Danfoss VLT AQUA Drive FC 202 Programming Manual page 97

Software version: 3.30
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Parameter Description
3.8.6 6-5* Analog Output 1
Parameters for configuring the scaling and limits for analog
output 1, that is terminal 42. Analog outputs are current
outputs: 0/4–20 mA. Common terminal (terminal 39) is the
same terminal and has the same electrical potential for
analog common and digital common connection.
Resolution on analog output is 12 bit.
6-50 Terminal 42 Output
Option:
Function:
NOTICE
Values for setting the minimum
reference are found in
parameter 3-02 Minimum Reference and
values for maximum reference in
parameter 3-03 Maximum Reference.
Select the function of terminal 42 as an
analog current output. A motor current of
20 mA corresponds to I
[0]
No
operation
[52]
MCO
0-20mA/
0-10V
[53]
MCO
4-20mA
[100]
Output
0–100 Hz (0–20 mA).
freq. 0-100
*
[101] Reference
Minimum reference - maximum reference (0–
Min-Max
20 mA).
[102] Feedback
-200% to +200% of parameter 3-03 Maximum
+-200%
Reference (0–20 mA).
[103] Motor cur.
0–Inverter maximum current
0-Imax
(parameter 16-37 Inv. Max. Current), (0–20 mA)
[104] Torque 0-
0–Torque limit (parameter 4-16 Torque Limit
Tlim
Motor Mode), (0–20 mA).
[105] Torque 0-
0–Motor rated torque (0–20 mA).
Tnom
[106] Power 0-
0–Motor rated power (0–20 mA).
Pnom
[107] Speed 0-
0–Speed high limit (parameter 4-13 Motor
HighLim
Speed High Limit [RPM] and
parameter 4-14 Motor Speed High Limit [Hz]),
(0–20 mA)
[108] Torque
(0–20 mA).
+-160%
[109] Out frq 0-
Fmax
[113] Ext. Closed
0–100% (0–20 mA).
Loop 1
[114] Ext. Closed
0–100% (0–20 mA).
Loop 2
MG20OB02
Programming Guide
6-50 Terminal 42 Output
Option:
[115] Ext. Closed
[116] Cascade
[117] Shaft
[118] Shaft
[130] Out frq
[131] Reference
[132] Feedback
[133] Motor cur.
.
max
[134] Torq.0-lim
[135] Torq.0-nom
[136] Power
[137] Speed
[138] Torque
[139] Bus ctrl.
[140] Bus ctrl.
[141] Bus ctrl t.o.
[142] Bus ctrl t.o.
[143] Ext. CL 1
[144] Ext. CL 2
[145] Ext. CL 3
[146] Cascade
[147] Main act
[148] Main act
[150] Out frq 0-
[156] Flow Rate
Danfoss A/S © 05/2018 All rights reserved.
Function:
0–100% (0–20 mA).
Loop 3
Reference
Power
Power
4-20mA
0–100 Hz.
0-100
4-20mA
Minimum reference–maximum reference.
4-20mA
-200% to +200% of parameter 3-03 Maximum
4-20mA
Reference.
0–Inverter maximum current
4-20mA
(parameter 16-37 Inv. Max. Current).
0–Torque limit (parameter 4-16 Torque Limit
4-20 mA
Motor Mode).
0–Motor rated torque.
4-20mA
0–Motor rated power.
4-20mA
0–Speed high limit (parameter 4-13 Motor
4-20mA
Speed High Limit [RPM] and
parameter 4-14 Motor Speed High Limit [Hz]).
4-20mA
0–100% (0–20 mA)
0–100%.
4-20 mA
0–100% (0–20 mA).
0–100%.
4-20mA
0–100%.
4-20mA
0–100%.
4-20mA
0–100%.
4-20mA
Ref.
4-20mA
val 0-20mA
val 4-20mA
Fmax
4-20mA
3