Parameters 6-** Analog In/Out - Danfoss VLT AQUA Drive FC 202 Programming Manual

Software version: 3.30
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Parameter Description

3.8 Parameters 6-** Analog In/Out

3.8.1 6-0* Analog I/O Mode
Parameter group for setting up the analog I/O configu-
ration.
The frequency converter is equipped with 2 analog inputs:
Terminals 53.
Terminals 54.
The analog inputs can be allocated freely to either voltage
(0–10 V) or current input (0/4–20 mA).
NOTICE
Thermistors may be connected to either an analog or a
digital input.
6-00 Live Zero Timeout Time
Range:
Function:
10
[1 -
Enter the live zero timeout in s. Live zero timeout
s
99 s]
time is active for analog inputs, that is terminal 53
*
or terminal 54, used as reference or feedback
sources.
If the reference signal value associated with the
selected current input drops below 50% of the
value set in:
Parameter 6-10 Terminal 53 Low Voltage
Parameter 6-12 Terminal 53 Low Current
Parameter 6-20 Terminal 54 Low Voltage
Parameter 6-22 Terminal 54 Low Current
for a time period longer than the time set in
parameter 6-00 Live Zero Timeout Time, the function
selected in parameter 6-01 Live Zero Timeout
Function is activated.
6-01 Live Zero Timeout Function
Option:
Function:
Select the timeout function. The function set in
parameter 6-01 Live Zero Timeout Function is
activated if the input signal on terminal 53 or 54
is below 50% of the value in:
Parameter 6-10 Terminal 53 Low Voltage.
Parameter 6-12 Terminal 53 Low Current.
Parameter 6-20 Terminal 54 Low Voltage.
Parameter 6-22 Terminal 54 Low Current.
The function can also be activated for a time
period defined in parameter 6-00 Live Zero
Timeout Time. If several timeouts occur simulta-
neously, the frequency converter prioritizes the
timeout functions as follows:
MG20OB02
Programming Guide
6-01 Live Zero Timeout Function
Option:
[0]
Off
*
[1]
Freeze
output
[2]
Stop
[3]
Jogging
[4]
Max.
speed
[5]
Stop and
trip
Par 6-xx
High Ref./
Feedb. Value'
Par 6-xx
Low Ref./
Feedb. Value'
Illustration 3.34 Live Zero Conditions
6-02 Emergency Mode Live Zero Timeout Function
Option:
[0]
Off
*
[1]
Freeze
output
[2]
Stop
[3]
Jogging
[4]
Max. speed
Danfoss A/S © 05/2018 All rights reserved.
Function:
1.
Parameter 6-01 Live Zero Timeout
Function.
2.
Parameter 8-04 Control Word Timeout
Function.
Frozen at the present value. Live zero timeout
time does not apply to freeze output.
Overruled to stop.
Overruled to jog speed.
Overruled to maximum speed.
Overruled to stop with subsequent trip.
Ref./Feedback
[RPM]
1500
1200
900
600
300
150
1 V
5 V
Par 6-xx
'Low Voltage'or
'Low Current'
Par 6-xx
'High Voltage'or
'High Current'
Function:
Select the timeout function when the
emergency mode is active. The function set in
this parameter is activated if the input signal
on analog inputs is lower than 50% of the
low value for a time period defined in
parameter 6-00 Live Zero Timeout Time.
Frozen at the present value.
Overruled to stop.
Overruled to jog speed.
Overruled to maximum speed.
3
3
10 V
[V]
Analog input
91