Advertisement

Parameter Description
13-02 Stop Event
Option:
[43]
OK Key
[44]
Reset Key
3
3
[45]
Left Key
[46]
Right Key
[47]
Up Key
[48]
Down Key
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[75]
Start command
given
[76]
Digital input x30/2
[77]
Digital input x30/3
[78]
Digital input x30/4
[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
[90]
ECB Drive Mode
[91]
ECB Bypass Mode
[92]
ECB Test Mode
[93]
Emergency Mode
[94]
RS Flipflop 0
[95]
RS Flipflop 1
[96]
RS Flipflop 2
[97]
RS Flipflop 3
[98]
RS Flipflop 4
[99]
RS Flipflop 5
[100] RS Flipflop 6
[101] RS Flipflop 7
[102] Verifying Flow
[103] Relay 1
116
®
VLT
AQUA Drive FC 202
Function:
This event is true if [OK] is pressed.
This event is true if [Reset] is pressed.
This event is true if [◄] is pressed.
This event is true if [►] is pressed.
This event is true if [
] is pressed.
This event is true if [
] is pressed.
Use the result of comparator 4 in the
logic rule.
Use the result of comparator 5 in the
logic rule.
Use the result of logic rule 4 in the
logic rule.
Use the result of logic rule 5 in the
logic rule.
Use the result of timer 3 in the logic
rule.
Use the result of timer 4 in the logic
rule.
Use the result of timer 5 in the logic
rule.
Use the result of timer 6 in the logic
rule.
Use the result of timer 7 in the logic
rule.
See parameter 13-15 RS-FF Operand S,
parameter 13-16 RS-FF Operand R.
Danfoss A/S © 05/2018 All rights reserved.
13-02 Stop Event
Option:
Function:
[104] Relay 2
[105] Relay 3
[106] Relay 4
[107] Relay 5
[108] Relay 6
[109] Relay 7
[110] Relay 8
[111] Relay 9
[112] System On Ref
[125] Digital input x46/1
[126] Digital input x46/3
[127] Digital input x46/5
[128] Digital input x46/7
[129] Digital input x46/9
[130] Digital input
x46/11
[131] Digital input
x46/13
[140] ATEX ETR cur.
warning
[141] ATEX ETR cur.
alarm
[142] ATEX ETR freq.
warning
[143] ATEX ETR freq.
alarm
3.12.2 13-1* Comparators
Comparators are used for comparing continuous variables
(that is output frequency, output current, analog input, and
so on) to fixed preset values.
Par. 13-11
Comparator Operator
Par. 13-10
Comparator Operand
=
TRUE longer than.
Par. 13-12
Comparator Value
. . .
. . .
Illustration 3.41 Comparators
There are digital values that are compared to fixed time
values. See the explanation in parameter 13-10 Comparator
Operand. Comparators are evaluated once in each scan
interval. Use the result (true or false) directly. All
parameters in this parameter group are array parameters
with index 0–5. Select index 0 to program comparator 0,
select index 1 to program comparator 1, and so on.
MG20OB02