Parameter Description
1-93 Thermistor Source
Option:
3
3
[0]
None
*
[1]
Analog
Input 53
[2]
Analog
Input 54
[3]
Digital input
18
[4]
Digital input
19
[5]
Digital input
32
[6]
Digital input
33
1-95 KTY Sensor Type
Option:
[0]
KTY Sensor 1
*
[1]
KTY Sensor 2
[2]
KTY Sensor 3
1-96 KTY Thermistor Resource
Option:
[0]
None
*
[2]
Analog
input 54
1-97 KTY Threshold level
Range:
80 °C
[-40 - 140 °C] Select the thermistor sensor threshold
*
62
VLT
Function:
(selected in parameter 3-15 Reference 1 Source,
parameter 3-16 Reference 2 Source, or
parameter 3-17 Reference 3 Source).
®
When using VLT
PTC Thermistor Card MCB
112, always select [0] None.
Function:
Select the type of the thermistor sensor.
1 kΩ at 100 °C (212 °F).
1 kΩ at 25 °C (77 °F).
2 kΩ at 25 °C (77 °F).
Function:
Select analog input terminal 54 as a thermistor
sensor input. Terminal 54 cannot be selected as
thermistor source if otherwise used as reference
(see parameter 3-15 Reference Resource 1 to
parameter 3-17 Reference Resource 3).
NOTICE
Connection of thermistor sensor
between terminals 54 and 55 (GND). See
chapter 3.3.15 PTC Thermistor Connection.
Function:
level for motor thermal protection.