Status Word 2 Ext.
Page 739
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 81: Description of Extended Status Word (continued) Ext. status word Ext. status word 2 Ext. status word 3 Parameter 16-94 Parameter 16-95 Parameter 16-99 Ext. Status Word Ext. Status Word 2 Ext.
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Table 81: Description of Extended Status Word (continued) Ext. status word Ext. status word 2 Ext. status word 3 Parameter 16-94 Parameter 16-95 Parameter 16-99 Ext. Status Word Ext. Status Word 2 Ext.
Page 741
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting WARNING/ALARM 4, Mains Phase Loss Cause A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier.
Page 742
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Show the thermal drive load on the LCP and monitor the value. When running above the drive continuous current rating, the counter increases. When running below the drive continuous current rating, the counter decreases. WARNING/ALARM 10, Motor ETR Overtemperature Cause According to the electronic thermal protection (ETR), the motor is too hot.
Page 743
Alarm 15, Hardware Mismatch Cause A fitted option is not operational with the present control card hardware or software. Troubleshooting Record the values of the following parameters and contact Danfoss. Parameter 15-40 FC Type Parameter 15-41 Power Section Parameter 15-42 Voltage...
Page 744
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting WARNING/ALARM 17, Control Word Timeout Cause There is no communication to the drive. The warning is only active when parameter 8-04 Control Word Timeout Function is NOT set to [0] Off. If parameter 8-04 Control Word Timeout Function is set to [5] Stop and Trip, a warning appears. The drive then ramps down until it trips, while giving an alarm.
Page 745
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Warning 23, Internal Fan Fault Cause The fan warning function is a protective function that checks if the fan is running/mounted. The fan warning can be disabled in parameter 14-53 Fan Monitor by selecting [0] Disabled. For drives with DC fans, a feedback sensor is mounted in the fan.
Page 746
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting ALARM 27, Brake IGBT/Brake Chopper Short-circuited Cause The brake transistor is monitored during start-up. If a short circuit occurs, the brake function is disabled, and an alarm is issued. The drive is tripped.
Page 747
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting ALARM 32, Motor Phase W Missing Cause Motor phase W between the drive and the motor is missing. Troubleshooting Remove power from the drive and check motor phase W. ALARM 33, Inrush Fault Cause Too many power-ups have occurred within a short time period.
Page 748
Power cycle the drive. If the alarm occurs again, contact a Dan- foss supplier. Troubleshooting See the above table for the causes and solutions for different internal faults. If the fault persists, contact the Danfoss supplier or service department for assistance. ALARM 39, Heat Sink Sensor Cause There is no feedback from the heat sink temperature sensor.
Page 749
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting WARNING 41, Overload T29 Troubleshooting Check the load connected to terminal 29 or remove the short-circuit connection. Check parameter 5-00 Digital I/O Mode and parameter 5-02 Terminal 29 Mode. WARNING 42, Ovrld X30/6-7 Troubleshooting, X30/6 Check the load connected to the terminal or remove the short-circuit connection.
Page 750
ALARM 50, AMA Calibration Cause A calibration error has occurred. Troubleshooting Contact a Danfoss supplier or the Danfoss service department. ALARM 51, AMA check U and I Cause The settings for motor voltage, motor current, and motor power are wrong.
Page 752
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting WARNING/ALARM 59, Current Limit Cause The current is higher than the value in parameter 4-18 Current Limit. Troubleshooting Ensure that the motor data in parameter 1-20 to parameter 1-25 is set correctly. Possibly increase the current limit.
Page 753
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting ALARM 63, Mechanical Brake Low Cause The actual motor current has not exceeded the release brake current within the start delay time window. WARNING 64, VOLTAGE LIMIT Cause The load and speed combination demands a motor voltage higher than the actual DC-link voltage. Troubleshooting Check if the mains input is not high enough.
Page 754
Cause The control card and power card are incompatible. Troubleshooting To check compatibility, contact the Danfoss supplier with the type code from the unit nameplate and the part numbers on the cards. ALARM 71, PTC 1 Safe Stop Cause Because the motor is too warm, the VLT® PTC Thermistor Card MCB 112 activated Safe Torque Off (STO).
Page 755
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting WARNING 76, Power Unit Setup Cause The required number of power units does not match the detected number of active power units. Troubleshooting When replacing a drive module, this warning can occur if the power-specific data in the module power card does not match the rest of the drive.
