Parameters 2-** Brakes - Danfoss VLT AQUA Drive FC 202 Programming Manual

Software version: 3.30
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Parameter Description

3.4 Parameters 2-** Brakes

3.4.1 2-0* DC brakes
Parameter group for configuring the DC brake and DC hold
functions.
2-00 DC Hold/Preheat Current
Range:
Function:
NOTICE
50
[ 0 -
%
160 %]
*
Parameter 2-00 DC Hold/Preheat Current is
not effective when parameter 1-10 Motor
Construction = [1] PM, non-salient SPM.
NOTICE
The maximum value depends on the rated
motor current.
Avoid 100% current for too long. It may
damage the motor.
Enter a value for holding current as a percentage
of the rated motor current I
parameter 1-24 Motor Current. 100% DC hold
current corresponds to I
This parameter holds the motor (holding torque)
or preheats the motor.
This parameter is active if [1] DC hold/Preheat is
selected in parameter 1-80 Function at Stop.
2-01 DC Brake Current
Range:
Function:
NOTICE
50
[ 0 -
%
1000 %
*
The maximum value depends on the rated
]
motor current. Avoid 100% current for too
long. It may damage the motor.
Enter a value for current as a percentage of the
rated motor current I
Current. 100% DC brake current corresponds to
I
.
M,N
DC brake current is applied on a stop command,
when the speed is lower than the limit set in:
Parameter 2-03 DC Brake Cut In Speed
[RPM].
Parameter 2-04 DC Brake Cut In Speed
[Hz], when the DC brake inverse function
is active, or via the serial communication
port.
The braking current is active during the time
period set in parameter 2-02 DC Braking Time.
MG20OB02
Programming Guide
set in
M,N
.
M,N
, see parameter 1-24 Motor
M,N
Danfoss A/S © 05/2018 All rights reserved.
2-02 DC Braking Time
Range:
Function:
10 s
[0 - 60 s] Set the duration of the DC brake current set in
*
parameter 2-01 DC Brake Current, once
activated.
2-03 DC Brake Cut In Speed [RPM]
Range:
Function:
NOTICE
Size
[ 0 - 0
related
RPM]
*
Parameter 2-03 DC Brake Cut In Speed
[RPM] is not effective when
parameter 1-10 Motor Construction =
[1] PM, non-salient SPM.
Set the DC brake cut-in speed to activate
the DC brake current set in
parameter 2-01 DC Brake Current after a
stop command.
When parameter 1-10 Motor Construction is
set to [1] PM non-salient SPM, this value is
limited to 0 RPM (OFF).
2-04 DC Brake Cut In Speed [Hz]
Range:
Function:
NOTICE
0.0 Hz
[0.0 - par.
*
4-14 Hz]
Parameter 2-04 DC Brake Cut In Speed
[Hz] is not effective when
parameter 1-10 Motor Construction =
[1] PM, non-salient SPM.
Set the DC brake cut-in speed for activation
of the DC brake current set in
parameter 2-01 DC Brake Current after a stop
command.
2-06 Parking Current
Range:
Function:
NOTICE
50
[ 0 -
%
1000 %]
*
Parameter 2-06 Parking Current and
parameter 2-07 Parking Time: Only active
if [1] PM, non-salient SPM is selected in
parameter 1-10 Motor Construction.
Set current as percentage of rated motor
current, parameter 1-24 Motor Current. Active
with parameter 1-73 Flying Start. The parking
current is active during the time period set in
parameter 2-07 Parking Time.
3
3
63