Parameter Description
26-54 Terminal X42/9 Timeout Preset
Range:
0 %
[0 -
*
100 %]
3
3
26-60 Terminal X42/11 Output
Option:
[0]
No operation
*
[52]
MCO 0-20mA/
0-10V
[100] Output freq.
0-100
[101] Reference Min-
Max
[102] Feedback +-200% -200% to +200% of
[103] Motor cur. 0-Imax 0–inverter maximum current
[104] Torque 0-Tlim
[105] Torque 0-Tnom
[106] Power 0-Pnom
[107] Speed 0-HighLim
[108] Torque +-160%
[109] Out frq 0-Fmax
[113] Ext. Closed Loop
1
[114] Ext. Closed Loop
2
[115] Ext. Closed Loop
3
[139] Bus ctrl.
[141] Bus ctrl t.o.
[156] Flow Rate
222
VLT
Function:
Holds the preset level of terminal X42/9.
If a fieldbus and a timeout function are
selected in parameter 26-60 Terminal X42/11
Output, the output presets to this level.
Function:
Set the function of terminal X42/11.
0–100 Hz, (0–10 V).
Minimum reference–maximum
reference, (0–10 V).
parameter 3-03 Maximum Reference, (0–
10 V).
(parameter 16-37 Inv. Max. Current), (0–
10 V).
0–torque limit (parameter 4-16 Torque
Limit Motor Mode), (0–10 V).
0–motor rated torque, (0–0 V).
0–motor rated power, (0–10 V).
0–speed high limit
(parameter 4-13 Motor Speed High Limit
[RPM] and parameter 4-14 Motor Speed
High Limit [Hz]), (0–10 V).
0–100%, (0–10 V).
0–100%, (0–10 V).
0–100%, (0–10 V).
0–100%, (0–10 V).
0–100%, (0–10 V).
Danfoss A/S © 05/2018 All rights reserved.
®
AQUA Drive FC 202
26-61 Terminal X42/11 Min. Scale
For more information, see parameter 6-51 Terminal 42 Output Min
Scale.
Range:
0 %
[0 -
*
200 %]
26-62 Terminal X42/11 Max. Scale
See Illustration 3.36.
Range:
100 %
[0 -
200 %]
*
26-63 Terminal X42/11 Bus Control
Range:
0 %
[0 - 100 %] Holds the level of terminal X42/11 if
*
26-64 Terminal X42/11 Timeout Preset
Range:
0 %
[0 - 100 %] Holds the preset level of terminal X42/11.
*
Function:
Scale the minimum output of the selected
analog signal at terminal X42/11 as a
percentage of the maximum signal level. For
example, if 0 V is required at 25% of the
maximum output value, program 25%. Scaling
values up to 100% can never be higher than
the corresponding setting in
parameter 26-62 Terminal X42/11 Max. Scale.
Function:
Scale the maximum output of the selected
analog signal at terminal X42/9. Set the value to
the maximum value of the voltage signal
output. Scale the output to give a voltage lower
than 10 V at full scale; or 10 V at an output
below 100% of the maximum signal value. For
example, if 10 V is the required output current
at a value between 0–100% of the full-scale
output, program the percentage value in the
parameter, that is, 50%=10 V. If a voltage 0–10 V
is required at maximum output, calculate the
percentage as follows:
10V
x100 %
desired maximum voltage
that is
10V
5V :
x100 % = 200 %
5V
Function:
controlled by bus.
Function:
If a fieldbus and a timeout function are
selected, the output presets to this level.
MG20OB02