Parameter Descriptions

3.17 Parameters: 16-** Data Readouts

3.17.1 16-0* General Status
3
3
16-00 Control Word
Range:
0 N/A
[0 - 65535 N/A] View the control word sent from the
*
16-01 Reference [Unit]
Range:
0.000 Reference-
FeedbackUnit
*
16-02 Reference %
Range:
0.0 %
[-200.0 - 200.0
*
%]
16-03 Status Word
Range:
0 N/A
[0 - 65535 N/A] View the status word sent from the
*
16-05 Main Actual Value [%]
Range:
0.00 %
[-100.00 - 100.00
*
%]
16-09 Custom Readout
Range:
0.00 CustomRea-
doutUnit
*
3-132
FC 300 Programming Guide
Function:
adjustable frequency drive via the serial
communication port in hex code.
Function:
[-999999.000 -
View the present
999999.000
reference value applied
ReferenceFeed-
on impulse or analog
backUnit]
basis in the unit
resulting from the
configuration selected in
1-00 Configuration Mode
(Hz, Nm or RPM).
Function:
View the total reference. The total
reference is the sum of digital, analog,
preset, bus, and freeze references, plus
catch-up and slow-down.
Function:
adjustable frequency drive via the serial
communication port in hex code.
Function:
View the two-byte word sent with
the status word to the bus master
reporting the main actual value.
Function:
[0.00 - 0.00
View the value of custom
CustomRea-
readout from 0-30 Unit for
doutUnit]
User-defined Readout to
0-32 Custom Readout Max
Value
MG.33.MA.22 - VLT
3.17.2 16-1* Motor Status
16-10 Power [kW]
Range:
0.00
[0.00 -
kW
10000.00
*
kW]
16-11 Power [hp]
Range:
0.00
[0.00 -
hp
10000.00 hp]
*
16-12 Motor voltage
Range:
0.0 V
[0.0 - 6000.0 V] View the motor voltage, a calculated
*
16-13 Frequency
Range:
0.0 Hz
[0.0 - 6500.0 Hz] View the motor frequency, without
*
16-14 Motor Current
Range:
0.00 A
[0.00 -
*
10000.00 A]
16-15 Frequency [%]
Range:
0.00 %
[-100.00 -
*
100.00 %]
®
is a registered Danfoss trademark
Function:
Displays motor power in kW. The value
shown is calculated on the basis of the
actual motor voltage and motor current.
The value is filtered, and therefore approx.
30 ms may pass from when an input value
changes to when the data readout values
change. The resolution of readout value on
serial communication bus is in 10 W steps.
Function:
View the motor power in HP. The value
shown is calculated on the basis of the
actual motor voltage and motor current.
The value is filtered, and therefore approx-
imately 30 ms may pass from when an
input value changes to when the data
readout values change.
Function:
value used for controlling the motor.
Function:
resonance dampening.
Function:
View the motor current measured as a
mean value, IRMS. The value is filtered,
and thus approximately 30 ms may pass
from when an input value changes to
when the data readout values change.
Function:
View a two-byte word reporting the actual
motor frequency (without resonance
dampening) as a percentage (scale 0000–
4000 Hex) of 4-19 Max Output Frequency.
Set 9-16 PCD Read Configuration index 1 to
send it with the status word instead of the
MAV.