Page 756
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting WARNING/ALARM 92, No Flow Cause A no-flow condition has been detected in the system. Parameter 22-23 No-Flow Function is set for alarm. Troubleshooting Troubleshoot the system and reset the drive after the fault has been cleared. WARNING/ALARM 93, Dry Pump Cause A no-flow condition in the system with the drive operating at high speed may indicate a dry pump.
Page 757
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Troubleshooting Troubleshoot the system. Reset the drive when the fault is cleared. WARNING 98, Clock Fault Cause Time is not set or the RTC clock has failed. Troubleshooting Reset the clock in parameter 0-70 Date and Time. ALARM 99, Locked Rotor Cause The rotor is blocked.
Page 758
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting WARNING/ALARM 146, Mains Voltage Cause Mains voltage is outside valid operating range. Troubleshooting See the following report values for details. Voltage too low: 0=R-S, 1=S-T, 2=T-R Voltage too high: 3=R-S, 4=S-T, 5=T-R WARNING/ALARM 147, Mains Frequency Cause Mains frequency is outside valid operating range.
Page 759
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Warning 200, Emergency Mode Cause Emergency mode is active. Troubleshooting The warning clears when emergency mode is removed. See the emergency mode data in the alarm log. Warning 201, Emerg. M Was Active Cause Emergency mode is no longer active.
Page 760
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting ALARM 243, Brake IGBT Cause This alarm is only for multi-drive systems. It is equivalent to alarm 27, Brake chopper fault. The report value in thie alarm log indicates which drive module generated the alarm. This IGBT fault can be caused by any of the following: The DC fuse is blown.
Page 761
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting ALARM 246, Power Card Supply Cause The supply on the power card is out of range. This alarm is only for multi-drive systems. It is equivalent to Alarm 46, Power card supply. The report value in the alarm log indicates which drive module generated the alarm: 1 = Left drive module.
Page 762
Emergency mode critical alarm has occurred and impacts the drive performance in Emergency mode. Troubleshooting Reset the drive. If resetting the drive does not solve the problem, contact Danfoss service department. ALARM 421, FPC Temp Cause A fault caused by the on-board temperature sensor is detected on the fan power card. The report values identify which fan power card detected the fault.
Page 763
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting ALARM 424, FPC Update Successful Cause This alarm is generated when the control card has updated the fan power card PUD successfully. Troubleshooting Press [Reset] to stop the alarm. ALARM 425, FPC Update Failure Cause This alarm is generated after the control card failed to update the fan power card PUD.
Page 764
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Troubleshooting Check the stator windings. Warning 501, Load Envelope Warning 2 Cause Application load has reached condition yellow. Troubleshooting Investigate the root cause for the increased motor load. Warning 502, Vibration Monitoring Warning 2 Cause A significant increase in motor vibration is detected.
Page 765
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Cause Application load has reached condition yellow. Troubleshooting Check root cause for high motor load. Alarm 512, Sensor 1 Monitoring Alarm Cause There is an excessive amount of motor vibration on sensor 1. The vibration levels have reached condition red. Troubleshooting Investigate the root cause for the excessive vibration.
Page 766
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Alarm 515, Sensor 4 Monitoring Alarm Cause There is an excessive amount of motor vibration on sensor 4. The vibration levels have reached condition red. Troubleshooting Investigate the root cause for the excessive vibration. Before commissioning of condition-based monitoring, ensure to comply with the ISO10816 standard for machinery.
Page 767
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Warning 522, Sensor 1 Thld At Max/Min Cause The sensor 1 threshold in the condition-based monitoring is at its minimum or maximum value of the Sensor 1 function. Troubleshooting Check the threshold values at maximum or minimum in parameter group 46-** CBM Adv Thresholds to parameter group 46-4* Sensor 1 and adjust the values if needed.
Page 768
Programming Guide | VLT® Aqua Drive FC 202 Troubleshooting Troubleshooting Investigate the root cause for the value reaching the red low level. For example, lost connection to analog inputs or no proper data communication on fieldbus sensors. Alarm 551, Sensor 2 Low Monitoring Alarm The value measured on Sensor 2 is very low and has reached condition red low.
Page 770
Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies.
Need help?
Do you have a question about the VLT Aqua Drive FC 202 and is the answer not in the manual?
Questions and answers