Danfoss VLT AQUA Drive FC 202 Programming Manual page 248

Software version: 3.30
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Parameter Description
35-25 Term. X48/7 Temp. Monitor
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/7. The temperature limits
can be set in parameter 35-26 Term. X48/7 Low Temp. Limit and
parameter 35-27 Term. X48/7 High Temp. Limit.
3
3
Option:
[0]
*
[1]
35-26 Term. X48/7 Low Temp. Limit
Range:
Size related
*
35-27 ]
35-27 Term. X48/7 High Temp. Limit
Range:
Size related
*
204 ]
3.28.4 35-3* Temp. Input X48/10 (MCB 114)
35-34 Term. X48/10 Filter Time Constant
Range:
0.005 s
[0.005 - 10
*
s]
35-35 Term. X48/10 Temp. Monitor
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/10. The temperature limits
can be set in parameter 35-36 Term. X48/10 Low Temp. Limit/
parameter 35-37 Term. X48/10 High Temp. Limit.
Option:
[0]
*
[1]
35-36 Term. X48/10 Low Temp. Limit
Enter the minimum temperature reading that is expected for
normal operation of the temperature sensor at terminal X48/10.
Range:
Size related
*
246
Function:
Disabled
Enabled
Function:
[ -50 - par.
Enter the minimum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/7.
Function:
[ par. 35-26 -
Enter the maximum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/7.
Function:
Enter the filter time constant. This is a
first-order digital low-pass filter time
constant for suppressing electrical noise
in terminal X48/10. A high time constant
value improves dampening, but also
increases the time delay through the
filter.
Function:
Disabled
Enabled
Function:
[ -50 - par. 35-37 ]
Danfoss A/S © 05/2018 All rights reserved.
®
VLT
AQUA Drive FC 202
35-37 Term. X48/10 High Temp. Limit
Enter the maximum temperature reading that is expected for
normal operation of the temperature sensor at terminal X48/10.
Range:
Size related
3.28.5 35-4* Analog Input X48/2 (MCB 114)
35-42 Term. X48/2 Low Current
Range:
4 mA
*
35-43 Term. X48/2 High Current
Range:
20 mA
*
35-44 Term. X48/2 Low Ref./Feedb. Value
Range:
0 ReferenceFeed-
backUnit
35-45 Term. X48/2 High Ref./Feedb. Value
Range:
100 Reference-
FeedbackUnit
35-46 Term. X48/2 Filter Time Constant
Range:
0.005 s
*
[ par. 35-36 - 204 ]
*
Function:
[ 0 - par.
Enter the current (mA) that corresponds to
35-43 mA]
the low reference value, set in
parameter 35-44 Term. X48/2 Low Ref./Feedb.
Value. Set the value at >2 mA to activate the
live-zero timeout function in
parameter 6-01 Live Zero Timeout Function.
Function:
[ par. 35-42 -
Enter the current (mA) that corresponds
20 mA]
to the high reference value (set in
parameter 35-45 Term. X48/2 High Ref./
Feedb. Value).
Function:
[-999999.999 -
Enter the reference or
999999.999
feedback value (in RPM,
*
ReferenceFeed-
Hz, bar, and so on) that
backUnit]
corresponds to the voltage
or current set in
parameter 35-42 Term.
X48/2 Low Current.
Function:
[-999999.999 -
Enter the reference or
999999.999
feedback value (in RPM,
*
ReferenceFeed-
Hz, bar, and so on) that
backUnit]
corresponds to the voltage
or current set in
parameter 35-43 Term.
X48/2 High Current.
Function:
[0.005 - 10
Enter the filter time constant. This is a
s]
first-order digital low-pass filter time
constant for suppressing electrical noise
in terminal X48/2. A high time constant
value improves dampening, but also
increases the time delay through the
filter.