21-13 Ext. 1 Reference Source
Option:
3
3
[0]
No function
*
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20] Digital pot.meter
[21] Analog input X30/11
[22] Analog input X30/12
[23] Analog Input X42/1
[24] Analog Input X42/3
[25] Analog Input X42/5
[29] Analog Input X48/2
[30] Ext. Closed Loop 1
[31] Ext. Closed Loop 2
[32] Ext. Closed Loop 3
[33] PCD Bus Reference
[35] Digital input select
21-14 Ext. 1 Feedback Source
Option:
[0]
No function
*
[1]
Analog Input 53
[2]
Analog Input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog Input X30/11
[8]
Analog Input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[15]
Analog Input X48/2
[99]
Normal Feedback
[100] Bus Feedback 1
[101] Bus Feedback 2
[102] Bus feedback 3
[104] Sensorless Flow
172
®
VLT
AQUA Drive FC 202
Function:
This parameter defines which input
on the frequency converter should be
treated as the source of the reference
signal for the closed-loop 1 controller.
Analog input X30/11 and analog
input X30/12 refer to inputs on the
®
VLT
General Purpose I/O Card MCB
101.
Function:
This parameter defines which input
on the frequency converter should
be treated as the source of the
feedback signal for the closed-loop 1
controller. Analog input X30/11 and
analog input X30/12 refer to inputs
®
on the VLT
General Purpose I/O
Card MCB 101.
Danfoss A/S © 05/2018 All rights reserved.
21-14 Ext. 1 Feedback Source
Option:
Function:
[105] Sensorless Pressure
[200] Ext. Closed Loop 1
[201] Ext. Closed Loop 2
[202] Ext. Closed Loop 3
21-15 Ext. 1 Setpoint
Range:
0
[-999999.999 -
ExtPID1Unit
999999.999
*
ExtPID1Unit]
21-17 Ext. 1 Reference [Unit]
Range:
0 ExtPID1Unit
[-999999.999 -
*
999999.999
ExtPID1Unit]
21-18 Ext. 1 Feedback [Unit]
Range:
0 ExtPID1Unit
[-999999.999 -
*
999999.999
ExtPID1Unit]
21-19 Ext. 1 Output [%]
Range:
Function:
0 %
[0 - 100 %] Readout of the output value for the closed-
*
loop 1 controller.
3.18.3 21-2* Closed Loop 1 PID
21-20 Ext. 1 Normal/Inverse Control
Option:
Function:
[0]
Normal Reduces the output when feedback is higher than
*
the reference.
[1]
Inverse Increase the output when feedback is higher than
the reference.
21-21 Ext. 1 Proportional Gain
Range:
Function:
0.50
[0 - 10 ] The proportional gain contains the factor
*
indicating the number of times the error
between the setpoint and the feedback signal is
to be applied.
If the product error times gain jumps with a value equal to
what is set in parameter 3-03 Maximum Reference, the PID
controller tries to change the output speed equal to what
is set in parameter 4-13 Motor Speed High Limit [RPM]/
Function:
The setpoint reference is used in
extended 1 closed loop. Ext.1
Setpoint is added to the value
from the Ext.1 Reference Source
selected in parameter 21-13 Ext.
1 Reference Source.
Function:
Readout of the reference
value for the closed-loop
1 controller.
Function:
Readout of the feedback
value for the closed-loop
1 controller.