Parameter Description
Example 2:
Variable = feedback, range = -200% to +200%.
Range needed for output = 0–100%.
Output signal 0 mA or 4 mA is needed at 0% (50% of
range). Set parameter 6-51 Terminal 42 Output Min Scale to
50%.
Output signal 20 mA is needed at 100% (75% of range).
Set parameter 6-52 Terminal 42 Output Max Scale to 75%.
20 mA
0/4 mA
0%
50%
-200%
0%
Illustration 3.38 Example 2
Example 3:
Variable value = reference, range = minimum reference–
maximum reference
Range needed for output = minimum reference (0%)–
maximum reference (100%), 0–10 mA.
Output signal 0 mA or 4 mA is needed at minimum
reference. Set parameter 6-51 Terminal 42 Output Min Scale
to 0%.
Output signal 10 mA is needed at maximum reference
(100% of range). Set parameter 6-52 Terminal 42 Output
Max Scale to 200%.
(20 mA/10 mA x 100%=200%).
20 mA
10 mA
0/4 mA
0%
100%
Min ref
Max ref
Illustration 3.39 Example 3
MG20OB02
Programming Guide
6-53 Terminal 42 Output Bus Control
Range:
0 %
6-54 Terminal 42 Output Timeout Preset
Range:
0 %
6-55 Terminal 42 Output Filter
Option: Function:
75%
100%
+100%
+200%
[0]
[1]
3.8.7 6-6* Analog Output X30/8
Analog outputs are current outputs: 0/4–20 mA. Common
terminal (terminal X30/8) is the same terminal and
electrical potential for analog common connection.
Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
Same options and functions as parameter 6-50 Terminal 42
Output.
200%
Max ref X 20/10
Danfoss A/S © 05/2018 All rights reserved.
Function:
[0 - 100 %] Holds the level of output 42 if controlled by
*
bus.
Function:
[0 -
Holds the preset level of output 42.
*
100 %]
If a timeout function is selected in
parameter 6-50 Terminal 42 Output, the output
is preset to this level if a fieldbus timeout
occurs.
The following readout parameters from selection in
parameter 6-50 Terminal 42 Output have a filter
selected when parameter 6-55 Terminal 42 Output Filter
is on:
Selection
Motor current (0–I
)
max
Torque limit (0–T
)
lim
Rated torque (0–T
)
nom
Power (0–P
)
nom
Speed (0–Speed
)
max
Table 3.19 Readout Parameters
Off Filter off.
*
On
Filter on.
3
0–20 mA
4–20 mA
[103]
[133]
[104]
[134]
[105]
[135]
[106]
[136]
[107]
[137]
97
3