3.2 Parameters 0-** Operation and Display

Parameters related to the basic functions of the frequency
converter, function of the LCP keys, and configuration of
the LCP display.
3.2.1 0-0* Basic Settings
0-01 Language
Option:
Function:
Defines the language to be used in the
display.
The frequency converter is delivered with
2 different language packages. English and
German are included in both packages.
English cannot be erased or manipulated.
[0]
English
Part of language packages 1–2.
*
[1]
Deutsch
Part of language packages 1–2.
[2]
Francais
Part of language package 1.
[3]
Dansk
Part of language package 1.
[4]
Spanish
Part of language package 1.
[5]
Italiano
Part of language package 1.
[6]
Svenska
Part of language package 1.
[7]
Nederlands
Part of language package 1.
[10] Chinese
Part of language package 2.
[20] Suomi
Part of language package 1.
[22] English US
Part of language package 1.
[27] Greek
Part of language package 1.
[28] Bras.port
Part of language package 1.
[36] Slovenian
Part of language package 1.
[39] Korean
Part of language package 2.
[40] Japanese
Part of language package 2.
[41] Turkish
Part of language package 1.
[42] Trad.Chinese
Part of language package 2.
[43] Bulgarian
Part of language package 1.
[44] Srpski
Part of language package 1.
[45] Romanian
Part of language package 1.
[46] Magyar
Part of language package 1.
[47] Czech
Part of language package 1.
[48] Polski
Part of language package 1.
[49] Russian
Part of language package 1.
[50] Thai
Part of language package 2.
[51] Bahasa
Part of language package 2.
Indonesia
[52] Hrvatski
Part of language package 2.
MG20OB02
Programming Guide
0-02 Motor Speed Unit
Option:
[0]
RPM Select to show motor speed variables and parameters
*
[1]
Hz
0-03 Regional Settings
Option:
[0] Interna-
tional
[1] North
America
Danfoss A/S © 05/2018 All rights reserved.
Function:
NOTICE
This parameter cannot be adjusted while the
motor is running.
The information shown in the display depends on the
settings in parameter 0-02 Motor Speed Unit and
parameter 0-03 Regional Settings. The default settings
of parameter 0-02 Motor Speed Unit and
parameter 0-03 Regional Settings depend on to which
region of the world the frequency converter is
supplied.
NOTICE
Changing the motor speed unit resets certain
parameters to their initial value. Select the
motor speed unit before modifying other
parameters.
using motor speed (RPM).
Select to show motor speed variables and parameters
using output frequency (Hz).
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
The display output depends on the settings in
parameter 0-02 Motor Speed Unit and
parameter 0-03 Regional Settings. The default
settings of parameter 0-02 Motor Speed Unit and
parameter 0-03 Regional Settings depend on which
region of the world the frequency converter is
supplied to. Reprogram the settings as required.
The settings not used are made invisible.
Sets parameter 1-20 Motor Power [kW] units to
[kW] and the default value of
parameter 1-23 Motor Frequency to 50 Hz.
Sets parameter 1-21 Motor Power [HP] units to [hp]
and the default value of parameter 1-23 Motor
Frequency to 60 Hz.